You are on page 1of 2

PT.

KABELINDO MURNI Tbk

NAYY 0.6/1 kV
Aluminium Conductor, PVC Insulated, PVC Sheathed

1.
2.
3.
4.

Conductor
Insulation
Inner Sheath
Sheath

:
:
:
:

Aluminium Conductor
PVC Insulation
PVC Inner Sheath
PVC Sheath

PVC LOW VOLTAGE CABLE


TECHNICAL DATA
Spec

Cu

Specification : SPLN 43 -1

Conductor Shape : rm = Stranded Circ

IEC 60502 - 1

Non - Compacte

VDE 0271

sm = Shaped, Stra
Conductors

DCV

DC Test Voltage : 3,5 kV for 5 minute


Power cables for energy supply are installed in open, underground, indoors, in cable ducts,
APL

power stations, for industry and distribution boards, in subscriber networks, where mechanical
damages are not to be expected.

DIMENSIONAL & MECHANICAL DATA

SIZE
mm2

16
25
35
50
70
95
120
150
185
240
300

No.of wire
and Shaped
Of Conductor
pcs

shape

Nominal Thickness

Approximately
Overall
Net.
Insulation Outer Sheath
Diameter Weight
mm

mm

1.0
7

rm

1.2
1.4

19

1.6
sm
37

1.8
2.0
2.2
2.4

1.8
1.9
2.1
2.2
2.3
2.5
2.7
2.9
3.1

CORE

Min.
Bending
Diameter

Std.
Delivery
Length
m

mm

kg/km

mm

23
27
30
33
37
42
46
51
56
64
70

705
994
1,225
1,426
1,940
2,411
2,913
3,539
4,353
5,663
6,765

420
490
540
600
670
760
830
920
1,010
1,150
1,260

1000

500
250

ELECTRICAL DATA

SIZE

DC Resistance
Current Carrying
at 20C
Capacity at 30C
Conductor Insulation
In Ground
In Air
(Max)
(Min)

Conductor Short Circuit


Current Capacity at :
0.1
0.5
1.0
second second
second

AC
Voltage
Test

mm

Ohm/km

16
25
35
50
70
95
120
150
185
240
300

1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100

M.ohm.km

40

30

20

kA

kA

kA

kV/5 min.

92
111
130
161
194
221
248
282
328
377
436

82
100
119
152
186
216
246
285
338
400
472

3.85
6.01
8.41
12.0
16.8
22.8
28.8
36.0
44.5
57.7
72.1

1.72
2.69
3.76
5.37
7.52
10.2
12.9
16.1
19.1
25.8
32.2

1.22
1.90
2.66
3.80
5.32
7.22
9.12
11.4
14.1
18.2
22.8

3.5