AMT-MT SERIES

Accessories
Item

Power

Business Group

Rated current quick index table


Standard parts Option parts

Name plate

Earthing terminal

Rated current (A)

Capacity
(kVA)

Primary
(20000V)

Secondary
(400V)

Base

315

9.1

455

Lifting lug

400

11.5

577

Warning label

500

14.4

722

HV coil terminal

630

18.2

909

LV coil terminal

800

23.1

1155

No voltage tap changer

Bi-direction wheel

1000

28.9

1443

1250

36.1

1804

Digital temp. monitor

1600

46.2

2310

Dial type thermometer

2000

57.7

2887

Anti-vibration pad

2500

72.2

3609

Static shield

Cooling fan

Enclosure

LV copper busway

Flexible copper strip

Rated current =

(KVA)x1000

3 x Rated voltage (V)

AMORPHOUS CAST RESIN


DRY TYPE TRANSFORMER
Capacity: Up to 5000kVA
Voltage: Up to 36kV
(A)

Ordering or inquiring information required


Phase

Three

Capacity
HV side

Single

Frequency

50Hz

kVA

Condition

Altitude

Connection

connection

Y connection

Connection

connection

Y connection

Vector group

Dyn11

Other

Rated voltage
Tap

Rated voltage

Standard

IEC 60076-11

Impedance

4% 6%

Cooling type

Natural air (AN) Forced air (AF) ( AF capacity:

Special
accessories

Other
%

Yes ( Protection level: IP20 IP23 IP


No (IP00)
Yes

Hz

m, ambient temp.

No Yes( 2 2.5% Other:

LV side

Enclosure

60Hz Other

Dd0

kVA )
) Cable entrance
(with enclosure)

HV side Top Bottom Side


LV side Top Bottom Side

Bi-direction wheel Anti-vibration pad Temperature( digital type dial type )


Static shield between HV & LV Other

No ( Standard accessories )

Quantities

Transformer
comply with
E2/C2/F1
class

Partial
discharge
free

70% ~ 80%

Industrial Appliance Business Unit Export Division

No pollution,
all materials
can be
recycled

102 Minsheng Rd., Neihai Village, Tayuan, Taoyuan County, Taiwan, 33759, R.O.C.
TEL : +886-3-3863123 #1304
FAX : +886-3-3863123 #1380
E-mail Address : chienge@heap.tatung.com.tw
Head ofce

No. 22, Sec. 3, ChungShan N. Rd., Taipei City, Taiwan, 10435, R.O.C.
TEL: +886-2-25925252#3633
FAX: +886-2-25984425
Web site: www.tatung.com

2012.10

No load loss
reduced

Industrial Appliance
Business Unit

AMT-MT SERIES
Specication

Introduction of amorphous alloy


6

Raw materials are melted down in induction furnace, melt jet is quenched at 10 per second to
form an amorphous strip. Atoms are solidied before crystallization to have non-crystalline structures
like glass resulting in excellent properties as a soft magnetic metal.

Comparison of amorphous alloy and silicon Steel

Amorphous alloy ribbon

Cast-resin dry type, self cooled


Indoor
Class F
100K

Amorphous core

Phase

Primary voltage
(V)

Secondary
voltage (V)

Three

F21000 F20500
R20000 F19500
F19000

400/231

Hysteresis curve comparison


Tesla

2.03T
1.56T

Silicon steel core

Features of amorphous alloy compare to silicon steel

Silicon steel (CRGO)


Amorphous alloy

1
0

Lower retentivity
(1/3)
Less thickness
(1/10)
Higher resistance
(3 times)

Lower hysteresis losses


Less eddy current
Less eddy current

1
2

Oersteds

Benets of using amorphous core transformer

Energy saving
No pollution
Less co2 emission
Environmental
friendly

Fire prevention
Excellent insulation
Safety

Low noise
Long operation life
Quality

Patented amorphous core manufacturing process is adopted resulting in superior


low core loss and with low load loss design of coil increasing the transformer
efciency greatly, no-load loss of the transformer is about 70~80% lower than the
traditional silicon ones.
Non-polluted insulating materials and low energy consumption amorphous alloy
are adopted as well as the energy saving characteristics of the transformer,
achieve the goal of less CO2 emission and environment friendly.

Rated
capacity
(kVA)
315400
500630
8001000
12501600
20002500

Frequency
(Hz)

Connection

Standard

50

/Y

IEC 60076-11

315
400
500
630
800
1000
1250
1600
2000
2500

20000

400

Vector
group

No load Load loss


loss(W)
(W)

Dyn11

365
450
480
530
580
710
800
910
1070
1380

3300
3680
4500
5550
6520
7650
9150
11290
13800
16200

Efciency(%)
30%
50% 100%
load load load
99.30 99.25 98.85
99.35 99.32 98.97
99.41 99.36 99.01
99.45 99.39 99.04
99.51 99.45 99.12
99.53 99.47 99.17
99.56 99.50 99.21
99.60 99.53 99.24
99.61 99.55 99.26
99.62 99.56 99.30

No load
current(%)

Impedance
(reference)
(%)

0.6
0.6
0.5
0.5
0.5
0.4
0.4
0.3
0.3
0.3

4.0
4.0
4.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0

Tolerance is comply with IEC 60076-11.

Dimension
Outline dimension (mm) IP00
X
Y
Z
1400
800
1500
1500
800
1550
1500
800
1650
1650
1000
1700
1650
1000
1750
1700
1100
1800
1700
1200
2000
1900
1200
2100
2200
1900
1200
2100
1200
2300

Capacity
(kVA)
315
400
500
630
800
1000
1250
1600
2000
2500

Approx.
weight(kg)
2200
2700
2900
3400
3900
4500
5200
6200
7100
8900

Outline dimension (mm) IP20


X
Y
Z
1900
1300
2000
2000
1300
2100
2000
1300
2200
2100
1500
2200
2100
1500
2250
2200
1600
2300
2200
1600
2500
2400
1700
2600
2400
1700
2700
2500
1700
2800

Approx.
weight(kg)
2700
3200
3500
4000
4500
5100
5800
6900
7900
9700

The dimensions and weights are reference only, nal drawing will be issued after receipt of order.

Outline of transformer

H1

H2

H3

Low loss
High efficiency

Secondary voltage
1.1kV
3kV
---

Silicon steel

Applied voltage
BIL

Primary voltage
24kV
50kV
125kV

Characteristics (at 75 )
Capacity
Prim.
Sec.
(kVA) voltage(V) voltage(V)

Crystal metal model

Dielectric Strength

Rating

Atom model of material & core structure

Non-crystal amorphous model

Type
Service condition
Insulation
Temperature rise

The non-inammable epoxy resin is adopted for casting coils of the transformers to
have excellent dust-proof, anti-moisture and high insulating abilities, the coil has
passed the C2/E2/F1 test of IEC 60076-11 ensuring the operation safety.
Patented three-phase three-leg amorphous core structure owned by Tatung is
adopted for the transformer resulting in very low noise level (lower than the NEMA
standard about 3~5dB). The low operating temperature due to low losses help
longer life span of the transformer.

Y
X

IP00

IP20

AMT-MT SERIES