DS - HD4 17 50 (En)
DS - HD4 17 50 (En)
5kV up to 50 kA
DATA SHEET
CIRCUIT BREAKER
1.1 General
Item
1
Description
Manufacturer
1.1
1.2
1.3
1.4
1.5
2
Standard product
Quality certification
Environmental Management System cert.
Country
City , Address
Standards
2.1
3
3.1
3.2
3.2
3.4
Description
Rated Voltage (U)
Rated normal current (In) at 40C
3
4
Frequency
Operating Duty
Normal sequence
High speed three phase
Out of phase
Make-break time (C-O)
Rated Making and Breaking Current
during Normal/Reclose Operating sequence
Three phase terminal fault rating
5.1.1
Breaking current (symmetrical)
5.1.2
Breaking current (asymmetrical)
5.1.3
Making current
5.1.4
First pole to clear factor
Single phase earth fault rating
5.2.1
Breaking current (symmetrical)
5.2.2
Making current
Breaking current under out of phase
conditions
Short time rating - 3 sec
4.1
4.2
4.3
4.4
5
5.1
5.2
5.3
6
kV
A
rev.29-jan-2002
Page 1 of 8
Hz
msec
12-17.5
1600-2000-2500-3150-3600 (up to
2500 A for withdrawable version)
50/60
O - 0.3 sec - CO - 3 min - CO
O - 0.3 sec - CO - 15 sec - CO
CO
120
kA
%Idc
kAp
25 - 31.5 - 40 - 50
30% at 50 kA
63 - 80 - 100 - 125
1.5 (see Annex 1)
kA
kAp
25 - 31.5 - 40 - 50
63 - 80 - 100 - 125
kA
kA
6.25 - 8 - 10 - 12.5
25 - 31.5 - 40 - 50
HD4 12-17.5kV up to 50 kA
7
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8
7.9
7.10
8
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
Mechanical performances:
Maximum total break time (trip start
to final arc extinction)
Opening time (trip start to contact
separation)
7.2.1
100% of supply voltage
7.2.2
70% of supply voltage
7.2.3
110% of supply voltage
Maximum time interval between opening
of first and last phase of three phase
circuit breaker
Maximum time interval between opening
of interrupters of one phase
Closing time from energisation of close
coil to latching of circuit breaker in fully
close position
Making time (energisation of close coil
to contact touch) :
7.6.1
100% of supply voltage
7.6.2
85% of supply voltage
7.6.3
110% of supply voltage
Maximum time interval between closure
of first and last phase of three phase
circuit breaker
Maximum time interval between closure
of interruptors of one phase
Maximum time from separation of the
contact to their remaking during auto
reclosing duty (O-C) ("Dead time")
Critical current on which maximum arc
occour
Switching Overvoltages:
Maximum peak value of switching
overvoltage when interrupting rated
inductive current
Interruption of no-load MV/LV
trasformers
Interruption of compensation reactance
currents
Interruption of MV motor rated currents
Maximum peak value of switching
overvoltage when interrupting rated line
and cable charging current
Interruption of no-load cables and lines
Interruption of capacitive currents (C-O)
8.7.1
Single capacitor bank
8.7.2
Back-to-back capacitor bank
8.7.3
Capacitor bank inrush making
(IEC 62271-100 class E2)
Rated characteristic for short line fault
Current chopping level
rev.29-jan-2002
Page 2 of 8
msec
55-60
msec
msec
msec
45
65
42
msec
msec
N.A.
msec
60
msec
msec
msec
74
80
70
msec
msec
N.A.
sec
10
A
A
1250
1250
A
A
kA
1250
1250
20 at 4.25 kHz
400 A, inrush 20 kA, 4.25 kHz
N.A.
N.A. for SF6
HD4 12-17.5kV up to 50 kA
Basic Insulation Level ( BIL 1.2/50 sec)
phase to phase, phase to earth, across
open contact
kVp
Power frequency withstand voltage
phase-phase, to earth, across open contact
kVrms/1 min
Radio influence voltage (RIV) level measured
V
at 1.1Um 3 at 1MHz
Insulation material of outer contact arms
Maximum temperature rise test under
normal load conditions
C
10
11
12
13
14
15
mV
75(12) - 95(17.5)
28(12) - 38(17.5)
N.A.
Glass polyester mass
According to IEC 62271-100 and
IEC 60694
12 max
Test Duties 1-2-3-4-5 all
according IEC 62271-100
(see Annex 1)
General
Description
Number of poles
Number of current interrupting break units
in series per phase
Method of controlling voltage distribution
between break units (resistor, capacitor etc)
Value of resistors where used:
Breaking resistors
Making resistors
Insertion time of making resistors
Type of power device (pneumatic,
electro-pneumatic, hydraulic or spring)
for closing
for opening
Number of opening trip device per phase
Single phase mechanism
Three phase mechanism
Mass of complete CB
Fixed version
Withdrawable
Live mass of circuit breaker complete
Total load of heaters for circuit breakers
Minimum clearence distance (withdrawable
version C, W and P)
Phase - Phase
Phase - Earth
Between upper and lower terminal
rev.29-jan-2002
Page 3 of 8
3
1
N.A.
N.A.
N.A.
N.A.
Spring
Spring
N.A.
on request up to 2 coils
kg
kg
kg
W
mm
mm
mm
145 - 165
177 - 220
Depending on the panel type
N.A.
HD4 12-17.5kV up to 50 kA
11
1.3.2
Item
1
2
3
4
5
mm
mm
mm
mm
Description
Dead or live tank design
1.3.3
Item
4
5
6
7
6
7
8
9
1
2
3
mm
mm
gr
525
gr
bar (abs)
bar (abs)
bar (abs)
3.2 at 20C
2.8 at 20C (All dielectric and
interrupting performances
are guaranteed)
Pressure switch
10
Yes
Safety valve
1 per pole
16
>30
Epoxy resin
Composite material
kA
Yes/No
bar (abs)
bar (abs)
Description
Type
Number of mechanism per circuit breaker
Operating mechanism with solenoid or
motor charged spring
Trip springs separate from closing springs
Is the CB trip free?
Operating backup charging mechanism
Number of closing operation stored in fully
rev.29-jan-2002
Page 4 of 8
ESH
1
Yes/No
Yes/No
HD4 12-17.5kV up to 50 kA
8
8.1
8.2
9
9.1
9.2
9.3
10
11
11.1
11.2
12
13
14
15
15.1
15.2
15.3
16
17
18
18.1
18.2
18.3
18.4
19
19.1
19.2
19.3
19.4
20
21
22
22.1
O - CO
CO
sec
sec
sec
J
Yes/No
Yes/No
5...7
5...7
5...7
400
Yes (standard)
Yes (standard)
Yes/No
Yes (standard)
On the c.b. roof cubicle for CBE,
UniSafe and UniGear type ZS1.
On the c.b. truck for CBF and
UniGear type ZS1 (on request)
Yes (standard)
By means of truck tulip for CBE
By means of truck wheels for
UniSafe and UniGear type ZS1
Yes/No
rev.29-jan-2002
Page 5 of 8
V
V
V
Yes/No
24-30-48-60-110-125-220
24-48-60-110-127-220-230-240
110-127-220-230-240
Yes, mechanical
VA, W
1500 / 400
V
%
%
VA, W
See point 15
85%Vn
110%Vn
250 / 5
V
%
%
VA, W
See point 15
70%Vn for DC , 85%Vn for AC
110%Vn
125
VA, W
250 / 5
VA, W
n
250 / 5
10 or 15
3 NO + 4 NC
HD4 12-17.5kV up to 50 kA
22.2 set of 15 aux.cont. (8 NO + 7 NC)
Maximum number of free aux. contact
(depending on the accessories)
22.3
Auxiliary contacts characteristics
22.3.1
Rated voltage
22.3.2
Rated current
22.3.3
Breaking capacity (AC)
22.3.4
Breaking capacity (DC)
22.3.5
Insulating level 50Hz/1min
23
Signalling contacts characteristics
23.1
Rated voltage
23.2
Rated current
23.3
Breaking capacity (AC)
23.4
Breaking capacity (AC)
23.5
Breaking capacity (AC)
23.6
Breaking capacity (DC)
23.7
Breaking capacity (DC)
23.8
Insulating level 50Hz/1min
24
Routine tests on the assembly line on each
pole and complete CB
24.1
Leakage test
24.2
Millivolt drop measurement
24.3
Mechanical operations
24.4
O/C speeds, time spread between
poles (max 2msec)
24.5
Strokes
24.6
Insulating level test
24.7
Auxiliary contacts insulating test
4 NO + 6 NC
V
A
A
A
V
V
A
A
A
A
A
A
V
Yes/No
Yes/No
Yes/No
Yes
Yes
Yes
Yes/No
Yes/No
Yes/No
Yes/No
Yes
Yes
Yes
Yes
This Data-Sheet refers to the standard version: for particular applications, requirements,
performances ask to ABB T&D S.p.A. Unit Operativa SACE T.M.S.
rev.29-jan-2002
Page 6 of 8
HD4 12-17.5kV up to 50 kA
Here below is shown in a bilogarithmic scale the graph of permissible number of switching
fixed version
HD4
12-17.5 kV
withdrawable version
HD4/C - HD4/P
12-17.5 kV
HD4/W
12-17.5 kV
1600-3600 A
2000-2500-3150 A
1250 A
1600-2000-2500 A
1600-2000-2500 A
40-50 kA
25-31.5-40-50 kA
40-50 kA
25-31.5-40-50 kA
16-25-31.5 kA
Number of operation
10,000
1,000
100
10
1
0.1
1.0
10.0 16
rev.29-jan-2002
Page 7 of 8
25 40 50
31,5
100.0
ANNEX 1
Standard values of transient recovery voltage (font IEC 62271-100)
Rated
voltage
rev. 29-jan-2002
Type of test
Test duty
Time
Time
delay
Voltage
Time
RRRV
Ur
Kpp
Kaf
Uc
t3
td
u'
t'
Uc/t3
[kV]
[p.p.]
[p.p.]
[kV]
[s]
[s]
[kV]
[s]
[kV/s]
T100
T60
T30
T10
T100
T60
T30
T10
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.4
1.5
1.5
1.5
1.4
1.5
1.5
1.5
20.6
22
22
22
30
32
32
32
61
26
13
13
71
31
15
15
9
4
2
2
11
5
2
2
6.9
7.3
7.3
7.3
10
11
11
11
29
13
6
6
35
16
7
7
0.34
0.85
1.70
1.70
0.42
1.04
2.14
2.14
OP1-OP2
2.5
2.5
1.25
1.25
30.6
45
118
145
18
22
10
15
56
70
0.26
0.31
12
Terminal fault
17.5
Terminal fault
12
17.5
Out-of-phase