Professional Documents
Culture Documents
Combined Multipulse Multilevel
Combined Multipulse Multilevel
3.1
INTRODUCTION
Static synchronous compensator is a shunt connected reactive power
3.2
by using several pulses in each half cycle of the output voltage. The 48-pulse
inverter has low harmonic rate on the ac side and can be used for high power
FACTS controllers without ac filters. The 48-pulse inverter is realized by combining
eight 6-pulse voltage source inverters with adequate phase shifts between them. The
configuration of 48-pulse inverter is depicted in the Fig. 3.1 where each of the VSI
output is connected to the phase shifting transformer. Four of them are connected to
a Y-Y transformer and the remaining four to a -Y transformer. The output of the
phase shifting transformers is connected in series to cancel out the lower order
harmonics.
Coupling
transformer
Gate pulse
pattern
Phase shifting
transformer
Y-Y
+11.25
-11.25
-Y
-18.75
-11.25
Y-Y
-3.75
+3.75
-Y
-33.75
+3.75
Y-Y
+3.75
-3.75
-Y
-26.25
-3.75
Y-Y
-11.25
+11.25
-Y
-41.25
+11.25
48
3.3
three-level diode clamped multilevel inverters with an adequate phase shifts between
them. The voltages generated by each of the three level inverters are applied to the
secondary windings of four different PSTs. Two of them are Y-Y transformers with
a turns ratio of 1:1 and the remaining two are -Y transformers with a turns ratio of 1:3.
The primary windings of the PSTs are connected in series and the proper pulse pattern as
tabulated in Table 3.2 is maintained so that the fundamental components of the individual
3-level inverters are added in phase on the primary side.
In this configuration the number of PST requirement is reduced to half of
that needed in 48-pusle operation. Though the configuration is similar to a 24-pulse
inverter, it provides very less THD as that of the 48-pulse inverter. This is possible
by selectively eliminating the 23rd and 25th harmonic components through the
appropriate selection of the conduction angle () of the individual three-level
inverter units.
49
Coupling
transformer
Gate pulse
pattern
Phase shifting
transformer
Y-Y
+7.5
-7.5
-Y
-22.5
-7.5
Y-Y
-7.5
+7.5
-Y
-37.5
+7.5
= 180 1 -
m
(3.1)
50
Fig. 3.5 Phase and line voltages of diode clamped 3-level inverter
51
Carrying out the Fourier analysis of the inverter output voltage, the
instantaneous phase-to-neutral voltage is expressed as:
v an ( t ) = Van sin mt
m=1 m
where Van m =
-
cos m
m
2
2VDC
(3.2)
(3.3)
m=1
(3.4)
4 VDC
m
m
sin
cos
m
2
6
(3.5)
where Vab =
m
The voltages vbc(t) and vca(t) exhibit a similar pattern except that they are
phase shifted by 120 and 240 respectively. Similarly the phase voltages vbn(t) and
vcn(t) are also phase shifted by 120 and 240 respectively. It contains only odd
harmonics in the order of 6r1, where r is a numeral can assume values 1, 2, 3,..
In general star and delta connected windings have a relative phase shift of
30 and the three-level inverters connected to each of these Y and transformers
will give an overall 12-pulse operation and offers a better harmonic performance.
The output voltage will have a twelve pulse waveform, with harmonics of the order
of 12r1. Thus the twelve pulse inverter will have 11th, 13th, 23rd, 25th,..
harmonics with amplitudes of 1/11th, 1/13th, 1/23rd, 1/25th, respectively of the
fundamental ac voltage.
The relationship between the phase-to-phase voltage and the phase-to-neutral
voltage is expressed as:
v ab = ( -1)
3 v an m
(3.6)
v an ( t )1 =
1 Vabm
sin mt
r
3 m=1 ( -1)
(3.7)
m = 6r 1, r = 0,1, 2,.....
If the VSI2 produces phase-to-phase voltages lagging by 30 with respect to
VSI1 and with the same magnitude, it is given by
(3.8)
(3.9)
m=1
(3.10)
(3.11)
m=1
(3.12)
since
m=1
(3.13)
Similarly two twelve pulse inverters phase shifted by 15 from each other
can provide a 24-pulse inverter, with much lower harmonics in the ac side. The ac
output voltage will have 24r1 order harmonics, i.e., 23rd, 25th, 47th, 49th,..
53
van 24 ( t ) =
(3.14)
(3.15)
54
3.4
with the transmission line using a step-down transformer having leakage reactance
XL as shown in Fig.3.11. The ac voltage difference across this transformer leakage
reactance produces reactive power exchange between the inverter and the power
system at the point of common coupling.
56
The system parameters and the system voltages are three phase balanced.
ii)
iii)
power system. The reactive power supplied by the STATCOM is either inductive or
capacitive depending upon the relative magnitude of fundamental component of vs
with respect to vm. If |vm| > |vs|, the VSI draws reactive power from the ac bus
whereas if |vm| < |vs|, it supplies reactive power to the ac system.
disa -R
dt L
disb = 0
dt
disc 0
dt
0
-R
L
0
v ma -vsa
0 isa
1
0 isb + v mb -vsb
L
-R
v -v
mc sc
L isc
(3.16)
58
disd
dt
disq
dt
-R
= L
-
v md -vsd
isd
1
-R L
i
v
-v
mq sq
L sq
(3.17)
3
( Vsd Isd +Vsq Isq )
2
(3.18)
Since PWM technique is used in STATCOM, and all the voltage harmonics
produced by the inverter are neglected, the equation relating the dc side and ac side
can be written as
Vsd = kM a Vdc cos
(3.19)
Vsq = kM a Vdcsin
(3.20)
V
where = tan -1 sq is the angle between the inverter voltage and the system
Vsd
voltage.
Ma =
(V
2
sd
+Vsq2 )
kVdc
Idc
3
( kM a Vdc cosIsd + kM a Vdc sinIsq )
2
3kM a
=
( Isd cos+ Isq sin )
2
dV
3kM a
= Cdc dc =
( Isd cos+ Isq sin )
dt
2
dVdc
dt
Vdc Idc
3kM a
2 Cdc
(I
sd
59
(3.21)
Using equations (3.17) and (3.21), the complete system equation could be
expressed in matrix form as follows:
disd
-kM a
-R
v md
cos isd
dt
L
L
di
-kM a
-R
1
sq
sin isq + v mq
dt =
L
L
3kM
3kM
dV
a
a
dc
0
dt 2C cos 2C sin
Vdc
0
dc
dc
(3.22)
Using equation (3.17), the reference input to the PWM modulator is derived
as follows
dI
(3.23)
dIsq
dt
(3.24)
The equations (3.23) and (3.24) are realized to establish the STATCOM
operation in the closed loop control scheme.
3.5
60
compared with the reference current isq* derived from the ac voltage controller and
the error so obtained is stabilized through another PI controller to get the equivalent
q axis reference voltage. The parameters of these PI controllers are tuned in order to
minimize the integral square error (ISE) and integral time absolute error (ITAE).
The optimal parameters of PI controllers are tabulated in Table 3.3. Further the
equations (3.23) and (3.24) are realized in the inner current control loop in order to
obtain the reference wave for the PWM modulator.
61
3.6
PI Controllers
Kp
Ki
PI1
0.8
PI2
2.56
9.2
PI3
0.1
40
PI4
0.1
40
Significant Harmonics
Analytical
Simulation
rd
25.095
25.21
25th
23.087
24.27
47th
187.36
189.56
49th
179.715
183.02
23
62
a) Output voltage
b) THD
Fig. 3.14 Multipulse-multilevel inverter output voltage and its THD
The initial load in the system is with the ratings of P = 300 MW,
QL = 150 MVAR connected at load bus B3 through the circuit breaker CB1.
The transmission line current lags the voltage by 60 as seen in Fig. 3.15 before
t = 0.4 s resulting in a power factor of 0.5 lag and the bus voltage magnitude is at
0.975 pu as the STATCOM is inactive.
63
Fig. 3.15 Transmission line current and voltage with and without STATCOM
64
The d-q components of the STATCOM current are shown in Fig.3.18. It draws a
very small amount of real power from the network to compensate for the losses in the
inverter switches and coupling transformer and maintain the dc link voltage constant. This
is apparent from the id component of current depicted in Fig. 3.18.
65
The dc link voltage is maintained constant at the desired set reference value
as shown in Fig.3.19. It is observed from the Fig.3.20 that the ac terminal voltage
settles to 1 pu. The phase difference between the transmission line current and the
voltage is reduced to 14.5 as described in Fig.3.15 which improves the power factor
of the line from 0.5 lag to 0.968 lag.
66
67
Fig. 3.22 Reactive power injected by the STATCOM under varying load
68
The bus voltage is regulated to 1.002 pu as in Fig.3.24 and the phase angle is
corrected to 15 lag which leads to a power factor of 0.9659 lag. Thus the line
current is almost in phase with the voltage as depicted in Fig.3.25. The phase angle
difference between the line current and voltage is separately highlighted in Fig.3.26.
Fig. 3.25 Transmission line voltage and current under varying load
69
Fig. 3.26 Variation of phase angle between the line current and voltage
70
Duration
STATCOM
(s)
Modulation Injected
Bus
Index (Ma) Reactive (lag) Voltage
Power,
(pu)
Qinj (pu)
Load
0 0.2
Not
P = 300MW
Connected QL = 150MVAR
0.2-0.4
Connected
60
0.975
P = 300MW
QL = 150MVAR
0.778
0.24
14.5
0.999
0.4-0.6
P = 300MW
QL = 150MVAR
Connected
P = 300MW
QL = 180MVAR
0.83
0.49
15.1
1.002
0.6-0.8
P = 300MW
QL = 150MVAR
Connected
P = 300MW
QC = 100MVAR
0.76
0.13
15.5
1.002
It is seen from the Fig.3.25 that there is a dip in the supply voltage and the
supply currents are lagging. However when the STATCOM is connected to the
power system a uniform voltage profile is maintained and the three phase supply
currents are almost in phase with the supply voltage under varying load. Hence it is
observed from the simulation results that the STATCOM plays a vital role in
improving the power factor and regulating the bus voltage.
3.7
SUMMARY