FILE: DUCT7079 Example 6.

9 Chadderton

Duct sizing for rectangular sheet metal air ducts

Air Density= 1.2 kg/m4 Key to columns: Enter data under =====, calculated data under ****

A B C D E F G H I J K L M N O P Q R S T U V W
Section Length Q max v max D p Dia max Q Q error Likely Likely Rectangular size Equiv. Actual pv Fitting Duct(Dp) Fitting Plant Dp Total Start pt End pt Index
l dia v width depth dia v k value kpv Dp
(m) (m3/s) (m/s) (Pa/m) (m) (m3/s) % (m) (m/s) (mm) (mm) (mm) (m/s) (Pa) (Pa) (Pa) (Pa) (Pa) (Pa) (Pa)
===== ===== ===== ===== ===== **** **** **** ===== **** ===== ===== **** **** **** ===== **** **** ===== **** **** **** =====
1-2 0 1.75 2.5 0.07 0.944 1.76 -0.51 0.95 2.5 900 850 963 2.4 3.5 4.5 0 15.6 0.0 15.6 0 -15.6
2-3 3 1.75 3.5 0.16 0.798 1.76 -0.51 0.8 3.5 700 750 798 3.5 7.4 0.04 0.48 0.3 95.0 95.8 -15.6 -111.4
3-4 0 1.75 10 2.16 0.472 1.75 0.11 0.5 8.9 450 450 496 9.1 49.4 0.04 0 2.0 0.0 2.0 -111.4 -113.3
fan 0 1.75 10 0 0.472 na na 0.5 8.9 450 450 496 9.1 49.4 0 0 0.0 0.0 0.0 -113.3 -113.3
4-5 0 1.75 6 0.6 0.609 1.75 0.20 0.6 6.2 400 800 616 5.9 20.7 0.3 0 6.2 0.0 6.2 86.0 79.8
5-6 16 1.75 6 0.6 0.609 1.75 0.20 0.6 6.2 400 800 616 5.9 20.7 0.35 9.6 7.3 0.0 16.9 79.8 62.9
6-7 0 0.5 6 1.35 0.326 0.51 -2.29 0.6 1.8 400 400 440 3.3 6.5 1.25 0 8.1 50.0 58.1 62.9 4.9
7-8 15 1.25 6 0.75 0.515 1.26 -0.80 0.6 4.4 400 550 515 6.0 21.6 0.09 11.25 1.9 50.0 63.2 4.9 -58.3

O17 49.4 Sum 257.7


T21 63.2
E28-E27 13.8
C17 1.75