Whats the Difference?

Panelboard

Switchboard

Certifications
UL 67 Panelboards

UL 891

UL 50 Cabinets and Boxes

NEMA PB2

NEMA PB1
Features
Flush or surface wall-mounted

Free-standing

Front access only

Front or rear access

Box, interior, trim

Frame, buses, overcurrent devices, instrumentation, covers

1-Phase or 3-Phase

3-Phase or 1-Phase (rare)

Fixed mounted breakers

Fixed or draw out mounted power breakers

Through-feed or sub-feed lugs feed multiple panels

Horizontal bus feeds multiple sections

Pow-R-Line 1a, 2a, and 3e chassis measured in circuits; PowR-Line 3a and 4 measured in X-space

Layout measured in X-Space

Fully or series-rated

Full selection of surge and customer metering

Limited surge and customer metering options

NEMA 1 and 3R standard

NEMA 1, 2, 3R, 4, 4x, 4xNM, and 12 enclosure offerings as


standard

More internal wiring/working space

Typically fully-rated

Overcurrent Devices
Miniature and molded case circuit breakers, UL 489

Molded case circuit breakers, UL 489

Fusible switches, UL 98

Power circuit breakers, UL 1066

1200A maximum main

Fusible switches, UL 98

1200A maximum group mounted feeders

5000A maximum main

Typically bolt-on

Group mounted feeders up to 2000A


Individually mounted feeders up to 4000A

The Bottom Line


Wall-mounted, lower main amperage, lower capacity feeder
breakers, more NEMA enclosures as standard and fewer
accessory options

Free-standing, higher main amperage, higher capacity feeder


breakers, fewer standard NEMA enclosures, more accessory
options