lindab coverline

technical information profiled sheeting

Lindab Coverline TM

Lindab Profiled Sheeting


Technical Information

lindab coverline

profiled sheeting

Technical Facts

Colour chart
Number

Nearest RAL

Topline (0,5), Coverline

Name

Nearest NCS

001

Antique white

S 1002-G50Y

9002

010

Chalk white

S 0502-G

9010

0,4/0,5/0,6

015

Black

S 9000-N

9005

0,4/0,50,6/0,7/0,8/1,0

0,5/0,6

022

Light grey

S 2005-G60Y

7044

0,5

0,6

044

Anthracite metallic

S 600-N

9007

045

Silver metallic

9006

0,5/0,6

PE

0,5

0,6
0,5/0,6

078

Interior white

S 1502-Y

9002

0,7/0,8/
1,0/1,2

087

Dark grey

S 7005-B20G

7011

0,4/0,5/0,6

113

Beige

S 1010-Y30R

1015

0,4/0,5

152

Mustard yellow

S 2040-Y10R

1002

0,5

244

Zinc grey

S 3502-B

7040

412

Fire red

S 2070-Y90R

3000

0,5

418

Wine red

S 5040-Y90R

3011

0,5

434

Brown

S 8005-Y80R

8017

0,4/0,5

461

Goosewing grey

S 3502-Y

7038

502

Light blue

S 4030-B10G

5024

0,5

524

Dark blue

S 6020-B

5001

0,5

542

Signal blue

S 4550-R90B

5010

0,5

558

Azure blue

S 5030-R90B

5009

742

Tile red

S 4040-Y80R

8004

0,5

0,5/0,6

758

Dark red

S 5040-Y80R

3009

0,4/0,5/0,6

0,5/0,6

874

Forest green

S 6020-G30Y

6003

0,4/0,5

0,6

975

Verdigris

S 3020-G10Y

6021

0,5

0,6

0,5/0,6
0,6
0,6

0,6

HBP = High Build Polyester, Gloss: 40 5


MPE = (Matt Polyester) Gloss: 5 3
The thickness of the steel is specified in mm.

This colour chart is general with variations on markets and it can be subject for changes.
All of the thicknesses and colours are not available in all profiles.
See the actual pricelist for correct information.

MPE

0,5/0,6

PE = Polyester, Gloss: 30 5

HBP

0,6

0,5

lindab coverline

profiled sheeting

Technical Facts

Anti condensation NonDrip coating


Condensation occurs naturally on
profiled sheet roofs and walls in un

insulated buildings when the temperature of the sheeting falls below the dew
point. The biggest problems occur when
the weather changes warm damp air
meets sheeting which covered and
cooled by snow. Radiation condensation
is often enough (i.e. when the sheeting
becomes cooler than the surrounding air
as a result of radiation under cloudless
conditions) for water to start dripping. If
this condensation does form, drops of
water will run under the roof and along
the walls. This water dripping off the roof
and wall joists can cause considerable
damage to the contents of the building.
Profiled sheeting can be coated with
Lindab NonDrip to reduce the problem.
NonDrip contains a mineral which can
quickly absorb and evaporate moisture.
The coating can absorb up to 300 g water per m2. NonDrip can also retain water
on inclined or vertical surfaces.
NonDrip sheeting is always supplied with
masked sides and end overlaps, to prevent water from being absorbed from
outside the building.
It is important to observe the standards
for dimensioning and location of ventila-

tion openings, to achieve good drying.


The lowest recommended roof pitch is
8 to avoid stationary air which would
impede drying. A constant supply of
moisture from an earth floor or activities
in the building can also affect the drying
process.

Warning! If drying is prevented,


the NonDrip becomes saturated
and water will drip.

The light grey NonDrip coating is able to absorb


and evaporate moisture quickly and efficiently
thanks to its unique pore structure.
Evaporation is frequently quicker than absorption
with NonDrip coatings.

Acoustic panels
Profiled sheeting can be perforated to
damp noise. Lindab acoustic panels
are suitable for interior partitions and
roofs where they are used in sports
halls, factories and canteens. Whilst
the wall panels are fully perforated, the
floor deck are only perforated on the
web in order to maintain the required
strength.
The perforation ratio is 23% in the
perforated area for all profiles.

Only minor variations in the absorbation factor occur when differing profile lenghts and/or plastic foil is used,
only give minor variations in absorption
factor.

Absorbtionfactor
1,2
1,0
0,8
0,6
0,4

Perforated
Web Perforated

0,2

125

250

500

1000

4000
2000
Frequency (Hz)

lindab coverline

profiled sheeting

Technical Facts

Cladding

= paint side

LVV18
/ SE
LVV 18
75
26

Covering width = 1060 mm

Thickness, nominal
Yield point fty
Mass

SE

18

16

133

mm
N/mm2
kg/m

0.40
250
3.9

0.50
250
4.8

0.60
250
5.8

LLP20 / SE

35

18

100

18

LLP 20

35
Covering width = 1000 mm

Thickness, nominal
Yield point fty
Mass

SE

mm
N/mm2
kg/m

0.40
250
3.9

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

lindab coverline

profiled sheeting

Technical Facts

Cladding

115

18

LVP 20/ SE
LVP20

25

65

Covering width = 1035 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.40
250
3.9

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

SE

SIN 26

26

SIN26 / SE

125
Covering width = 1000 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.50
250
4.8

0.60
250
5.8

SE

167

30

30

LV30 / LV
SE30

104
Covering width = 1000 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.60
250
5.8

0.70
350
6.8

SE

lindab coverline

profiled sheeting

Technical Facts

Cladding

167

30

30

LVV30LVV
/ SE30

104

Covering width = 1000 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

SE

TR
35
TR35

/ SE
30

28

333

35

223
Covering width = 1000 mm

Thickness, nominal
Yield point fty
Mass

SE

mm
N/mm2
kg/m

0.50
250
4.8

0.60
250
5.8

lindab coverline

profiled sheeting

Technical Facts

Cladding

77

180

43

LVP45LVP
/ SE45

47
Covering width = 900

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

SE

115

LVP115
SE
LVP/115

245

82

56

Covering width = 735 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.50
250
4.8

0.60
250
5.8

0.40
250
3.9

0.50
250
4.8

SE
LP1100
/ DK

157

25

18

LP 1100

99
Covering width = 1100 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

DK

lindab coverline

profiled sheeting

Technical Facts

Cladding

18

SIN 18
SIN18
/ DK

76
Covering width = 1066 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.40
250
4.0

0.50
250
5.0

mm
N/mm2
kg/m

0.40
250
4.0

0.53
250
5.0

mm
N/mm2
kg/m

0.53
250
5.0

0.60
250
6.0

DK

LP20
LP
20 vgg / DK

Thickness, nominal
Yield point fty
Mass

DK

LP
35 vgg / DK
LP35

Thickness, nominal
Yield point fty
Mass

DK

0.60
250
6.0

lindab coverline

profiled sheeting

Technical Facts

Cladding

115

18

LVP20
/ HU
LVP 20

25

65

Covering width = 1035 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.40
250
3.9

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

0.60
250
5.8

0.70
350
6.8

HU

LVP 45

77

180

43

LVP45 / HU

47
Covering width = 900

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.40
250
3.9

0.50
250
4.8

HU

115

65

18

LVP20
/ PL
LVP 20
25
Covering width = 1035 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.40
250
3.9

0.50
250
4.8

PL

lindab coverline

profiled sheeting

Technical Facts

Cladding

180

77

43

45
LVP45LVP
/ PL

47
Covering width = 900 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

PL

LVP 20

LVP20 / CZ
12

64

25

17

18

114

Covering width = 1035 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

LVP20 / CZ New Design

0.40
250
3.9

CZ

LVP 20 new design


12

64

25

17

18

114

Covering width = 1025 mm

Thickness, nominal
Yield point fty
Mass

CZ

10

mm
N/mm2
kg/m

0.40
250
3.9

lindab coverline

profiled sheeting

Technical Facts

Cladding
LVP 45

77

180

43

LVP45 / CZ

47
Covering width = 900 mm

Thickness, nominal
Yield point fty

LVP45Mass
/ CZ New Design

mm
N/mm2
kg/m

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

0.60
250
5.8

0.70
350
6.8

0.50
250
4.8

0.60
250
5.8

CZ

180

77

43

LVP 45 new design

47
Covering width = 900 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.50
250
4.8

CZ

LVP 20
LVP20
/ RO
12

64

25

17

18

114

Covering width = 1035 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.40
250
3.9

0.70
350
6.8

RO

11

lindab coverline

profiled sheeting

Technical Facts

LVP20
/ RO New Design
Cladding
LVP 20 new design
12

17

25

64

18

114

Covering width = 1035 mm

mm
N/mm2
kg/m

Thickness, nominal
Yield point fty
Mass

0.40
250
3.9

0.50
250
4.8

0.60
250
5.8

0.60
250
5.8

0.70
350
6.8

0.60
250
5.8

0.70
350
6.8

0.70
350
6.8

RO

180

77

43

LVP
45
LVP45
/ RO

47
Covering width = 900 mm

nominal
LVP45Thickness,
/ RO New
Design
Yield point fty
Mass

mm
N/mm2
kg/m

0.50
250
4.8

RO

180

77

43

LVP 45 new design

47
Covering width = 900 mm

Thickness, nominal
Yield point fty
Mass
RO

12

mm
N/mm2
kg/m

0.50
250
4.8

lindab coverline

profiled sheeting

Technical Facts

Roofing

= paint side

LTP18
LTP 18/ SE
134

16

75

18

26

Covering width = 1070 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.40
250
3.9

0.50
250
4.8

0.60
250
5.8

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

LLP20 / SE

SE

35

18

100

18

LLP 20

35
Covering width = 1000 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.40
250
3.9

SE

115

65

18

LTP 20
LTP20
/ SE

25
Covering width = 1035 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.40
250
3.9

SE

13

lindab coverline

profiled sheeting

Technical Facts

Roofing

26

SIN 26/ SE
SIN26

125
Covering width = 1000 mm

mm
N/mm2
kg/m

Thickness, nominal
Yield point fty
Mass

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

SE

TR
35
TR35

/ SE
28

333

30

35

223
Covering width = 1000 mm

mm
N/mm2
kg/m

Thickness, nominal
Yield point fty
Mass

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

0.60
250
5.8

0.70
350
6.8

SE

180

47

43

LTP /45SE
LTP45

77

Covering width = 900 mm

Thickness, nominal
Yield point fty
Mass

SE

14

mm
N/mm2
kg/m

0.50
250
4.8

lindab coverline

profiled sheeting

Technical Facts

Roofing
TR45
TR 45 / SE
150

30

60

44

30

Covering width = 890 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

SE

18

SIN 18 / DK
SIN18

76
Covering width = 990 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.40
250
4.0

0.53
250
5.0

mm
N/mm2
kg/m

0.40
250
4.0

0.53
250
5.0

DK

LP 20

LP20 tak / DK

Thickness, nominal
Yield point fty
Mass

0.60
250
6.0

DK

15

lindab coverline

profiled sheeting

Technical Facts

Roofing
LP 35 tak / DK
LP35

mm
N/mm2
kg/m

Thickness, nominal
Yield point fty
Mass

0.53
250
5.0

0.60
250
6.0

DK

LTP20 / HU

65

115

18

LTP 20

25
Covering width = 1035 mm

mm
N/mm2
kg/m

Thickness, nominal
Yield point fty
Mass

0.40
250
3.9

0.50
250
4.8

HU

180

47

43

LTP /45
LTP45
HU

77

Covering width = 900 mm

Thickness, nominal
Yield point fty
Mass

HU

16

mm
N/mm2
kg/m

0.40
250
3.9

0.50
250
4.8

lindab coverline

profiled sheeting

Technical Facts

Roofing
LTP20 / PL

65

115

18

LTP 20

25
Covering width = 1035 mm

Thickness, nominal

mm

Yield point fty

N/mm2

Mass

kg/m

0.40
250
3.9

0.50
250
4.8

PL

180

47

43

LTP /45PL
LTP45

77

Covering width = 900 mm

Thickness, nominal

mm

Yield point fty

N/mm2

Mass

kg/m

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

0.50
250
4.8

0.60
250
5.8

PL

LTP20 / CZ

115

65

18

LTP 20

25
Covering width = 1035 mm

Thickness, nominal

mm

Yield point fty

N/mm2

Mass

kg/m

0.40
250
3.9

0.70
250
6.8

CZ

17

lindab coverline

profiled sheeting

Technical Facts

Roofing

180

47

43

LTP45
CZ
LTP/ 45

77

Covering width = 900 mm

LTP45
/ CZ New
Design
Thickness,
nominal
mm
N/mm2
kg/m

Yield point fty


Mass

0.50
250
4.8

0.60
250
5.8

0.70
250
6.8

0.60
250
5.8

0.70
250
6.8

CZ

180

47

43

LTP 45 new design

77

Covering width = 900 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.50
250
4.8

CZ

LTP20
/ RO
LTP 20
11

114

64

18

12

25
Covering width = 1025

Thickness, nominal
Yield point fty
Mass

RO

18

mm
N/mm2
kg/m

0.40
250
3.9

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

lindab coverline

profiled sheeting

Technical Facts
LTP20 / RO New Design

Roofing
LTP 20 new design

11

64

114

18

12

25
Covering width = 1025

mm
N/mm2
kg/m

Thickness, nominal
Yield point fty
Mass

0.40
250
3.9

0.50
250
4.8

0.60
250
5.8

0.60
250
5.8

0.70
350
6.8

0.60
250
5.8

0.70
350
6.8

0.70
350
6.8

RO

180

47

43

LTP /45
LTP45
RO

77

Covering width = 900 mm

Thickness, nominal
mm
LTP45
/ RO New Design

N/mm2
kg/m

Yield point fty


Mass

0.50
250
4.8

RO

180

47

43

LTP 45 new design

77

Covering width = 900 mm

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.50
250
4.8

RO

19

lindab coverline

profiled sheeting

Technical Facts

Roofing uninsulated

115

LTP 115

82

245

56

Covering width = 735

Thickness, nominal
Yield point fty
Mass

mm
N/mm2
kg/m

0.50
250
4.8

0.60
250
5.8

0.70
350
6.8

0.80
350
7.7

1.00
350
9.7

SE

Roofing insulated

115

LTP /115
LTP115
SE

245

82

56

Covering width = 735 mm

Thickness, nominal
Yield point fty
Mass
SE

20

mm
N/mm2
kg/m

0.70
350
6.8

1.20
350
11.6

lindab coverline

profiled sheeting

Notes

21

lindab coverline

Notes

22

profiled sheeting

lindab coverline

profiled sheeting

Notes

23

lindab coverline

technical information profiled sheeting

Lindab Building Components is a business area within


the Lindab Group that develops, manufactures and
markets efficient, economical and aesthetic steel and
sheet metal solutions for the building industry.
We offer a wide range of components and systems
for all types of housing, as well as commercial and
industrial buildings.
Lindab Building Components is represented in over
30 countries throughout Europe. Our head office is in

Art. no. 153113 2010-06-18

Frslv, in the south of Sweden.

Lindab Profile
SE-269 82 Bstad
Phone +46 (0)431 850 00
www.lindab.com