Professional Documents
Culture Documents
Capitulo 8.1
Capitulo 8.1
Module 8.1
Pressure Control Applications
8.1.1
Steam boilers are usually designed to work at high pressures in order to reduce their physical
size. Operating them at lower pressures can result in reduced output and carryover of boiler
water. It is, therefore, usual to generate steam at higher pressure.
Steam at high pressure has a relatively higher density, which means that a pipe of a given size
can carry a greater mass of steam at high pressure, than at low pressure. It is usually preferable
to distribute steam at high pressure as this allows smaller pipes to be used throughout most of
the distribution system.
Lower condensing pressures at the point of use tend to save energy. Reduced pressure will
lower the temperature of the downstream pipework and reduce standing losses, and also
reduce the amount of flash steam generated when condensate from drain traps is discharging
into vented condensate collecting tanks.
It is worth noting that if condensate is continuously dumped to waste, perhaps because of the
risk of contamination, less energy will be lost if the condensing pressure is lower.
8.1.2
Because steam pressure and temperature are related, control of pressure can be used to control
temperature in some processes. This fact is recognised in the control of sterilisers and autoclaves,
and is also used to control surface temperatures on contact dryers, such as those found in
papermaking and corrugator machines. Pressure control is also the basis of temperature control
in heat exchangers.
For the same heating duty, a heat exchanger designed to operate on low-pressure steam will
be larger than one designed to be used on high-pressure steam. The low-pressure heat exchanger
might be less expensive because of a lower design specification.
The construction of plant means that each item has a maximum allowable working pressure
(MAWP). If this is lower than the maximum possible steam supply pressure, the pressure must
be reduced so that the safe working pressure of the downstream system is not exceeded.
Many plants use steam at different pressures. A stage system where high-pressure condensate
from one process is flashed to steam for use in another part of the process is usually employed
to save energy. It may be necessary to maintain continuity of supply in the low pressure system
at times when not enough flash steam is being generated. A pressure reducing valve is ideally
suited for this purpose.
With this self-acting type of pressure controller, the downstream (control) pressure is balanced
(via a bellows) against a spring force.
Advantages:
1.
2.
3.
4.
5.
6.
Inexpensive.
Small.
Easy to install.
Very robust, giving long life with minimum maintenance.
Tolerant of imperfect steam conditions.
Self-acting principle means that no external power is required.
Disadvantages:
Applications:
Non-critical, moderate load applications with constant running flowrates, for example:
1. Small jacketed pans.
2. Tracer lines.
3. Ironers.
4. Small tanks.
5. Acid baths.
6. Small storage calorifiers.
7. Unit heaters.
8. Small heater batteries.
9. OEM equipment.
Points to note:
High pressure
steam in
Separator
Pressure
reducing
valve
Safety valve
Low pressure
steam out
Condensate
Fig. 8.1.1 General arrangement of a direct operating, self-acting pressure reducing station
8.1.3
With this self-acting type of pressure controller, the downstream (control) pressure is balanced
(via a diaphragm) against a spring force.
Advantages:
1.
2.
3.
4.
5.
6.
7.
Very robust.
Tolerant to wet and dirty steam.
Available in large sizes, so high flowrates are possible.
Easy to set and adjust.
Simple design means easy maintenance.
Self-acting principle means that no external power is required.
Able to handle pressure drops of 50:1 in small sizes, and 10:1 in large sizes.
Disadvantages:
1. Large proportional band means that close control of downstream pressure is improbable with
large changes in load.
2. Relatively high purchase cost, but lifetime cost is low.
3. Bulky.
Applications:
1. Distribution mains.
2. Boiler houses.
Points to note:
1. Because the diaphragm is subject to fairly low temperature limitations, a water seal is required
on steam applications. This adds to the cost slightly.
2. Because of the large proportional band, this type of valve is better suited to reducing steam
pressure to plant areas rather than individual plant items.
3. A bellows sealed stem ensures zero maintenance and zero emissions.
4. Although wide proportional band provides stability, care is needed if a safety valve needs to
be set close to the apparatus working pressure.
5. Suitable for liquid applications.
6. More expensive than a pilot operated valve, but less expensive than a pneumatic control
system.
Safety valve
High pressure
steam in
Condensate
Separator
Low pressure
steam out
Pressure
reducing
valve
Fig. 8.1.2 General arrangement of a direct operating, self-acting pressure reducing station
8.1.4
These have a more complex self-acting design, and operate by sensing the downstream pressure
via a pilot valve, which in turn operates the main valve.
The effect is a very narrow proportional band, typically less than 200 kPa.
This, together with low hysterisis, results in very tight and repeatable control of pressure, even
with widely varying flowrates.
Advantages:
1. Accurate and consistent pressure control, even at high and variable flowrates.
2. A variety of pilot valves may be used on one main valve. Pilot valve options include electrical
override, multi-pilot for a choice of control pressures, a surplussing option and remote control,
as well as different temperature / pressure control combinations.
3. Self-acting principle means that no external power is required.
4. Tolerant of varying upstream pressure.
Disadvantages:
Applications:
1. A system which requires accurate and consistent pressure control, and installations which
have variable and medium flowrates. For example: autoclaves, highly rated plant such as
heat exchangers and calorifiers.
2. A system where installation space is limited.
Points to note:
Separator
Safety valve
Low pressure
steam out
Condensate
Fig. 8.1.3 General arrangement of a pilot operated, self-acting pressure reducing station
8.1.5
Advantages:
1.
2.
3.
4.
5.
6.
7.
Disadvantages:
Applications:
A system which requires accurate and consistent pressure control, and installations which have
variable and high flowrates and / or variable or high upstream pressure. For example: autoclaves,
highly rated plant such as large heat exchangers and calorifiers.
Points to note:
High pressure
steam in
Separator
Low pressure
steam out
Safety
valve
Condensate
Pneumatic controller
Fig. 8.1.4 General arrangement of a pneumatic pressure reducing station
8.1.6
Set point(s) which may be remotely adjusted, with the possibility of ramps between set points.
Advantages:
1.
2.
3.
4.
5.
6.
Disadvantages:
Applications:
A system which requires accurate and consistent pressure control, and installations which have
variable and high flowrates and/or variable or high upstream pressure, including autoclaves, highly
rated plant such as large heat exchangers and calorifiers, and main plant pressure reducing stations.
Points to note:
Pneumatic
pressure
reducing
valve
High pressure
steam in
Separator
Safety
valve
Low pressure
steam out
Pressure
transmitter
Condensate
Fig. 8.1.5 General arrangement of an electropneumatic pressure reducing station
8.1.7
Advantages:
Disadvantages:
1. If a spring return actuator is required, the available shut-off pressure may be limited.
2. Relatively slow actuator speed, so only suitable for applications where the load changes slowly.
Applications:
Points to note:
1. Safety: If electrical power is lost the valve position cannot change unless a spring return
actuator is used.
2. Spring return actuators are expensive and bulky, with limited shut-off capability.
Electronic
controller
Electronic
pressure
reducing
valve
Safety
valve
High pressure
steam in
Separator
Low pressure
steam out
Pressure
transmitter
Condensate
Fig. 8.1.6 General arrangement of an electric pressure reducing station
8.1.8
Pressure reducing stations may be configured as shown below for one of two reasons:
1. The valves are serving a critical application for which downtime is unacceptable
The equipment is operated on a one in operation, one on stand-by basis to cover for breakdown
and maintenance situations
2. The turndown ratio between the maximum and minimum flowrates is very high
The equipment is operated on a pressure sequence principle with one valve set at the ideal
downstream pressure, and the other at a slightly lower pressure.
When demand is at a maximum, both valves operate; when flow is reduced, the valve set at the
lower pressure shuts off first, leaving the second valve to control.
Point to note:
The valves selected for this type of application will require narrow proportional bands (such as
pilot operated pressure reducing valves or electro-pneumatic control systems) to avoid the
downstream pressure dropping too much at high flow rates.
Pressure
reducing
valve
Pressure
reducing
valve
High pressure
steam in
Safety
valve
Safety
valve
Separator
Low pressure
steam out
Condensate
Fig. 8.1.7 Parallel pressure reducing station
8.1.9
Pilot operated
reducing valves
High pressure
steam in
Pilot operated
reducing valves
Safety
valve
Separator
Low pressure
steam out
Trapping
point
Condensate
Condensate
The trapping point between the two reducing valves (Figure 8.1.8) is to stop a build up of
condensate under no-load conditions. If this were not fitted, radiation losses would cause
condensate to fill the connecting pipe, which would cause waterhammer the next time the
load increased.
8.1.10
Desuperheaters
Desuperheating is the process by which superheated steam is either restored to its
saturated state, or its superheated temperature is reduced. Further coverage of desuperheaters is
given in Block 15.
The system in Figure 8.1.9 illustrates an arrangement of a pressure reducing station with a
direct contact type pipeline desuperheater.
In its basic form, good quality water (typically condensate) is directed into the superheated steam
flow, removing heat from the steam, causing a drop in the steam temperature.
Pressure
controller
Pressure
control
valve
Temperature
control valve
Superheated
steam in
Desuperheater
unit
Temperature
controller
PT100
temperature
Pressure
sensor
transmitter
Steam out
It is impractical to reduce the steam temperature to its saturated value, as the control system is
unable to differentiate between saturated steam and wet steam at the same temperature.
Because of this, the temperature is always controlled at a value higher than the relevant saturation
temperature, usually at 5C to 10C above saturation.
For most applications, the basic system as shown in Figure 8.1.9 will work well. As the downstream
pressure is maintained at a constant value by the pressure control loop, the set value on the
temperature controller does not need to vary; it simply needs to be set at a temperature slightly
above the corresponding saturation temperature.
However, sometimes a more complex control system is required, and is shown in Figure 8.1.10.
Should there be a transient change in the superheated steam supply pressure, or a change in the
water supply temperature, the required water/steam flow ratio will also need to change.
A change in the water/steam flow ratio will also be required if the downstream pressure changes,
as is sometimes the case with certain industrial processes.
8.1.11
Pressure
controller
Saturation
temperature
computer
Pressure
control
valve
Temperature
control
valve
Temperature
controller
Superheated
steam in
Desuperheater
unit
PT100
temperature
sensor Pressure
transmitter
Steam out
Fig. 8.1.10 Steam atomising desuperheater station with downstream pressure / temperature compensation
The system shown in Figure 8.1.10 works by having the pressure controller set at the required
downstream pressure and operating the steam pressure control valve accordingly.
The 4-20 mA signal from the pressure transmitter is relayed to the pressure controller and the
saturation temperature computer, from which the computer continuously calculates the saturation
temperature for the downstream pressure, and transmits a 4-20 mA output signal to the temperature
controller in relation to this temperature.
The temperature controller is configured to accept the 4-20 mA signal from the computer to
determine its set point at 5C to 10C above saturation. In this way, if the downstream pressure
varies due to any of the reasons mentioned above, the temperature set point will also automatically
vary. This will maintain the correct water/steam ratio under all load or downstream pressure
conditions.
8.1.12
These are applications which utilise the predictable relationship between saturated steam pressure
and its temperature.
Advantages:
1. The pressure sensor may be located in the steam space, or close to the control valve rather
than in the process medium itself. This is an advantage where it is difficult to measure the
process temperature.
2. This arrangement can be used to control a number of different elements from a single point.
Disadvantage:
1. Control is open loop, in that the sensor is not measuring the actual product temperature.
Applications:
Point to note:
Good air venting is essential (refer to Module 11.12 for further details)
Safety valve
High pressure
supply
Separator
Pilot
operated
pressure reducing
valve
Condensate
Autoclave
Fig. 8.1.11 Pressure control of an autoclave
Condensate
Condensate
Automatic air vent
High pressure
supply
Jacketed pipe
Jacketed pipe
Condensate
Condensate
8.1.13
Safety valve
High pressure
supply
Multi-platen
press
Pilot operated pressure
reducing valve with on-off
function
Low pressure
to press
Condensate
Fig. 8.1.13 Pressure control on a multi platen press
Safety
valve
Direct acting
pressure reducing
valve
Automatic
air vent
Jacketed pan
High pressure
steam supply
Condensate
Fig. 8.1.14 Pressure / temperature control on a jacketed pan
Pilot
operated
pressure
reducing
valve
Electropneumatic
control system
Flow
8.1.14
In these applications the control valve will open and close to maintain a set differential pressure
between two points.
Advantages:
Disadvantage:
Application:
Point to note:
A special controller or differential pressure transmitter is required to accept two inputs; one
from the primary steam supply and the other from the flash vessel. In this way, the pressure
differential between the flash vessel and the primary steam supply is maintained under all
load conditions.
High pressure
steam in
Condensate
Differential
pressure
controller
Pneumatic
pressure
reducing
valve
Flash vessel
High pressure condensate discharging into a flash vessel
Fig. 8.1.16 Differential pressure control
Condensate
8.1.15
Surplussing control
Description
The objective is to maintain the pressure upstream of the control valve. Surplussing valves are
discussed in further detail in Module 7.3, Self-acting pressure controls and applications.
Applications:
1. Boilers on plants where the load can change by a large proportion over a very short period.
The sudden reduction in boiler pressure may result in increased turbulence and rapid flashing
of the boiler water, and large quantities of water being carried over into the pipework system.
2. Accumulators where surplus boiler output is used to heat a mass of water under pressure.
This stored energy is then released when the boiler has insufficient capacity.
Points to note:
1. Minimum pressure drop is usually required over the fully open control valve; this may mean
a line size valve is needed.
2. Not all self-acting controls are suitable for this application and it is important to consult the
manufacturer before use.
Surplussing valve
Condensate
Surplussing
valve
Pneumatic
pressure
reducing
valve
Steam to plant
Overflow
Accumulator
Fig. 8.1.18 Steam accumulator
8.1.16
Where it is necessary to control two variables with one valve it is necessary to employ two
separate controllers and sensors. It is always the case that the control valve accepts its control
signal from the slave controller.
The slave controller is configured to accept two input signals, and its set point will change (within
defined limits) depending on the electrical output signal from the master controller.
This form of control is very important where the pressure to the apparatus must be limited,
despite the heat demand.
Application:
The steam heated plate heat exchanger shown in Figure 8.1.19 is heating water circulating in a
secondary system. The heat exchanger has a maximum working pressure, consequently this is
limited to that value in the slave controller.
In order to control the secondary water temperature, a master controller and temperature
transmitter monitors the heat exchanger outflow temperature and sends a 4-20 mA signal to the
slave controller, which is used to vary the slave set point, between pre-determined limits.
Points to note:
1. An adequate pressure margin must exist between the set pressure of the safety valve and the
pressure limitation imposed by the controller.
2. The safety valve must not be used as a device to limit pressure in the heat exchanger; it must
only be used as a safety device.
Slave
Master
controller 4-20 mA controller
4-20 mA
Pneumatic
pressure
control
valve
Safety
valve
Steam in
Pressure
sensor
Flow
Temperature
sensor
Return
Condensate
Pump trap
Fig. 8.1.19 Cascaded controllers on the steam supply to a heat exchanger
8.1.17
The objective is to reduce steam pressure but not at the expense of overloading the available
supply capacity.
Application:
The upstream pipework is a high-pressure distribution pipe possibly from a distribution manifold
or steam boiler supplying plant of a non-essential nature (Figure 8.1.20). Should the demand be
higher than the supply capacity, the valve closes and throttles the steam flow, maintaining the
pressure in the upstream pipework.
The master controller is set at the normal expected supply pressure. If the master detects a drop
in upstream pressure below its set value (due to an increase in demand) it reduces the set point
in the slave controller, in proportion to pre-determined limits.
The slave closes the valve until the steam demand falls to allow the upstream pressure to
re-establish to the required value. When this is achieved, the set point of the slave controller is
set at its original value.
Master
controller
Slave
controller
4-20 mA
4-20 mA
Steam flow
High
pressure
Low
pressure
Typical settings
The output from the master controller is direct acting, that is, when the upstream pressure is at or
above its proportional band, the masters output signal is maximum at 20 mA; when at the
bottom of, or below the proportional band, the control signal is minimum at 4 mA.
When the control signal is 20 mA, the slave set point is the required downstream pressure; when
the signal is 4 mA, the slave set point is at a pre-determined minimum.
Consider the normal upstream pressure to be 10 bar g, and the maximum allowable
downstream pressure to be 5 bar g. The minimum allowable upstream pressure is 8.5 bar g,
which means that if this pressure is reached the valve is fully shut. The minimum reduced
pressure is set at 4.6 bar g.
These conditions are recorded in Table 8.1.1
Table 8.1.1
P1
bar g
10.0
9.5
9.0
8.5
8.0
8.1.18
P1 and Master
output signal
Output signal
Upstream pressure
The main objective is to limit and regulate the temperature to a particular process, where
steam is the available heat source but it cannot be used directly to heat the final product for
operational reasons.
Application:
Slave
Temperature sensor
Steam flow
Temperature sensor
Cream flow
Water
Pasteuriser
Cream return
Condensate
Fig. 8.1.21 Schematic diagram showing a pasteuriser control using the cascade principle
8.1.19
Questions
1. What is MAWP?
a| Maximum attenuated working pressure
2. One large and one small steam-heated heat exchanger have exactly the same
heating duty. Which will operate at the lower pressure?
a| The smaller one
4. What type of pressure reducing station is required when the pressure ratio
is greater than 10:1
a| A parallel station
c| A series station
d| A surplussing station
Answers
1: d, 2: b, 3: a, 4: c, 5: b, 6: b
8.1.20