Professional Documents
Culture Documents
CYME 7.0 Whats New Industrial and Transmission
CYME 7.0 Whats New Industrial and Transmission
CYME 7.0
Industrial and Transmission
Power Engineering Software
New Features and Modules
Table of Contents
Chapter 1 General Enhancements .............................................................. 5
1.1 Keywords Units ......................................................................................... 5
1.2 System Parameters .................................................................................... 5
1.3 Induction Motors ........................................................................................ 6
1.3.1
Locked Rotor Current Entry in p.u .......................................................... 6
1.3.2
Computation of the Power Factor .......................................................... 6
1.4 Transformer Loading (ANSI / IEC)................................................................... 6
1.5 Customer Types ........................................................................................ 7
Chapter 2 Load Flow Analysis .................................................................... 8
2.1 Tolerance on Impedances ............................................................................ 8
2.2 Include DC Network .................................................................................... 9
2.3 Line Charging ........................................................................................... 9
Chapter 3 Short Circuit Analysis ............................................................... 10
3.1 Tolerance on Impedances .......................................................................... 10
3.2 All Duty Type Analysis ............................................................................... 11
3.1 ANSI / IEC Report Enhancements................................................................. 12
3.1.1
Available reports ............................................................................ 12
3.1.1.1
ANSI & IEC Summary on all Buses ............................................................... 12
3.1.1.2
3.1.2
Sample Reports ............................................................................. 13
3.1.2.1
IEC Initial Duty Report ................................................................................... 13
3.1.2.2
3.1.2.3
3.1.3
5.2.1
5.2.2
Nominal Rating from Cell Data Sheet (IEEE 946 STD) ................................. 43
6.2.10.3
Keywords Units
1.2
System Parameters
1.3
Induction Motors
1.3.1
1.3.2
1.4
1.5
Customer Types
Tolerance on Impedances
CYMFLOW and CYMFAULT now include the capability to apply tolerances on Transformer, Line
and Cable lengths for maximum and minimum analysis.
These tolerances are either User Defined or as per IEC 60076 or IEEE C57.12 default values.
2.2
Include DC Network
2.3
button.
Line Charging
Tolerance on Impedances
CYMFAULT now include the capability to apply tolerances on Transformer and Synchronous
Generator Impedances, Line and Cable lengths for maximum and minimum analysis.
10
3.2
Summary
short
circuit
analysis for all ANSI or IEC
duty types in a single run.
11
3.1
Reports layout for all ANSI or IEC duty types have been modified especially when faulting a
desired bus
3.1.1
Available reports
The Short Circuit Reports that the user can display on screen are now dependent on the type of
fault applied.
The following are examples of the reports available for IEC short circuit analysis.
3.1.1.1 ANSI & IEC Summary on all Buses
The Fault Flow reports at a bus for the initial current and system wide contributions and
voltage profiles are provided in detail. For all other duties fault level and first ring
contributions are provided along with the IEC multiplying factors for the initial current..
12
3.1.2
Sample Reports
3.1.2.1
Parameters
Study Name
Coopr-Cyme-Variable-Frequency-Drive-Network-7.0.sxst
Date
Time
12h11m55s
Project Name
New
Faulted Bus
V-SB-012-A
Duty Type
Initial
Fault Type
All
Faulted Phases
Default
Voltage
Phase
kV
Deg
6.6
6.6
-120
6.6
120
Amp
Deg
LLL
16262
-84.89
LL
14083
-174.89
LLG
14951
166.82
LG
11902
-84.02
R + jX
pu
R/X
Z1
0.0527 + j0.5894
0.089
Z0
0.1472 + j1.2336
0.119
Type
LLL
LG
LL
LLG
10165.7
4967.5
8803.7
8925.7
V-EHP-1005
Cable
6.6KV_B_TIE
Switch
0.0
0.0
0.0
0.0
V-EHP-1007
Cable
3143.5
5494.3
2722.4
4414.0
V-EHP-1008
Cable
2661.3
1298.2
2304.7
2325.0
V-EHP-1009
Cable
215.1
104.7
186.3
187.9
V-EHP-1010
Cable
82.5
40.2
71.4
72.1
Type
Z1
Z0
V-EHP-1005
Cable
0.0520 + j0.5876
0.1473 + j1.2336
V-EHP-1007
Cable
0.0454 + j0.5828
0.0297 + j1.1649
V-EHP-1008
Cable
0.0467 + j0.5836
0.1473 + j1.2336
V-EHP-1009
Cable
0.0522 + j0.5889
0.1473 + j1.2336
V-EHP-1010
Cable
0.0527 + j0.5893
0.1472 + j1.2336
3.1.2.2
Parameters
Study Name
Coopr-Cyme-Variable-Frequency-Drive-Network-7.0.sxst
Date
Time
12h08m28s
Project Name
New
Faulted Bus
V-SB-012-A
Duty Type
Peak
Fault Type
All
Faulted Phases
Default
Method
Voltage
Voltage
14
kV
Deg
6.6
6.6
-120
6.6
120
Amp
LLL
45995
LL
39832
LLG
42287
LG
33663
R/X
Z1
0.0527 + j0.5894
0.089
Z0
0.1472 + j1.2336
0.119
IEC Factors
Device Number
Type
V-EHP-1005
Cable
2.000
6.6KV_B_TIE
Switch
2.000
V-EHP-1007
Cable
2.000
V-EHP-1008
Cable
2.000
V-EHP-1009
Cable
2.000
V-EHP-1010
Cable
2.000
Type
LLL
LG
LL
LLG
V-EHP-1005
Cable
28753.8
14048.8
24901.5
24864.7
6.6KV_B_TIE
Switch
0.0
0.0
0.0
0.0
V-EHP-1007
Cable
8892.6
15539.4
7699.0
12264.1
V-EHP-1008
Cable
7526.4
3671.3
6519.5
6542.2
V-EHP-1009
Cable
608.1
297.0
526.1
528.9
V-EHP-1010
Cable
231.9
113.1
200.8
203.6
15
Type
Z1
Z0
V-EHP-1005
Cable
0.0520 + j0.5876
0.1473 + j1.2336
V-EHP-1007
Cable
0.0454 + j0.5828
0.0297 + j1.1649
V-EHP-1008
Cable
0.0467 + j0.5836
0.1473 + j1.2336
V-EHP-1009
Cable
0.0522 + j0.5889
0.1473 + j1.2336
V-EHP-1010
Cable
0.0527 + j0.5893
0.1472 + j1.2336
3.1.2.3
Parameters
Study Name
Coopr-Cyme-Variable-Frequency-Drive-Network-7.0.sxst
Date
Time
13h21m22s
Project Name
New
Faulted Bus
V-SB-011-B
Duty Type
Contact Parting
Fault Type
All
Faulted Phases
Breaker Speed
2 cycles
Contact Parting
1.5 cycles
kV
Deg
19052.56
19052.56
-120
19052.56
120
16
Voltage
Voltage
Current
Current
Phase
kV
Deg
kA
Deg
90
16.63
-80.01
-30
16.63
159.99
-150
16.63
39.99
10.14
-72.89
22.75
-138.55
24.75
133.55
LLL
LG-A
R + jX
ohms
pu
X/R
Z1
0.1989 + j1.1281
0.0183 + j0.1036
5.673
Z0
1.2616 + j3.1322
0.1158 + j0.2876
2.483
Z1 (ANSI)
0.1975 + j1.1281
0.0181 + j0.1036
5.711
Z0 (ANSI)
1.2476 + j1.5308
0.1146 + j0.1406
1.227
2X1+X0
2R1+R0
pu
pu
(2X1+X0)/
(2R1+R0)
0.495
0.152
3.247
0.495
0.151
2.305
ANSI Factors
LLL Fault
Local
Remote
Multiplier
Multiplier
(LM)
(RM)
ANSI C37.010
ANSI C37.5
ANSI
Standard
Fault
LG Fault
I Sym
RM
only
I Sym
Weighte
d
Local
Remote
Multiplier
Multiplier
kA
kA
kA
(LM)
(RM)
16.63
16.63
16.63
1.105
16.63
18.38
18.33
2.883%
97.117%
Fault
I Sym
RM
only
Weighted
kA
kA
kA
10.13
10.13
10.13
1.063
10.13
10.78
10.76
17
I Sym
3.1.3
18
Frequency by Zone
19
20
4.1
Global Settings
In the absence of data for controller models, or in the interest of saving time, it may be necessary
to perform simplified stability simulations. That is why, in the Global Settings tab, you have the
option to run your simulation with no Turbines, Exciters or Stabilizers, even if some have already
been defined.
Note:
For Synchronous Generators, you have the option to simplify matters by applying the same
synchronous machine model type to all Generators, or to utilize the models you have selected on
an Individual basis.
You can overwrite the individual generator control model specified at the network level with the
following selections.
Note:
Make sure that sufficient data has been entered in the Generator database for each
machine to be able to use the selected model type. (See Section Error! Reference
source not found. Error! Reference source not found.)
21
The Exclude all Controls option disables all controls on all Generators. Alternatively, you may
use the Exclude All option for each type such as Turbines, Stabilizers and Exciters with or
without saturation modeling.
Wind Turbines and Photovoltaic can be assigned Use Individual Settings or apply a particular
wind or solar model on all. In addition the constant power model is also available for the user at
this level.
22
4.1
The Over Current relay now includes the Transient Stability Functionality.
4.1.1
General Settings
The Over Current Relay network settings dialog box includes two tabs: General and Controlled
Breakers.
The settings at the General tab include the bus Number, the relay Status and the Text displayed
in the relay one line diagram symbol. In addition, it includes the Time Current Settings, Relay
Operating Time and Observation Delay.
The Observation Delay in seconds is included in the total response of the system to account for
the fact that the current may recover to within acceptable limits before the breaker trip signal is
initiated.
23
4.1.2
Controlled Breakers
The Controlled Breakers tab is used to select the circuit breakers that are to trip due to an over
current in the protected branch.
The Breaker Operating Time in seconds represents the delay of the breaker trip mechanism to
trip or close the contacts. This delay is entered in the Network Settings of the desired breaker.
The Total Breaker Operating Time in seconds is the sum of all three namely.
Observation Delay + Relay Operating Time + Breaker Operating Time
24
4.1.3
TCC Settings
User defined Definite Time or directly from the device Time Current curves for either Definite
Time or relays with time dial functionality.
User Defined
Definite Time
Settings
The Relay Current Pick Up, Operating and Observation Delay times can be
entered by the user.
Note
The Relay Pick Current is used to calculate the branch current threshold
that will activate the trip signal.
Example
Relay Pick up is 10 A
The CT Ratio is 200:5
The Branch Current trip threshold is
25
5.1
To access the Locked Rotor Analysis, go to Analysis > Motor Start > Locked Rotor. You can
also choose Motor Start Locked Rotor Analysis from the Simulation Toolbar and click on the
Run Simulation
5.1.1
button.
Analysis Settings
Locked Rotor Analysis calculates the voltage dip starting motors will cause on a network. This
calculation assists in determining the proper motor size for installation.
Specify the Status (Off, Running, Locked Rotor) of the motors and the starting mode of each
Starting motor. At least one motor in the network should be at Starting status to perform a
Locked rotor analysis. To change and/or to view the current settings of a motor, click the Modify
hyperlink.
26
Under the During Motor Start group box, you define if the equivalent source, regulators,
generators and capacitors are locked or un-locked. For each class of devise, click to place a
check mark in the selection box to lock.
Enable these options to calculate the voltage drop at the moment of motor start before regulators,
generators or switched capacitors have time to react.
In the Output Options group box, you can choose whether to display outputs automatically:
summary report, detailed report. Check-mark Color by Voltage Dip to color-code the One
Line diagram by voltage dip levels, based on the limits as defined in the Color by Voltage Dip
tab% (see View > Display Options, Layers tab, select Analysis layers as the Category).
Hint:
Run a Locked rotor analysis with different starting modes to see the decrease
of the voltage dip in the network. The acceleration of the motor over time is not
simulated.
27
5.1.2
This Table defines the allowed voltage dip depending on the number of starts per day. These are
used to compare with the real values obtained from the simulation. This comparison is included in
the summary report.
Voltage dip values greater than the maximum allowed setting will be displayed in red.
Starts/day (minimum), Starts/day (maximum): define the range of starts/day of motors. Motors
with a starts/day value falling within a specific range will be subjected to that ranges allowed
voltage dips.
28
5.1.3
V-K-001C
Input Summary:
Nameplate HP
Number of Phases
Rated Voltage
Applied Voltage
Starts/Day
Starting Assist
Efficiency
Power Factor
Locked Rotor PF
NEMA Code
kVA/HP Ratio
6500 HP
3
6.60 kV
6.60 kV
1 Starts/Day
Variable Frequency Starter
95.0%
89.0%
15.0%
D
4.30
No.
1
2
3
4
5
6
Minimum
Maximum
At Substation
At Upstream Section
At Motor Terminal
Starts/Day
1
6
96
1440
14400
144000
Starts/Day
6
96
1440
14400
144000
1440000
(%)
(%)
(%)
(%)
3.00
2.00
2.00
0.00
0.00
0.00
7.00
5.00
3.50
1.50
0.80
0.50
9.00
7.00
5.00
1.50
0.80
0.50
9.00
7.00
5.00
1.50
0.80
0.50
At Substation
At Upstream Section
At Motor Terminal
(%)
3.00
0.00
(%)
7.00
7.69
91.62
99.25
(%)
9.00
8.39
91.62
100.00
(%)
9.00
8.64
91.27
99.90
Output Summary:
Current
Current
At Motor Terminal
(A)
R1
+jX1
2444.99
501.69
459.71
0.23
6.76
1.14
1.54
3.46
7.51
Impedance(Ohms)
Voltage Dip:
Maximum motor starts/day that satisfies the Flicker Table: 0 per day
Highest Constraint Location: At Upstream Section
Section Id
Value (%)
A
B
C
V-K-001A
V-K-001A
V-K-001A
91.27
91.27
91.27
29
5.1.4
To define the color-coding used by the One Line diagram after a Locked Rotor Analysis, go to
View > Display Options > Layers tab. Select the category Analysis Layer and select the layer
Voltage Level Color (%).
30
5.2
To access the Motor Start Maximum Size Analysis, go to Analysis > Motor Start > Locked
Rotor. You can also choose Motor Start Maximum Start from the Simulation Toolbar and click
on the Run Simulation
5.2.1
button.
Analysis Settings
This type of analysis is used to estimate the maximum motor size that can be started on a given
section.
5.2.2
Click Run to start the analysis. Depending on the options selected, either or both the Maximum
Motor Size Result Box and the Maximum Start Size Analysis detail report(s) will be displayed
automatically.
31
The Motor Size Result Box displays the same information as the detail report but displays the
information one section at a time.
Hint:
If you did not check the Display the result box option, generate it by running
the analysis again. Un-check the detail report so you will not get double
reports.
Hint:
Select a section from the detailed report and both the result box and the One
Line will highlight the same section and vice versa.
32
Chapter 6 DC Analysis
6.1
Introduction
DC Analysis is limited to networks that contain safe power supplies to critical equipment such as
DC Motors, Valves and other loads that are required when the DC battery is supplying power to
these loads due to a loss in the supply voltage to the Charger.
The equipment library has now been enhanced with the addition of DC equipment such as
Station Batteries, Charger, Uninterruptable Power Supply (UPS) and DC / DC Converter.
In addition DC Cables, Impedance branch, protective devices, loads and machines are now
included in the library which allows the user to build any DC network with all the necessary
network components.
6.2
DC Equipment
DC Bus
6.2.1
Sources
Loads
Branches
Protective Devices
DC Bus
Depending on the network topology the DC Bus base voltage will be automatically propagated by
the software. As an example the Charger Rated output DC Voltage will be selected as the base
voltage.
Only DC equipment can be connected to a DC bus and all other AC network components will be
blocked from connection to a DC bus.
33
6.2.2
DC Cable
In DC circuits it is assumed that the two identical cables are connected between the positive and
negative terminals of the devices.
This includes the General Data including the construction details of the cable, loading limits
and symbol dialog boxes.
In the absence of the electrical parameters data the program can compute the electrical
parameters of the Cable from the geometrical construction of the cable.
6.2.3
DC Impedance
The DC Impedance from an electrical stand point is treated exactly as a cable with the only
difference being that the impedance value R + jX is entered as a total resistance and inductance
of the cable.
34
6.2.4
DC Load
DC loads are commonly rated based on their operating voltage and power.
The Rated voltage (V) of the load is specified along with either its Power (KW) or Current (A) and
the other is computed since the power equation always should hold true.
6.2.5
DC Motor
The DC motor is very similar to an induction motor and is represented by the following equivalent
circuit.
Rs
Motor Resistance
Winding Inductance
Vg
Back e.m.f
RL
Magnetic Losses
Note
35
Mechanical
Power
Rated Power
Rated Voltage
Efficiency
Speed
Load Factor
Short
Circuit
contribution
36
6.2.6
Protective Devices
The protective devices follow a common format as far as the data entry and settings in both the
equipment and network properties of each device.
Fuse
Switch
LVCB
Nominal Rating
.
Rated current
Rated Voltage
In kV.
Interrupting
Rating
In Amps.
However, you must enter non-zero value for withstand rating. If this
value is zero no check will be made.
37
6.2.7
Charger
A charger is a constant voltage source, maintaining its terminal bus voltage at the desired control
value as specified in the network settings.
Whenever the terminal bus voltage drops below the desired regulated voltage of a charger, it will
try to raise the voltage to the regulated value until the charger current reaches Imax. On the other
hand if the terminal bus voltage is higher than the charger regulated voltage, the charger
becomes inactive and is switched off from the system.
However, when the current drawn from the charger is greater than Imax, the maximum current it
can provide while keeping its terminal voltage constant at the same time, it becomes a constant
current source. The current drawn from the charger is then kept at Imax, while the terminal
voltage drifts, depending on the system loading and sources such as batteries or a UPS
Nominal Rating
Nominal Voltages
In KW or Amps.
Input AC Voltage in Kilo Volts (KV)
Output DC Voltage in Volts (V)
Efficiency
38
Power Factor
Maximum Output
Current
Control Type
Short
Circuit
contribution
39
6.2.8
6.2.9
DC-DC Converter
Nominal Data
Nominal Rating
Nominal Voltages
In KW or Amps.
Primary Input DC Voltage in Volts (V)
Secondary Output DC Voltage in Volts (V)
Efficiency
In % to quantify the electrical power losses in the Converter.
Maximum Output
Current
Control Type
Short
Circuit
contribution
6.2.10 DC Battery
Each Battery consists of a number of Cells with a typical value of 2.08 Volts connected in series
for the desired Battery Voltage as an example 12 or 24 V.
41
These in turn are connected in Series and Parallel combinations to generate the required DC
Station Voltage and AH Capacity. The voltage could be in the range of 120, 240 or 480 Volts.
The Battery equipment properties offer two choices of entering the nominal information Battery
Type:
Nominal Rating from Battery Data Sheet
6.2.10.1
Nominal Data
Nominal Voltage
Number of Cells
Nominal Capacity
Internal
Resistance
per
Cell
Maximum
Discharge Current
Short
Current
Circuit
42
6.2.10.2
Nominal Data
Nominal Capacity
Voltage Per Cell
Number of Plates
Resistance
Per
Positive Plate
Maximum
Discharge Current
Short
Current
Circuit
43
6.2.10.3
Battery Type
Series
Connected
Batteries
Parallel Strings
System Nominal
Voltage
System Nominal
Capacity
External
Connections
Short
Circuit
Contribution
Voltage Source
Behind
an
Impedance
Where
Constant Current
Source
45
6.3
The default calculation method in the DC Analysis module is the Newton Raphson Load Flow
solution method.
Select DC Load Flow Analysis from the list of available analyses. (See illustration.) You can
also select it from Analysis > DC Load Flow Analysis.
Before accessing the Analysis dialog box go to File System Parameters to modify, if desired,
the Base Power for solving the DC Networks.
46
6.3.1
Analysis Parameters
The DC Load Flow Analysis dialog box comprises configuration settings and four tabs that will
allow you to set the:
Remove All
Constraints
Adjust
Impedance
If this option is checked then the load flow will be solved by relaxing
all the constraints on Batteries, Chargers, UPS and Converters. This
includes the limit on Imax and the detection of reverse power flow in
devices.
Note:
This is useful for networks that have difficulty converging
since the results of the load flow, with relaxed constraints,
can provide useful tips as to where the problem may be.
The next three dialog boxes are similar to the AC Load Flow Analysis module:
You may select to analyze a network without analyzing all the other
networks connected to this particular network.
47
6.3.2
Once the parameters for the DC load flow analysis have been set, you may click on the Save
button if you wish to permanently save the parameters to your disk. This is only useful if you wish
to re-use the same parameters as default parameters for future studies.
Click on the Run button to start the analysis and display the results on the one line diagram, the
results box and in the reports.
The default layer for the DC Power Flow Results is
provided with the program and can be accessed
through the results layer tool bar.
After the analysis is completed you can display and color code the one line diagram with any
abnormal condition such as overloaded equipment and bus violations by clicking on the
of the analysis tool bar.
icon
.
48
6.3.3
To select and display the DC Load Flow Results reports click on the
toolbar or select Report > On Calculation from the menu.
.
Lists of reports provided with the software are detailed below:
49
6.4
DC Short Circuit
Select DC Short-Circuit from the list of available analyses. You may also select Analysis >
Fault Analysis > DC Short-Circuit from the menu.
6.4.1
Analysis Parameters
The DC Short Circuit Analysis dialog box comprises configuration settings and four tabs that will
allow you to set the:
When the calculation mode Fault Flow currents and voltages is selected, the fault location group
box is activated to allow users to specify the location at which a fault is to be applied.
Location
The next three dialog boxes are similar to the AC Short Circuit Analysis module:
6.4.2
Once the parameters for the DC short circuit analysis have been set, you may click on the Save
button if you wish to permanently save the parameters to your disk. This is only useful if you wish
to re-use the same parameters as default parameters for future studies.
Click on the Run button to start the analysis and display the results on the one line diagram, the
results box and in the reports.
The default layers for the DC Short Circuit results
provided with the program can be accessed
through the results layer tool bar.
51
Fault at a bus
52
6.4.3
.
6.4.3.1
List of reports provided with the software for this are detailed below:
53
6.4.3.2
List of reports provided with the software for this are detailed below:
54
6.5
Interface to AC System
To include the results of the DC system you need to access the CYMFLOW analysis Controls
menu and activate the option
button.
By including the DC analysis keywords in ac power flow layer then the results of both analyses
can be displayed on screen.
55
56
The Harmonic current source data can be entered in the database settings of the general
Frequency Source included in the equipment library of harmonic devices.
The desired frequency source can then be associated to the particular device from the Harmonic
Settings of that particular device in the Section Properties dialog box. An example illustrating
the settings of the harmonic model for a Charger is shown below.
57
To display the harmonic voltage and current distortion results simply activate the CYMHARMO
analysis module, set the parameters, specify the location of the points of common coupling (PCC)
between the AC and DC and display the results on the OLD, print reports and generate the
charts.
58
Chapter 7 CYMPROTEC
CYME 7.0 brings numerous enhancements and new features to its Network Protection Analysis
module. The CYMPROTEC Module is an advanced protection analysis module that is now fully
integrated within the CYME 7.0 software package.
New Features
7.1
59
Library Editor
To modify the TCC Library by
accessing the Library Editor, click on
View to arrange the list displayed on
the left hand side to show Protective
Devices, Manufacturers, Re-closer
Control Types, Cable Insulations,
Cable Sizes, Relay Tap Ranges,
Device Tolerance and Transformer
Inrush. The display of each of the
above categories would give access to
different data that is pertinent to the
category chosen, and these data can
be modified.
Import and Export Device Settings
Device settings as entered in the
Library Editor can be imported, or
exported to another TCC Library.
Re-Index, Compact and Repair
Online Update
Relay
Settings
General
60
61
UTILITY-SUPPLY
C-L1
C-L1
Electronic
CUTLER HAMMER
C-H FP5000 ANSI VERY
13.80 KV
921.00 A
14879.94 A
Setting
Value
Phase
70:1
Tap with Tap Range
0.05
0.05 / 2.4
0.65
45.50 A
Off
Off
Protection Type
CT Ratio
Operation Mode
Time Dial
Tap Range
Tap
Primary Pickup
Short Time
Instantaneous
62
7.2
User-defined
location.
fault
63
Tracing of the
protective devices
triggered in the
one-line diagram
Tabular
report
listing
the
sequence
of
device triggered,
the opening time
and fault current
detected at each
operation
64
The Minimum Fault analysis is offered to assist engineers in the verification of whether the
protective devices can adequately detect and clear the minimum faults seen in their respective
protection zone.
A detailed report is provided to list all areas that are inadequately protected. Those areas are also
color-coded on the one-line diagram for easier visualization.
65