It
remains one of the most important protection devices, monitoring oil and
gas levels within the machine. A Buchholz relay trip generally indicates
that a potentially catastrophic situation has been avoided.
Buchholz relays
in South Africa
By P De Matos, Allbro
Conclusion
The gas build-up (or loss of oil) function is tested by slowly introducing
air into the gas sampling valve and recording at which volume the alarm
and then the trip switches are activated. The current Eskom specified
values are shown in the Tables 1 and 2.
Oil content of transformer
1 000 litres
25 mm
150 50 cm
50 mm
300 50 cm
10 000 litres
75 mm
400 100 cm
Relay
nominal size
1 000 litres
25 mm
300 502 cm
50 mm
700 502 cm
75 mm
800 1002 cm
50 000 litres
75 mm
800 1002 cm
The final routine tests are the 60 s, 2 kV RMS at 50 Hz electrical withstand tests, applied in turn between each electrically independent
circuit and the casing of the device, and between the separate independent electrical circuits.
Bibliography
BS EN 50216-1:2002. Power transformers and reactor fittings: General.
ESKOM 240-56063908. Buchholz relay specification.