Media Search - RENR2480 - VR6 Voltage Regulator

Page 1 of 2

Shutdown SIS
Previous Screen
Product: NO EQUIPMENT SELECTED
Model: NO EQUIPMENT SELECTED
Configuration: NO EQUIPMENT SELECTED

Systems Operation
VR6 Voltage Regulator
Media Number -RENR2480-04

Publication Date -01/12/2007

Date Updated -17/12/2007

i02652153

Series Boost
SMCS - 4467

Illustration 1

g01332287

Typical Example of a Series Boost Module

A series boost module is an option. Series boost allows the self-excited generators to stay on the line
(approximately 10 seconds) when there is a short in the generating circuits or in the load circuits.

https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe...

10/8/2010

Media Search - RENR2480 - VR6 Voltage Regulator

Page 2 of 2

Therefore, circuit breakers in the load distribution system have the opportunity to trip in sequence. When
circuit breakers trip in sequence, there is less chance for a total loss of power of the entire electrical system.
Series boost consists of the series boost module and current transformers (CT).
Voltage sensing and power are applied to the series boost module from the voltage regulator sensing
terminals 22 and 24.
When the sensed voltage is within normal limits, an electrical signal is sent to the gate of a triac which is
located in the series boost module. This triac short circuits the current transformer. This prevents any series
boost during normal operation.
If there is a short circuit in the system that causes the voltage at the regulator sensing terminals to drop to a
low value, the control signal to the gate of the triac will be turned off. Current from the current transformer
will be rectified. This current will be applied directly to the exciter stator. This field current will be enough
to give at least three times full load current into a short circuit. After approximately ten seconds, a timer
within the series boost module will again cause a control signal to be applied to the gate of the triac. The
triac will short circuit the current transformer. Current flow to the exciter stator will be zero, until the short
circuit is corrected.
Note: A PM generator will provide a similar short circuit current characteristic.