i 1G >
ELECTRIC Instructions
Ee PRC Commissioning
| SS
Type UIT
| oemCOMMISSIONING
INSTRUCTIONS
TYPE VTT
DANE I
AOLIntroduction :
Thie manual covers the commissioning and maintenance instruction for the datinite
time delay ralays type VIT.
‘umber of operations and consistent accurecy with little or na maintenance over fon
‘The Type VTT time delay relay is particulerly suitable in application requiring lerge
poriods.
10 is also commonly used in industrial processes plant. Static cltcults hava been designed to
perform with complete reliability in electrically hostile onvironments offen encounterod ir
electrical power stations and substationa and also over a vory wido rango of ambient
temperatures.
24.1
2.2.2
General Description ; Types VITI1/VITI2
A stabilised voltage is spplied to a resistance capacitance circuit and the potential
developed across tho capacitor is epplied to 2 transistor switching circuit
which operates an attracted armature relay when tho potential reaches the trigger level.
‘The time dolay is varied by altering the rasistence value in the resistance-cepacitance
circuit by # potentiometer calibratad in saconde. A circuit to protect the transistor from
damage dus to high peak transients in the supply voltae is incorporated. A diode is
also fitted in the elrcuitry 19 take care of inadvertent connection of supply with
reversed polarity. Ref, Fig. 1
Typo VITI1/VTT14 unite have 2 dolayed pick-up i. timing is startsd by closing
an initiating contact and the output relay is enargised at the end of the sot time. The
unit reseis when the initiating contact re-opens.
Type VITI2/VIT15 unite have a dolayed drop-oif ie. the output relay ic normally
energised. Timing is started by opaning an initiating contact and the output relay is
de-norgised at the snd of the sat time, The unit resets when the initiating contact is
roclosod.
Type VIT14, with time delayed pick-up
‘As shown in Figure 2, the YTT14 relay'is initiated when the power supply to the ralay is
switched on, starting a CMOS resistance/capacitance oscillator which generates a
‘square wave utput to a binary coded decimal, counter
I is also arranged that when the D.C. or ractified A.C. supply first appears, the counter
is set immediately to zero before the count commences,
Tho required time doiay ic presot by adjusting ¢ group of throo binary coded docimal
switches. The time delay setting Is selected from within the 1000/1 tange by
adjusting the thumbwheel protuding from sech switch Although the switch output
to the associated circuitry is in binary form, the thumbwhesls aro celibrated for
convenience in decimals, each switch providing a successive decade of 0 to 9.
32.2.3
54
When the count from the instant of relay initiation reaches the setling of tha thumb-
wheel switches, es detected by a comparator, tho latter produces @ signal which
operatas the output element and also stops the oscillator. The relay resets nominally
instantaneously when the initiating contact is re-opened,
Typical circuit diagrams for the VTT14 relay are shown in Figure 3,, from which it may be
noted that the initisting contact closes the rectified D.C, circuit, rather than
the input circuit, in the design for use with an A.C. power supply This is to
‘ensure that the transient time delays normally inherant in the filter circuit
to smooth the rectified D.C. do not cause timing errors
‘Typo VIT15, with time delayed drop-off
As indicated in Figure 4. the VIT15 relay has a similar circuit, but application of tha
power supply causes the relay to pickup nominally Instanteneously.
‘Tho drop-off timo delay ia initiatad by opsning an extemal break contact connected in
the inhibit control circuit to the oscillator.
4m this ratay, the output from the comparator disappears at the end of the set time dolay.
Until then the output element is continuously energised,
‘Typical circuit diagrams for the VTT15 relay are shown in Figuro 5.
Location :
The location should be dry, clean, free from dust and excessive vibrations and reasonably
well illuminated to facilitate inspection,
Mounting:
‘The relay caso should be mounted in a vertical panel surface (within -£5%%), sa that the
Unit is proctically horizontal.
Commissioning:
The following tests are recommended for tho initial commissioning of VIT rolaye;
i) General Inspection
ng checks
iif) Insulation tests
iv) Timing teste
v) Operational checks
ral Inspection:
Wipo away any dust that has collacted on outside of the relay before opening the cover.
Make # general inspection of the ralay to ensure thet all moving parts are frea to meva
45.2
58
5S
6.0
61
and that there are no signs of damage anywhere. Check that there are no loose
connections of terminals and that the equipment is clean and free from dust. General
inspection is normally carried out sfter disconnecting the trinping supply.
Wiring Check :
Make a thorough check of the Internal and extemal wiring of the relay. The internal
‘witing can bo checked by roferonce to the relay wiring diagram which fs supplied for
each relay. The extemal wiring should be checked with the help of schematic
diagrams (showing reference number of intorconnscting wires, relay terminal nos, etc:),
supplied by the rolay panol manufacturers
Insulation Test :
Isolate the wiring from earth. Bind all rolay terminals together and moasure the
insulation resistance to earth with 1000V magger. Reconnect all wiring according to
the schematic diagram, It is especially importent that DC supplies are wired with
correct polaiity
Timing Test :
To twst relays mounted in dravout cases, no alteration need be made to the relay or 10
tho switchboard wiring. This is automatically done by the test plug MPB which is
inserted between the contact fingers of the cradie and case,
If the relay ie mounted in a non-drayout casa, test connections must be made directly
to the relay and the external circuit isolated.
Semple tost circults for VIT11 & 12 are shown in Figs, 6 & 7 and the correct one for
the relay under test should be selected, Similar tasts can ba carried out on VIT14 &
\TT15 with reference to fig. 2,3,4,5 whichever is relevant,
‘Tha timing can be checked at various settings. The actual timing should be within
4£5% of the setting value.
Trip and Alarm Circuit Check +
During the timing tests, tho tip, intortrip and elarm circuits ato usually rondored in-
operative by removal of isolating links, relay trip latches etc. It is thus essential that
‘on completion of thess tests, tha tripping, intar-triaping and elarm circuits are chacked.
Close the ralay contacts by hand fter restoring all the links and latches to their
original positions and check that the corect sequence of events is initiated and the
right alarm comes on.
MAINTENANCE
Inspection :
Drawout Case
To inspect the rmlay loosen the cover nuts and remove the cover. Rotate the latches,
‘which then provide finger holes for withdrawing the relay chassis. The action of rote~
ting the latches oparates a switch which isolates the trip circuit.
562
68
Non-Drawout Case:
To insnect the relay lodsen the caver nuts and remove the caver. If necessary remove
the nameplate.
Dust Filter :
Dust filters should be examined at least once 8 yoar. IM necessary the filter element
should be cleaned as follows.
Romove the filter unit from the relay case, Remove the white/black nylon filter alemant,
‘Wash the olemont in detergent, ring and dry. Dip the element in light machine oll and
Shaka off excess oii, Replace the filtar unit in the relay ease.
Attracted Armature Units :
‘The attracted armature relays aro very simpls and robust and taraly go wrong. Unless
the relay is not operating correctly or damage has occured it should bo loft undisturived,
Injaction tests can de carried out once a year, if dasitad, to verity that the relay oporatos
satisfactorily, and thet the pick-up is within the spscitied tolorance,
Contacts should bo examined to ensure that thoy are clean; if it is necessary to clean
them a burnishing too! should be used. It is most important that {iles or abrasive
‘materials ara NOT used for cleaning contacts.
‘Tho English Electric ralay too! kit contains burnishing tool suitable for leaning
Contacts, Details of this kit and instructions for its use are given in Publication
5138. If thacontacts are badly damaged, either retum the rslay to the factory ot
replace the contacts and proceed as set out in ‘Mechanical settings’
Mechanical Settings
Attracted armature units will not function correctly unless contact pressures, armature
aps etc., are within the manufacturing tolerances, These settings will not change
during normal use and it is not necessary to make any routine checks on them. However,
if parts have been repleced oF repaired the settings mus! be readjusted,
Contact:
When replacing contacis thay chould be bent slightly, adjacent 10 the insulating blocks,
80 that they exert a pressure on the push-rads or support arms.
Bofore commencing with the settings ensure that :
The armature platform is loval
The bottom contacts are sitting on the push-tod shoulders
‘The push-rods are vartical
Tho contest tips are level when viewed from the front
68 010" fecler gauge between the armature and the core face, close the amature
by exerting pressure above the centra line of the cere face. Adjust the top contact and
Support so that the contacis just touch. This gives a follow thraugh of 020".
‘Set the contact gap to .070"/.080" by adjusting the armature stop.
Using a gramme gauge. check that the top contact lifts off [ts support whan a pressure
of 16/20 grammee is exerted and that the bottom contact touches the top contact when
a pressure of 20/25 grammes is applied. Tho pressuras should bo tekon with tho arm
of the gauge ploced under the tips of the contact. Any adjustmont is obtained by
increasing or decreasing tho bend put into the contact at the start of the sstting proce
dure. Chock all sattings.
6.4 Operation indicators :
The sheild must be pertectly fre0 to drop whan tha contacts are about ta touch of just
before they touch, but never aftar. This enables that the contacts do nat close without
the operation indicator being displayed.
Adjustment is made by bending the spring cateh, which locates ina notch in the arma-
ture,
7.0 RELAY TECHNICAL DATA:
7.1 Timing ranges
TAA VITH and IT 12
‘The following sianderd settings. continuously variable, time dalay on pick-up ar reset
are availablo,
005 — 05 Secs
o1 = 1.0
o5 — 50
10 — 10.0
25 — Bo
60 — 60.0
12.0 — 120.0
30.0 — 3000
+ TAQ VIT 14 and VIT 15
1) 0.110999 secs
ft) 1 to 909 secs
iii) 10 t 9990. secs
zi72
724
122
Voltage Rating :
D.C. Supply - DC voltage 20, 110 or 220 volts continuous. Satisfactery operation is
‘maintained et between 80%, and 120% of rated voltage.
Units for use on 110 oF 220 volts are supplied with a suiteble external resistor.
AC Supply = 110, 240 or 416 volts continuous. Relays suitable for operation
from AC supply have a built-in power pack. Satisfactory operation Is maintained at
betweon 80% and 110% of rated voltage.
7.3 Accuracy :
7.3.4 VITH &VTTI2
Within 36% of setting or +10 milliseconds whichever is greater at rominal voltage
and an ambient temperatura within the range of 10°C and 30°C,
Within 5% of sotting or lissconds whichever (s greater for supply voltage
variation of +20%,
Operating temperature range -5°C to +-50°C.
7.3.2 VITIA &VTTIS +2% of satting or +30ms, ~Oms whichover is greater
7.4 Repeatability :
7.4.4 VITM &VTTIZ
‘The unit will repeat excessive timings within +1% or +10 milliseconds whichever is
greater whon allowed to completely reset.
‘When allowed to reset to within 3% of the maximum operating time, tha accuracy is
within £5% on the next successive timing operation.
7.4.2 VIT14 & 15 The unit will repest successive timings within 40.5% of £5 ms which-
ever is greater.
7.8 Burden:
Burden is imposed when the relay is in the energised condition.
78.4 VITI & VTTI2
Typical burden values are :
D.C, Volts 30v 110v 220
Burden (Watts) 1.28 4.48 94
AC. Voits 410 240 415
Burden (VA) 24 23 267.6.2, VIT14/VTT 15 Burden:
Rolay or
element Supply
‘ype
IT 14 de.
(delayed
pickup) ae,
VIT 16 de
(delayed
drop-off) ac
nding current
quicgeont
85
10
65
Max. current
(mA) during
operation
40.
65
45
66
7.8. Contacts :
7.6.1, VTT11.& VTT 12
Four pairs of sol reset contacts in any combination of normally apen or normally closed
with a maximum of 2 NC contacts are provided on the output attracted armature unit
Of VIT 11 relays, For VIT 12 rolaye 3 paire of
normally closed contacts are avallablo.
VIT 41 unit only,
Note; Relays with heavy duty magnetic blow out contacts
7.6.3, Contact Ratings
i resat contacts with maximum of 2
Hand rosot contacts ean be provided on
also available on request.
Make & Carry Make & Carry Break
continuously for 3 seconds
AG. 1250 VA with 7500 VA with 1250VA with
maximum of BA maximum of 30 maximum of 5A
and 660 vols amps and 660V and 660
D.C. 1250 Watts 7500 watts 100 watts
max, with max, (resistive) 50
of 5A and of 30 ampe Wi
660 volts and 660 volts with max. of 5A
and 680 volts7.6.2.
VIT 14 & VTT 15
7.6.2.1, Contacts :
Relay or
element type
vin
(dolayod
pick-up)
vit 45
(delayed
drop-orf) |
element
Output | Contacts hs
‘Auactod | 9 Alpsits of mato, break,
armatura salf or hand resetting.
in any combination or
2 change-over contacts
Attracted 3 pairs of make, break, solf or
‘ormaturo hand resetting, in any
combination ef 1 change
‘over plus 1 N/O. contact.
WT.
Operation indicator
‘A hand raset mechanical flag operation indicator can be provided on the cutpur relay,
10UNITIATING
qua
eee
TRANSIENT SUPRESSOR
FIG.1. BASIC CIRCUIT DIAGRAM FOR VIT1 RELAY.
1"Sie 00D | Jeowranazonbed
SiStuaron [7] BECwA
Ean
BevAVED rick UP
Nociaeel
a Aer
Figure SIMPUEITD SEOUENCE DIAGHAM FOR TYPE VITTA RELAY WTI TIM
by Fon AE town SUPPLY
Figute @ TYPICAL CIRCUIT DIAGRAMS FOR TYPE VTT14 RELAYS
12b) FOR A powen suPrLy
amany erany
eoore Jcouranatonfe] Gove
Becht. - Bech
counteh Sirens
gurrur
pst agen | RLEMENT
ine eves
‘ouca st
"in. 4 SIMPLIFIED SEQUENGe DIAGRAM FOR TvPE VTT15 RELAY WiTH
That DELAYED DROP OFF
2 nae
‘
1
1
'
1
'
1
'
'
by Faw o€ powcr sur
cura ?
Sipsetr
: tas
S;
1
1
1
'
1
1
1
'
a
za 6
Fg D TYPICAL CIRCUIT DIAGRAMS FOR TYPE \TTI6 RELAYS
13digital — switch
Timer
Fig 6 Typical Timing Tost Circuit for VTT 11
relay with delay on pick-up,
imer— switch
Fig 7 Typical Timing Test Circuit for VIT 42
relay with delay on drop-off,
relay and 19 & 20 for 1D case relay.
14
Bo & a
jairecooaar ety w cee tot 9 open ten
| depending upon the use of
Jo oF nic contact respactively,
4 palte of auxiliary contacts
supply are given as standard,
- aside
* Close to stop or onan to stop
Gepending upon tha use of
le or nfa contact respectively.
4 pairs of auxiliary contacts
are given as standerd.
‘The terminal numbers read S & 6 for 4 N ceseatta 4
THE ENGLISH ELECTRIC COMPANY OF INDIA LTD.
HEAD OFFICE: PALLAVARAM. MADRAS-600083
WORKS: PALLAVARAM, MADRAS-600 043 G HOSUR-636 125
orree
PO 80K 2540, BaNGaLone $50006 @ 0.80% 117, LUCxtOW : 728001
PO Box 11112, BOMBAY - 60020 @ FO 80% 3308 MADRAS: 600036
PO, 60x 2226, CALCUTTA “700001 @ PO. BOX 207, NEW DELHI. 1000
erry