D E E P S E A E L E C T R O NI C S
5 5 1 0 I N S T AL L AT I O N I N S T R U C T I O N S
Front Panel Configuration Editor (Factory default settings are shown in bold italicised text)
Timers
Generator
Engine
Displa y
AC System
Values
0bar - 4bar (1.17bar)
0bar - 4bar (1.03bar)
80C - 140C (115 C)
80C - 140C (120 C)
67C - 137C (disabled)
0% - 100% (disabled)
0 -10s (0s)
0 - 60m (5s)
0 - 60m (0s)
0 - 60s (10s)
0 - 60s (10s)
0 - 30s (10s)
0 - 10s (0s)
0 - 60m (0s)
0 - 60m (30s)
0 - 60m (1m)
0 - 30s (30s)
0- 10m (1m)
0 -10m (1m)
0- 30s (2s)
50V-360V ph-N (184V)
50V-360V ph-N (196V)
52V-330V(230V)
50V-360V ph-N (265V)
50V-360V ph-N (277V)
0Hz - 75Hz (40Hz)
0Hz - 75Hz (42Hz)
0Hz - 74Hz (50Hz)
0Hz - 75Hz (55Hz)
0Hz - 75Hz (57Hz)
100% - 200% full load rating (100%)
50% - 300% full load rating (200%)
0% - 200% full load rating (35kW)
1% - 100% full load rating (10%)
0RPM - 6000RPM (disabled)
0RPM - 6000RPM (disabled)
0RPM - 6000RPM (disabled)
0RPM - 6000RPM (disabled)
0% - 10% (0%)
0V - 40 V (10V)
0V - 40 V (30V)
0V - 40 V (6V)
ENGLISH, OTHERS
Enable, Disable
Enable, Disable
3 Phase 4 wire
1 Phase 2 wire
3 phase 3 wire
2 phase 3 wire L1 & L2
3 phase 4 wire EDISON DELTA
2 phase 3 wire L1 & L3
0A - 8000A (500A)
Enable, Disable
Droop %
0% - 5%
Displa y
Contrast
Clock
Misc.
CT
Power
053-008
ISSUE 9
the Stop/Reset
button.
EDITING A PARAMETER
Press the + and buttons to cycle to the parameter you wish to change.
Press the button to enter edit mode. When in edit mode (indicated by the
flashing parameter)
Pressing the + and buttons will adjust the parameter to the desired value.
To exit the front panel configuration editor at any time, press the Stop/Reset
have saved any changes you have made by pressing the button first.
NOTE:
NOTE: - When the editor is visible, it is automatically exited after 5 minutes of inactivity to
ensure security.
NOTE:
NOTE: - The PIN number is automatically reset when the editor is exited (manually or
automatically) to ensure security.
Ensure the engine is at rest and the module is in STOP mode by pressing
NOTE:
NOTE: - More comprehensive module configuration is possible using the 5xxx series PC
configuration software in conjunction with the P810 PC interface. Please contact us for further
details.
NOTE:
NOTE: - Languages are subject to change as the modules are updated. Please
Ple ase contact us for
the list of latest supported languages.
Power Cycle
Power Cycle
Power Cycle
Power Cycle
After Exit
After Exit
After Exit
After Exit
DIMENSIONS
240mm x 172mm x 57mm
(9.5 x 6.8 x 2.25)
PANEL CUTOUT :
220mm x 160mm
(8.7 x 6.3)
SCREW TERMINALS
Suitable for: 0.6mm - 1.3mm
(22 16 AWG)
Press the
buttons simultaneously to
enter the editor.
Press
Press
to change the visible parameter.
To exit select Abandon or Save changes and exit and
press either
button.
Parameter
Contrast
Values
|
Language
ENGLISH , OTHERS
1-16 (1)
YES, NO
YES, NO