@ weseronezane LP Any Engineering SPECIFICATION FOR BEDD DEMONSTRATION H2 PSA oar isaue: ont 12 201 Job No. : A11226 Page : 40 of 47 5.1.5.2. 5.1.5.3. 5.1.5.4. normally d) Screw compressors, conforming to API Standard 619 (latest edition), can be specified in special cases where found to have an operating, economic or maintenance advantage over other choict's. Screw compressors shall not be spared but specifications shall be given for a spare rotor. Driver selection shall be as for centrifugal compressors. COMPRESSOR CONTROLS Compressor control (interlocks and shutdown) shall be PLC based and located incontrol room. PLC make shall be standardized for entire unit Only start-up operation is carried out from local panel and normal control from central control room. COMPRESSOR SEALS Dry gas seals are preferred. irectional and inter-changeability in Drive-end and driven end to be considered Unit designers shall address issues such «as common or individual compressor suction and interchange KODs, common or individual compressor inter-stage coolers and surge control etc. as part of unit operability and cost saving factors. 5.2, PIPING Engineering Design Basis shall define the detailed design requirements for