Professional Documents
Culture Documents
12 kV switchgear manual
ABB Switchgear
CONTENTS
Page
0. Access zones....................................................................................................................................................................................1
1. General description ................................................................................................................................................................1
1.1.
Standards ................................................................................................................................................................................................3
1.2.
Cubicle design ................................................................................................................................................................................4
1.2.1. Personnel safety ..............................................................................................................................................................................5
1.2.2. Dimensions and weights.....................................................................................................................................................7
1.2.3. Busbars and downleads .....................................................................................................................................................8
1.2.4. PC intermediate wall with shields .........................................................................................................................8
1.2.5. Earthing.........................................................................................................................................................................................................8
1.2.6. Running gear and interlock system....................................................................................................................9
1.2.7. Temperature indicators.....................................................................................................................................................11
1.3.
Power circuit breaker cubicle ..........................................................................................................................12
1.4.
Load disconnector cubicle SFL .....................................................................................................................13
1.5.
Load disconnector cubicle NAL/NALF ..............................................................................................14
1.6.
Disconnector cubicle ......................................................................................................................................................15
1.7.
Metering cubicle ......................................................................................................................................................................16
1.8
Sectioning cubicle ................................................................................................................................................................17
1.9
Contactor cubicle ..................................................................................................................................................................18
2. Contactor cubicle .....................................................................................................................................................................19
2.1.
Erection requirements ...................................................................................................................................................19
2.1.1. Lift truck ...................................................................................................................................................................................................19
2.2.
Floor..............................................................................................................................................................................................................20
2.2.1. Space requirements...............................................................................................................................................................21
2.3.
Unloading ............................................................................................................................................................................................23
2.4.
Moving in ..............................................................................................................................................................................................23
2.5.
Setting up ............................................................................................................................................................................................24
2.6.
Fitting busbars ............................................................................................................................................................................27
2.6.1. Fitting busbars, light series .........................................................................................................................................27
2.6.2. Fitting busbars, heavy series ...................................................................................................................................28
2.7.
Cubicle and system earthing..............................................................................................................................30
2.8.
Fitting roof panels .................................................................................................................................................................31
2.9.
Connecting power cables........................................................................................................................................31
2.10. Connecting control cables .....................................................................................................................................35
2.11. Post-tightening ..........................................................................................................................................................................37
3. Post-tightening ............................................................................................................................................................................38
4. Post-tightening ............................................................................................................................................................................41
4.1.
Commissioning new switchgear ................................................................................................................41
4.2.
Commissioning after stoppage for repair or other action .............................41
4.3.
Commissioning after stoppage......................................................................................................................41
5. Operating instructions....................................................................................................................................................42
5.1.
Circuit breakers HPA and HA ............................................................................................................................42
5.1.1 Circuit breaker shift ................................................................................................................................................................43
5.1.2. Circuit breaker shift to operating position ............................................................................................44
5.1.3. Circuit breaker shift to disconnected position ...............................................................................45
5.2.
Load disconnector SFL ..............................................................................................................................................47
5.2.1. Safesix SFL interlock chain ......................................................................................................................................47
5.2.2. Shifting load disconnector SFL ............................................................................................................................48
5.2.3. Shifting load disconnector SFL to operating position ......................................................48
5.2.4. Switching load disconnector on ........................................................................................................................49
5.2.5. Shifting load disconnector SFL to disconnected position .........................................49
5.2.6. Switching load disconnector off .........................................................................................................................49
5.3.
Load disconnectors NAL 12/630, NALF 12/630 ..................................................................50
5.3.1. Operating NAL/NALF ...........................................................................................................................................................52
6. Maintenance rules ................................................................................................................................................................54
6.1.
Switchgear cubicle maintenance ...............................................................................................................55
6.2.
Lubricants ...........................................................................................................................................................................................57
6.3.
Cleaning agents ........................................................................................................................................................................57
7. Accessories, spares and ancillary equipment ............................................................................58
8. Documentation references ......................................................................................................................................60
Safesix 12 kV switchgear
0
Access zones
Switchgear is not intended to be accessible to the general
population. The access zone for operators is the service entrance at the front of the switchgear. Only servicing personnel
are allowed to open switchgear doors. All operation of a withdrawable switching or connecting unit must be with the doors
closed.
1
General description
ABB's Safesix switchgear series is divided into compartments
and intended for indoor locations. It is available in three different
voltage versions of 12, 17.5 and 24 kV. This documentation is
for the 12 kV version. The cubicles are sized for operating
currents of up to 3150 A and maximum 4000 A on the busbars
and a short-circuit current of up to 40 kA.
Safesix 12 kV switchgear is available in two forms:
Light series
Max. rated current 1600 A.
Max. short-circuit current 31.5 kA.
Heavy series
Max. rated current 4000 A.
Max. short-circuit current 40 kA.
Interconnection cubicle
The withdrawable switching and connecting units have the following functions:
Circuit breaker
Can make, carry and break operating
current and short-circuit current
Switch disconnector
Safesix 12 kV switchgear
Contactor
Electrical switch that is operated electrically and has an electrical or mechanical latch. Can make, carry and break
normal operating current and carry
short-circuit current for a specified
period. Can be supplied with fuses as
short-circuit protection. Type of switch
used preferably where switching
density is high and current low.
Circuit breaker
cubicle
Sectioning cubicle
31.5 kA 630 - 1600 A
Sectioning cubicle
40 kA 800 - 3150 A
Disconnector
cubicle
Metering
cubicle
Switch disconnector
cubicle
Inter connection
cubicle
Contactor
cubicle
Safesix 12 kV switchgear
1.1.
Standards
Safesix 12 kV switchgear
1.2.
Cubicle
design
Busbar compartment
Low-voltage compartment, with contents varying from installation to installation. A detailed description of this compartment appears in the documentation specific to each
order
Cable compartment
All HV compartments (busbar compartment, cable compartment and withdrawable switching or connecting unit compartment) have individual upward pressure relief ducts with top
covers that opens by any overpressure in the respective compartment.
Busbar compartment
LV compartment
Instrument space
Upper door
Racking mechanism
Lower door
Air intake for cubicles with
rated current 1600 A
Compartment for
withdrawable switching
or connecting unit
PC partitions
Partition wall for
compartment division
Cable compartment
Safesix 12 kV switchgear
1.2.1.
Personnel
safety
Personnel safety
High voltages and currents can cause serious injuries, so the
Safesix range is designed for maximum elimination of
accident risks.
Contact safety
As it is vitally important for servicing personnel to be protected
from inadvertent contact with energised parts, Safesix cubicles
are divided into compartments. Among other advantages, this
prevents access to energised busbars when disconnected
circuit breakers are being inspected. The walls between
compartments are partly transparent. The advantages of this
include being able to view the disconnection distance through
the window in the LV compartment.
CAUTION! There is no contact protection inside the lower
door. The cable side has to be de-energised and be earthed
by means of the earthing switch before opening the door.
Unauthorised access can be prevented by padlocking the
handles of both the upper and lower doors.
Arcing safety
The outer enclosure has been arc-tested to SS-IEC 298.
The front, rear and sides withstand the pressure caused by
arcing faults. Safesix cubicles have also been successfully
tested to SS-IEC 298 with breaker doors open.
Damage caused by arcing faults is extensive and costly,
so their causes need to be eliminated despite the high
degree of personnel safety built into Safesix switchgear. The
following are possible causes of flashover:
Safesix 12 kV switchgear
contacts or overload
SafeGuard (option)
SafeGuard is a monitoring system covering, among other
things, the temperatures of busbar joints and contacts in the
main circuit. The continuous information thus provided helps
to eliminate the risk of arcing faults.
Safesix 12 kV switchgear
Temporary earthing
Safesix switchgear is equipped with a patented earthing
switch that has the following features:
Training
It is very important that operators and servicing personnel be
trained in handling the equipment.
1.2.2.
Dimensions
and weights
Weights
A 12 kV switchgear cubicle (without circuit breaker) normally
weighs 400 to 600 kg depending on equipment, e.g. an 800 A
circuit breaker cubicle weights 400 kg.
A circuit breaker weighs between 180 and 235 kg, depending
on its rated current.
Max
Series
current A
Dimensions mm
H
W
D
1600
2500
3150
2160
2160
2160
Light
Heavy
Heavy
700
700
700
1200
1300
1600
Safesix 12 kV switchgear
1.2.3.
Busbars and
droppers
1.2.4.
PC-partition
with shutters
The switchgear is of the drawer-mounted type. The withdrawable units can be cranked into and out of the
compartments. The withdrawable unit compartment and the
busbar compartment are separated by a partition of
polycarbonate to prevent inadvertent contact with live parts
when the unit is removed. This partition incorporates six
shutters that are opened by the connecting bars when the
unit reaches operating position.
The PC partition and the shutters provide IP3X as degree
of protection.
PC partitions
Shutters
Box with earthing
switch auxiliary contacts
and interlock magnets
1.2.5.
Earthing
Safesix 12 kV switchgear
1.2.6.
Each withdrawable unit is provided with wheels that run
Racking mechanism
and interlocking system along channel sections on the sides of the cubicle. The unit
can be pulled out onto the door. A stop mounted on the door
prevents its being pulled too far out. For instructions on
shifting withdrawable units, see section 5.1.1. The racking
mechanism has interlocks to prevent incorrect operation.
Torsion disc
Selector cam
Selector
Stop
Racking
mechanism
operating hole
Earthing switch
operating hole
Safesix 12 kV switchgear
10
Safesix 12 kV switchgear
1.2.7.
Temperature
indicators
11
Safesix 12 kV switchgear
1.3.
Circuit breaker
cubicle
Data
Rated current
Rated voltage
Insulation level
Insulation level
Rated short-time
current peak value
Rated short-time current, 1 s
Rated short-timecurrent, 3 s
kV
kV
kV
kA
kA
kA
Window in
low voltage
compartment
12
Safesix 12 kV switchgear
1.4.
Switch disconnector
cubicle SFL
Window in
low voltage
compartment
13
Safesix 12 kV switchgear
1.5.
Switch
disconnector
cubicle
NAL/NALF
Window in
low voltage
compartment
14
Safesix 12 kV switchgear
1.6.
Disconnector
cubicle
Same construction as the circuit breaker cubicle. The withdrawable disconnector has the same contact positions in the
conducting path as the corresponding circuit breaker. Disconnection is achieved by shifting the withdrawable unit from
service position to disconnected position. Disconnection can
be effected by means of racking mechanism inside the closed
door. The cubicle can be provided with current and voltage
transformers and an earthing switch.
The disconnector has no make and break facilities. Interlocks prevent incorrect operation. The disconnection distance can be viewed through the window in the LV compartment. Blocking devices prevent withdrawable units with too
small a rated current being run into the cubicle.
Window in
low voltage
compartment
15
Safesix 12 kV switchgear
1.7.
Metering
cubicle
Fig. 11. Light-series metering cubicle measuring both current and voltage.
16
Safesix 12 kV switchgear
1.8.
Sectioning
cubicle
Fig. 12. Light-series circuit breaker cubicle with sectioning. For the heavy series a two-cubicle combination is used.
17
Safesix 12 kV switchgear
1.9.
Contactor
cubicle
Data
Rated voltage . . . . . . . . . . . . . . . . . . .3.6 kV . . .7.2 kV
Insulation level . . . . . . . . . . . . . . . . . . .10/40 kV .20/60 kV
Rated current with fuse . . . . . . . . . . .315 A . . . .315 A
Fuse length . . . . . . . . . . . . . . . . . . . . .292 mm . .442 mm
Rated short-time current . . . . . . . . . .9 kA . . . . .9 kA
Rated short-time current with fuse . .40 kA . . . .40 kA
This cubicle contains a VRC type vacuum contactor which is
drawer-mounted and placed in the withdrawable unit
compartment. It is operated electrically and has both electrical
and mechanical latch. For fuse replacement the withdrawable
unit has to be pulled out onto the door. Racking mechanism
can be used to shift the contactor to disconnected position
inside the closed door, thereby creating a disconnection
distance that can be viewed through the window in the
bottom of the LV compartment. The upper door is extended
by 40 mm, making a total cubicle depth of 1375 mm.
18
Safesix 12 kV switchgear
2
Erection instructions
CAUTION! Take good care to follow these instructions precisely so that cubicles are not dropped or tipped over during
unloading, moving in and setting up. When handling cubicles,
take particular care to avoid causing pinching or injuries.
2.1.
Erection
requirements
2.1.1.
Trolley
Order no.
Description
Section to
front wheel
Section to
front wheel
Square tube
Square tube
Fastening bolt
Fastening bolt
Position for 12 kV
Position for 24 kV
19
Safesix 12 kV switchgear
Pin
Spacer tube
2.2.
Floor
20
Safesix 12 kV switchgear
21
700
65
min 150
65
min 150
Safesix 12 kV switchgear
min 2650
min 450
65
400
min 1500
700
65
min 150
22
710
Safesix 12 kV switchgear
2.3.
Unloading
2.4.
Moving in
Lifting tackle
23
Safesix 12 kV switchgear
24
Safesix 12 kV switchgear
25
Safesix 12 kV switchgear
Use a small-diameter
hose to blow drill
cuttings away
door panel. To open a lower door, pull the handles out towards
you, then turn them upwards. The door will move upwards and
outwards. To close the lower door, fold the handles out from
the door and turn them upwards. Use the guide pins on the
door to raise it into position, then press the door downwards,
turn the handles downwards and fold them in.
The gap between cubicle front side-panels is a nominal 3 mm
and should not be reduced, as cubicles are tight together in
middle part.
26
Safesix 12 kV switchgear
2.6.
Fitting busbars
2.6.1.
Light series
Intermediate
cubicle
Right-hand
outer cubicle
Intermediate
cubicle
Left-hand
outer cubicle
Front
Busbars for
sectioning cubicle,
as seen from above
Rear
Busbars for:
Droppers for:
1250, 1600 A
1250, 1600 A
A-A
1250, 1600 A
800 A
A-A
1250, 1600 A
630 A
A-A
800 A
630, 800 A
A-A
630 A
630 A
Fitting busbars
B-B
Busbars for:
1250, 1600 A
B-B
800 A
B-B
630 A
27
Safesix 12 kV switchgear
2.6.2.
Heavy series
Outer cubicle
Busbars
Droppers
2500 - 3150 A
2500 - 3150 A
Intermediate cubicle
Outer cubicle
Busbars
Droppers
2500 - 3150 A
1600 - 2000 A
Intermediate cubicle
Outer cubicle
Busbars
Droppers
2500 - 3150 A
800 - 1250 A
28
Safesix 12 kV switchgear
Intermediate cubicle
Outer cubicle
Busbars
Droppers
1600 - 2000 A
1600 - 2000 A
Intermediate cubicle
Outer cubicle
Busbars
Droppers
1600 - 2000 A
800 - 1250 A
Intermediate cubicle
Outer cubicle
Busbars
Droppers
800 - 1250 A
800 - 1250 A
29
Safesix 12 kV switchgear
2.7.
Cubicle
and system
earthing
30
Safesix 12 kV switchgear
2.8.
Fitting roof
panels
2.9.
Connecting
power
cables
31
Safesix 12 kV switchgear
32
Safesix 12 kV switchgear
33
Safesix 12 kV switchgear
Cables
Primary
reconnectable
Position 1
800 A
IHBF 12 A
Circuit
breaker
cubicle
Primary
reconnectable
Position 1
2 x 3 phase
150-300 mm2
1250 A
IHBF 12 A
4 x 3 phase
300 mm 2
Circuit
breaker
cubicle
Primary
reconnectable
Position 2
4 x 1 core
500-630 mm2
630
65
34
769
645
75
75
480
75
75
90
6 x 1 core
500-1000 mm2
480
Primary not
reconnectable
6 x 1 core
500-1000 mm2
75
Cable
cubicle
700
75
6 x 1 core
500-1000 mm2
90
DIN-TRAFO
700
480
65
90
3150 A
645
90
4 x 3 phase
300 mm 2
562
Primary not
reconnectable
Position 3
90
90
32
65
Circuit
breaker
cubicle
663
772
4 x 1 core
500-630 mm2
90
DIN-TRAFO
65
D=13
90
2500 A
720
90
Primary not
reconnectable
Position 3
65
90
Circuit
breaker
cubicle
D=13 18
90
DIN-TRAFO
90
2000 A
D=13 18
622
Primary not
reconnectable
Position 2
1 x 3 phase
150-300 mm2
713
Circuit
breaker
cubicle
Circuit
breaker
cubicle
Holes
IHBF 12 A
DIN-TRAFO
Pattern
663 from front
800 A
1600 A
Cable lugs
692
Current
transformer
Safesix 12 kV switchgear
2.10.
Connecting
control
cables
35
Safesix 12 kV switchgear
Cubicle lighting
Cable duct
Terminal blocks for
cubicle lighting
Sliding terminal
blocks
36
Safesix 12 kV switchgear
2.11.
Posttightening
of busbar
M10
30
20
M12
60
40
M16
120
80
Nm
M8
10
M10
20
M12
35
M16
75
37
Safesix 12 kV switchgear
3
Functional testing
Only servicing personnel are allowed to open cubicle doors.
The following points are to be checked before commissioning
switchgear:
CAUTION! DANGER TO PERSONNEL
1. While switchgear is being worked on, it must be earthed to
eliminate any risk of its being energised by mistake.
CAUTION! When operating the earthing switch, no-one
must be in the cubicle, to avoid the risk of being pinched by
the switch. Effect earthing by closing the earthing switch
and connecting the temporary earthing to a through earth
bar or to each cubicle separately.
Only during phase identification and insulation testing
may the temporary earthing be temporarily removed.
For safety measures before and after energisation, see ABB
publications 1WAT 910034-031 and 1WAT 910034-051.
In some cases the earthing switch is electrically interlocked
so that if there is no control voltage the contact cannot be
released.
2. Unfasten and disconnect connected power cables.
3. Check the phase identify of the busbars.
Connect a battery box as follows:
Earth: - 0 V
L1 - 4.5 V
L2 - 9 V
L3 - 13.5 V
Check in every cubicle that the voltages measured on the
various busbars are correct.
Busbar positioning in ABB indoor switchgear is as follows:
a) From top to bottom: L1, L2, L3
b) From left to right: L1, L2, L3
Note: A diagram is provided in cases where any other
phase sequence is used.
4. Check the following on all withdrawable units:
38
Safesix 12 kV switchgear
39
Safesix 12 kV switchgear
40
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
4
Commissioning
The operator access zone is the aisle in front of the switchgear.
Only servicing personnel are allowed to open cubicle doors.
CAUTION! There is no contact protection inside the lower
door. The cable side must be de-energised and be earthed by
closing the earthing switch before opening the lower door.
When operating the earthing switch, no-one must be in the
cubicle, to avoid the risk of being pinched by the switch.
Unauthorised access inside the doors may be prevented by
padlocking the handles of both the lower and upper doors.
CAUTION! Beware risk of being pinched when closing
doors.
CAUTION! Cubicle enclosures have sharp edges on their
sides and roof. Be particularly careful when handling these
areas.
4.1.
Commissioning
new switchgear
4.2.
Commissioning
after stoppage
for repaire or
other action
4.3.
Commissioning
after stoppage
41
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
5
Operating instructions
The operator access zone is the aisle in front of the switchgear.
Only servicing personnel are allowed to open cubicle doors.
CAUTION! There is no contact protection inside the lower
door. The cable side must be de-energised and be earthed by
closing the earthing switch before opening the lower door.
When operating the earthing switch, no-one must be in the
cubicle, to avoid the risk of being pinched by the switch.
Unauthorised access inside the doors may be prevented by
padlocking the handles of both the lower and upper doors.
CAUTION! Beware risk of being pinched when closing
doors.
CAUTION! Cubicle enclosures have sharp edges on their
sides and roof. Be particularly careful when handling these
areas.
5.1.
Circuit breaker
HPA and HA
42
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
Mechanical opening is always possible by emergency trip on
the front of the cubicle (HPA) or by mechanical push-button
on the front of the circuit breaker (HA), neither of which are
affected by mechanical or electrical blocking.
If the circuit breaker has an anti-pumping relay (HPA option),
closing is blocked so long as the "make" pulse persists after a
make/break sequence. If the circuit breaker has an undervoltage trip (option) it opens the circuit breaker if the control
voltage falls below 70% of nominal.
The switchgear may have both manual and remote control.
Remote control makes it possible to use an actuator on the
cubicle front to select "local" in order to bar remote signals.
The unit can then be controlled manually.
5.1.1
Circuit breaker
shift
43
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
5.1.2
Circuit breaker
shift to operating
position
44
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
4. Turn the selector to the movement position (Fig. 31c). Insert
the crank in the operating hole and wind the circuit breaker
to service position so that the indication below the operating hole becomes "CLOSED". Remove the crank and turn
the selector to service position (Fig. 31d), thereby locking
the unit in service position and releasing the circuit breaker
control circuit.
Position a
Position b
Position c
Position d
5.1.3
Circuit breaker
shift to disconnected position
The procedure for removing the circuit breaker from the cubicle
or shifting it from service position to disconnected position
(test position) is as follows:
1. Use the cubicle front push-buttons to open the circuit
breaker (see Fig. 32a). If the circuit breaker is closed, the
selector cannot be operated.
2. Turn the selector from service position (Fig. 31d) to
45
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
movement position, as in Fig. 32b.
Insert the crank as in Fig. 32c. Wind it anticlockwise. Shifting the circuit breaker from service position (CLOSED) to
disconnected position (OPEN) takes place inside the closed
door. The circuit breaker position indicator displays
CLOSED in service position, OPEN in disconnected position
and a series of dots during shifting. Remove the crank.
3. Turn the selector to removable position, as in Fig. 32d.
Open the door to the withdrawable unit compartment and
pull the circuit breaker out onto the folded-down door. If the
circuit breaker is to be removed from the cubicle, go on to
item 5.
4. If the circuit breaker is not be removed from the cubicle,
turn the selector to earthing position (Fig. 31a), which is
used when the circuit breaker is to be test-operated. In this
position the circuit breaker is isolated from the busbar
system. It is also used when the cubicle is to be temporary
Position a.
Position c.
46
Position b.
Position d.
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
earthed. If there is risk of residual voltage in the cubicle, the
earthing switch should be provided with an interlock
magnet. When the selector is in position test/earthing, the
earthing switch can be closed, thereby earthing the cable
side, but remember that the LV circuits are not affected.
When the earthing switch is closed, the selector is
blocked. The indicator may display
or CLOSED.
5. Take the circuit breaker trolley away. CAUTION! When
using a trolley, the unit concerned must always be carried in
the lowered position. Do not leave it in a raised position on
the trolley. Pump the lifting cradle on the trolley up so that
the lifting lugs on both sides of the circuit breaker fit into the
recesses on the cradle. Then pump the cradle still higher so
that the circuit breaker can be removed from the door.
5.2.
Switch disconnector SFL
5.2.1
Safesix interlock
chain for SFL
47
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
4. Mechanical interlocking prevents rotation of the selector
if the unit is closed.
5. Mechanical blocking of the racking mechanism selector prevents a closed unit being withdrawn from service position.
6. It is not possible to close the earthing switch if SFL is in
service position or being shifted.
5.2.2.
Shifting switch
disconnector SFL
5.2.3.
Shifting switch
disconnector SFL to
service position
48
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
CAUTION! Beware the risk of pinching as the door
closes or between SFL and the door rails. Push SFL all the
way into the cubicle, fold its handle upwards, close the
door to the withdrawable unit compartment and fold the
door handle downwards. CAUTION! Beware the risk of
injury caused by arcing fault. It is important that the door
should be closed properly so as to prevent injury due to
any arcing fault. When the door closes, the handle should
be easy to slide down against the door panel.
4. Turn the selector to test/earthing position (Fig. 31a). SFL
can be tested in this position, in which it is disconnected
from the main circuit. N.B. The auxiliary circuit remains
connected.
In this position it is also possible to use the earthing
switch to earth the cable side temporary.
5. To put SFL into service position, disconnect the earthing
switch by inserting the crank in the operating hole and
winding it anticlockwise until the earthing switch opens.
The indicator below the operating hole will display "0" or
"OPEN". Turn the selector to movement position (Fig.31c),
insert the crank in the racking mechanism operating hole
and wind SFL to service position. The indicator below the
operating hole will then display "CLOSED". Remove the
crank and turn the selector to service position (Fig.31d),
thereby locking a cam on the selector shaft the unit in
service position.
5.2.4.
Switching switch
disconnector on
5.2.5.
Shifting switch
disconnector SFL to
disconnected position
49
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
5.2.6.
Switching switch
disconnector off
50
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
5.3.
Switch disconnectors Interlock chain for Safesix cubicles with NAL 12/630, NALF
12/630.
NAL 12/630,
Conditions to be fulfilled for switching on to be possible:
NALF 12/630
1. Selector to be in service position.
2. Control lever to be inserted manually and operating
device tensioned before the unit can be switched on.
Switching on results in:
1. Mechanical blocking of the racking mechanism selector,
prevents a closed unit being withdrawn from service
position.
2. The interlock fork situated on the left under the front
cover of the switch disconnector preventing the unit
being pushed into the cubicle (see Fig. 33d).
Conditions to be fulfilled for switching off to be possible:
1. Switch disconnector to be closed, use auxiliary contacts to
check that it is.
33 a.
33 c.
33 b.
33 d.
Switching on
Switching off
51
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
2. For manual switching off the control lever has to be inserted in the operating hole. With a switched off magnet
(option) the switch disconnector can be switched off electrically, in which case the control voltage has to be 70110% DC nominal or 85-110% AC nominal.
The switchgear may have both manual and remote control.
Remote control makes it possible to use an actuator on the
cubicle front to select "local" in order to bar remote signals.
The unit can then be controlled manually.
5.3.1.
Operating
NAL/NALF
52
Safesix 12 kV switchgear
CAUTION! Before taking action, follow the safety instructions on page 41.
CAUTION! Beware the risk of being injured during operation
of the switch disconnector, which has accessible open knives.
1. Move the interlock fork on the left under the front cover of
the switch disconnector to the lefthand position (see Fig.
33d). In this position the fork prevents the switch
disconnector being pushed into the cubicle while at the
same time allowing the unit to be operated.
2. Switch the switch disconnector on (see Fig. 33b) as per
item 4 under "Operating NAL/NALF".
CAUTION! Beware risk of accident due to switch
disconnector knives.
3. Switch the switch disconnector off (see Fig. 33b) as per
item 5 under "Operating NAL/NALF ".
4. Move the interlock fork to its upper position. The switch
disconnector can then be pushed into the cubicle.
53
Safesix 12 kV switchgear
6
Maintenance
rules
The operator access zone is the aisle in front of the switchgear.
Only servicing personnel are allowed to open cubicle doors.
CAUTION! There is no contact protection inside the lower
door. The cable side must be de-energised and be earthed by
closing the earthing switch before opening the lower door.
When operating the earthing switch, no-one must be in the
cubicle, to avoid the risk of being pinched by the switch.
Unauthorised access inside the doors may be prevented by
padlocking the handles of both the lower and the upper door.
CAUTION! Beware risk of being pinched when closing
doors.
CAUTION! Cubicle enclosures have sharp edges on their
sides and roof. Be particularly careful when handling these
areas.
Switchgear maintenance comprises inspection and cleaning
as per Table 6.1.
The maintenance intervals shown apply to normal environments and have to be shortened as necessary to cater for
severer conditions. Suitable times for undertaking maintenance
include when switchgear is taken out of operation to allow
extension work or is de-energised for other reasons.
The tool requirement is a normal set of tools for electrical
maintenance work and the special tools indicated in Chapter 7.
For circuit breaker maintenance, see separate manual.
CAUTION! Certain operations that require switchgear to be
completely de-energised and earthed for work are marked
in Table 6.1. Other operations that can be carried out with
switchgear energised are marked . Work under voltage is
governed by safety rules according to ESA. Operations marked
can be carried out both under voltage and/or when the
cubicle is temporary earthed.
54
Safesix 12 kV switchgear
6.1.
Switchgear cubicle
maintenance
Maintenance intervals
Before commissioning and
after 1 year
Every
5 years
Inspection/action
Underlined
instructions
to be carried
out as necessary regardless of
ordinary
maintenance
intervals
CAUTION! In most cubicles, opening the lower door provides access to parts carrying high voltage. Check that the cooling
air valves are in the open position. This applies to 1600, 2000, 2500
and 3150 A cubicles.
Check that the silvered female contacts are not oxidised. If they
are, clean and lubricate with grease type G.
Inspect each cubicle visually to see that there are no damaged
components or conductors.
Lubricate the moving parts of running gear with oil A or grease E.
CAUTION! Check that shielding and PC partitions are in
position.
55
Safesix 12 kV switchgear
Maintenance intervals
Before commissioning and
after 1 year
Every
5 years
Inspection/action
Check that connecting bars for withdrawable units are not oxidised. If they are, clean and lubricate with a fresh coating of grease
type G.
Check that earth connections for withdrawable units are not oxidised. If they are, clean and lubricate with a fresh coating of grease
type G.
Check that connecting bars of withdrawable units engage
properly1. Lubricate the contacts with a thin film of grease type G.
Operate any units that have not been used for a long time, and
their racking mechanism.
Check that the sliding contacts in the roof of the compartment for
withdrawable units are intact and run easily into one another.
CAUTION! Cubicle contacts are energised with auxiliary voltage..
1
The engagement distance should normally be 25 mm (tolerance range 17-33 mm) as per Fig. 34. Maximum lateral displacement 3 mm.
Maintenance to be done only when switchgear deenergised and temporary earthed.
Maintenance can be done with switchgear energised.
Maintenance can be done both under voltage and/or
when cubicle temporary earthed.
Data on contacts appear in Information sheet 5216 701-V.
56
Safesix 12 kV switchgear
6.2.
Lubricants
Brand
Oil A
Grease E
Grease G
O-ring grease
ABB no.
1171 2013-301
1171 4012-201
1171 4014-407
1171 4014-409
BP
Enegrol HLP 32
Energrease LS 2
Neblan
Klber
Microlube GL 261
Mobil
D.T.E. 24
OK
Hydraulic Oil 23
Q8
Hayden 32
Shell
Tellus Oil 32
Statoil
Hydraway HMA 32
6.3.
Cleaning
agents
Barrierta L55/2
Mobile Grease 28
57
Safesix 12 kV switchgear
7
Accessories, spares and ancillary equipment
Spares . . . . . . . . . . . . . . . . . . . . . . . . . . . .Order no.
Microswitch . . . . . . . . . . . . . . . . . . . . . . .1VEB 537301-002
Microswitch . . . . . . . . . . . . . . . . . . . . . . .1VEB 537301-003
Circuit breaker sliding contact . . . . . . . . .2657 992-H
Cubicle sliding contact . . . . . . . . . . . . . . .2657 992-G
Cubicle sliding contact . . . . . . . . . . . . . . .2657 992-F
Lower hatch handle, right . . . . . . . . . . . . .2184 4403-AD
Lower hatch handle, left . . . . . . . . . . . . . .2184 4403-AE
Hatch hinge . . . . . . . . . . . . . . . . . . . . . . . .2184 4402-9
Interlock box electromagnet . . . . . . . . . . .5254 778-XX
Racking mechanism 1250 A . . . . . . . . . .LV 841 028-MD
Racking mechanism > 1250 < 2500 A . . .LV 841 028-MC
Racking mechanism 2500 A . . . . . . . . . . .LV 841 028-ME
Racking mechanism 3150 A . . . . . . . . . . .LV 841 028-MF
Earthing switch operating arm, 31.5 kA . .2239 702-AN
Earthing switch operating arm, 40 kA . . . .2239 702-AP
Limit switch contact . . . . . . . . . . . . . . . . .LV 841 708-XX
Each cubicle lower earth bar is provided with two bulldog grips
for connecting earth conductors for system and cable sheath
earthing. If further clips are necessary, they can be ordered as
per table. The data are for clips mounted on bars 4-8 mm
thick.
For mm2 line
Fuse wires
Fine wires
RK
Order no.
16-50
35-185
95-300
16-50
35-120
95-185
16-50
35-150
95-240
LV 889 031-A
LV 889 031-B
LV 889 031-C
Patching paint
Light-beige paint.
Order no.
SA 263 022-VA
Crank
For cubicle front control operations. Normally included in
cubicle supply.
Order no.
2247 953-A
For HPA circuit breaker spring tensioning:
Order no.
LV 899 361-A
58
Safesix 12 kV switchgear
Trolley
To carry withdrawable units.
Order no.
1VES 841 930-AAA, hydraulic variant
Adaptor to carry voltage measuring sets:
Order no.
1VES 841 930-AAB
Tool set
Tool set for switchgear with Combiflex relays. Box contains 1
groove chisel, 5 RTXD extractors, 1 chisel set (Torx), 1 Polykomb 13 mm wrench and 1 wheel for locks.
Best. nr
LV 899 011-G.
Groove chisel with insulated blade 240 mm long.
For Ben Kri URTK/S terminal blocks
Order no.
SK 176 2130
Polykomb wrench type VNPK 13
For jaw width 13 mm, set of two
Order no.
SK 176 0918
Hexagon socket for cable erection
Order no.
LV 851 940-AA
59
Safesix 12 kV switchgear
8
Documentation references
ABB publication
Content
IVEB 580901-911
........
IVEB 580901-902
........
IVEE 301701-900
........
9VLB 9304-11
HPA manual
HA1 manual
SafeGuard manual
Tightening torque for electrical
connections made of coppe
............
Information on contacts
................
60
NOTES
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................
........................................................................................................................................................................................................................