NON-ARMOURED
CABLES
INCREASED SAFETY - Ex e
FLAMEPROOF - Ex d
FLAMEPROOF COMPOUND BARRIER Ex d
12/12/2012 22:36
2 de 4
http://www.cmp-products.com/selection_of_cable_intended_for_haz_a...
12/12/2012 22:36
3 de 4
http://www.cmp-products.com/selection_of_cable_intended_for_haz_a...
scrutinise in this respect, under IEC rules, is whether a cable gland deploying an elastomeric seal
can be used for every installation. This may inspire the following question :Q - Why do we need to use a compound barrier gland ?
A - If there is any doubt over the cable suitability for the installation of any Ex d equipment or
apparatus, it is the only safe and proven way to ensure that the adequate or minimum level of
safety is applied.
Users who choose not to use compound barrier glands for Ex d installations must first be able to
satisfy themselves, and also be able to demonstrate that the selected combination of cable and
cable gland types are adequate to maintain the Ex integrity of the installation.
Extreme care should be taken when selecting cable glands for use in hazardous areas
Q - When do we need to use a compound barrier gland ?
A - If the cable enters directly into the Ex d enclosure and,
a source of ignition prevails within the terminal enclosure, and
the enclosure volume exceeds 2 litres, or
the cable construction is not adequate to ensure the containment protection that the
equipment offers, against explosion transmission or cable 'blow out'. For example if the cable
sheath that enters the enclosure is not round.
the cable construction is not adequate to prevent gas migration along the length of the cable.
Cable Considerations
Under IEC & CENELEC standards, it should be recognised that limitations exist in the application
of cable glands incorporating an elastomeric Flameproof seal in Explosion Protected Ex d
apparatus.
The prevailing installation codes of practice require that extreme care is taken in the selection of
the correct type of cable glands for use with Flameproof Ex d equipment intended for use in Zone
1 flammable atmospheres.
The ultimate decision on which type of cable gland is the correct one to use must be taken with
consideration of the type of cable selected for the installation, combined with the specific type and
nature of equipment to be installed. So it should be recognised that unless the form of protection
of the equipment is defined and the cable configuration is explicitly known, then it is not possible to
be sure of making a correct cable gland selection.
Typical Multi-Core Cable - The cable construction is an important aspect of maintaining the
explosion protection status of the installation, which needs to be given careful consideration when
selecting the appropriate cable gland.
Special Conditions for Safe Use
It is important to note that Special Conditions for Safe Use may exist for a product or piece of
equipment which set conditions or limitations that if not observed will usually invalidate the
hazardous area certification.
Some limitations may relate to temperature ratings or time delays before opening the equipment
enclosure after isolation of the power supply, and may have an impact on the operational
efficiency of the process. In the case of cable glands there may also be additional conditions
12/12/2012 22:36
4 de 4
http://www.cmp-products.com/selection_of_cable_intended_for_haz_a...
applied in relation to external clamping of the cable, if the cable gland has not been able to
demonstrate full pull out resistance in accordance with prescribed type test levels.
As all Special Conditions for Safe Use should be considered and taken into account during the
selection process for any hazardous area equipment, CMP promote the following
recommendation. Please ask for this information from all manufacturers in advance of purchasing
product, before it is too late!
The following details the extent of Special Conditions for Safe Use currently applicable to CMP
hazardous area cable glands.
Equipment Considerations
Depending upon the nature of the equipment, whether Ex d, whether the cable entry is directly into
the main enclosure, or indirectly, and the amount of free volume inside that enclosure, will
constitute whether a "standard" flameproof Ex d cable gland can be used.
Firstly, however, the cable construction must be considered, in order to determine that the cable is
substantially compact and circular with an extruded bedding, and if any fillers are used that they
are Non-Hygroscopic. If the cable meets this criteria, then the following questions can then be
asked :Q - When do we need to use a compound barrier gland ?
A - If the cable enters directly into the Ex d enclosure and,
a source of ignition prevails within the terminal enclosure, and
the enclosure volume exceeds 2 litres, or
the cable construction is not adequate to ensure the containment protection that the
equipment offers, against explosion transmission or cable 'blow out' or
the cable construction is not adequate to prevent gas migration along the length of the cable.
The diagram above left shows a direct entry arrangement where an Ex d Compound Barrier Gland
has been selected. The example above right shows an Ex d enclosure with an indirect cable entry
approach that employs line barriers between the terminal chamber and the main enclosure
thereby segregating the source of ignition from the terminal enclosure and the cable entries.