Professional Documents
Culture Documents
DISCLAIMER:
Always double-check the values given in this document with
the actual laws. For corrections or clarifications, email
arch.pedrosantosjr@gmail.com.
Repealing clause
RA 9514 repeals PD 1185 (the old Fire Code).
Outline of RA 9514
1.
2.
3.
4.
5.
6.
7.
Interpretation
Coverage
Definition of terms
Authority of the BFP
Reorganization of the BFP
Fire brigades, safety practitioners
Assistance to the BFP
Outline of RA 9514
8.
9.
10.
11.
12.
13.
14.
RULE 3
Definition of terms
Abatement
Any act that would remove or neutralize a fire hazard
Automatic fire
suppression system
Fire
marshall
The head of the City or the Municipal Fire Station
Standpipe
system
A system of vertical pipes in a building to which fire
hoses can be attached on each floor,
Combination standpipe
A pipeline system filled with water and connected to
a constant water supply
Dry
standpipe
A standpipe system in which pipes are normally not
filled with water. Water is introduced into the system
through fire service connections when needed.
Fire
alarm
Any visual or audible signal produced by a device or
system to warn a buildings occupants of the
presence of fire
Fire
alerting
system
A fire alarm system activated by the the presence of
fire where the signal is transmitted to designated
locations instead of sounding a general alarm
Fire
wall
A wall designed to prevent the spread of fire, having a
fire resistance rating of not less than 4 hours with
sufficient structural stability to remain standing even
if construction on either side collapses under fire
conditions
Flame
retardant
Any compound which when applied improves the
resistivity or fire resistance quality of a material
High-rise
building
Buildings 15 meters or more in height
Horizontal
exit
A passageway from one building to another, through
or around a wall, on approximately the same floor
level
Means
of
egress
A continuous and unobstructed route of exit from
one point in a building to a public way
Occupancy
The purpose for which a building or space is used
Occupant
load
The maximum number of persons that may be
allowed to occupy a particular building or space
Overloading
The use of electrical appliances which draw or
consume electrical current beyond the designed
capacity of the existing electrical system
Sprinkler
system
A piping system integrated in a building with outlets
arranged in a systematic pattern which automatically
discharges water when activated by heat or fire
combustion products
Fire
hazard
Any condition or act which increases the probability
of the occurrence of fire, or which may hinder or
interfere with fire-fighting operations
Fire
trap
A building unsafe in case of fire because it will burn
easily or because it lacks adequate exits
Fire
lane
The portion of a roadway that should be kept
unobstructed at all times for the expedient
operations of fire-fighting units
Flame
spread
rating
Time in which flame will spread over the surface of a
burning material
RULE 9
General enforcement
General enforcement
Inspection of all buildings shall be done by
the Fire Marshall
Fire Safety Inspection Cetrtificate (FSIC)
shall be a prerequisite for permits/licenses,
including:
Occupancy permit
Business permit
General enforcement
The Fire Marshall and the Building Official
shall review designs/drawings and issue the
Fire Safety Evaluation Clearance (FSEC) if
the design is determined to be in accordance
with the Fire Code
Evaluation and
inspection
Construction inspection
The Fire Marshall shall conduct inspections
during construction to ensure that plans are
being followed
Routine inspection
Routine inspection
FALAR
FALAR applicability
For all buildings:
FALAR 1
FALAR 2
FALAR 1
Documentation on fire and life safety
features of the facility
A written report prepared by the Architect
and his Fire Protection Consultant
A compilation of plans and specs and design
analysis
FALAR 2
Documentation submitted by
contractor/CM certifying that construction
was in accordance with FALAR 1
A compilation report of all approved
submittals, test forms, acceptance forms
Shall be included in the as-built documents
given by contractor to owner
FALAR 3
Documentation of required periodic
maintenance and upkeep of facility
Written report prepared by the building
owner, his fire safety officer
A compilation of the maintenance and
testing records
FSEC
FSEC
Fire Safety Evaluation Clearance
Released once building plans and specs are
found to be in accordance with the Fire Code
Required for building permits
FSIC
FSIC
Fire Safety Inspection Certificate
Certifies that the building was inspected and
was found to be OK
Required for occupancy permits, business
permits, permits to operate, PHILHEALTH
accreditation for hospitals, DOH License to
Operate
Making sense of
everything
RULE 10
Means of egress
Means of egress
A continuous, unobstructed route of exit
from any point in the building to a public
way
Shall be integral or permanently affixed to a
building
Minimum width: 915mm
Number of exits
For any storey, mezzanine, balcony, etc:
0-499 occupant load: 2 exits
500-1000 occupant load: 3 exits
1000 or more: 4 exits
Headroom
Minimum of 2.00m
Doors
Provide a self-closing mechanism for exit
doors
Clear opening: 710mm-1220mm
Maximum threshold height: 13mm
Panic hardware
A mechanical device which when pushed
from the inside will cause the door to open
Maximum required force: 7kg-f
2/3 the width of the door
760-112mm above the floor
Panic hardware
A mechanical device which when pushed
from the inside will cause the door to open
Maximum required force: 7kg-f
2/3 the width of the door
760-112mm above the floor
Stairs
All stairways designated as a means of
egress should be continuous from the
uppermost floor level to the ground floor
Two sets of requirements
New stairs
Existing stairs
Handrails
760mm-865mm from upper surface of tread
Ramps
Ladders
Not allowed as fire escape or means of
egress
Exit marking
Label all exits as EXIT
Provide directional signs for locations where
the direction of travel to exit is not obvious
The word EXIT should be in letters at least
15cm high with strokes of letters at least
19mm wide
Features of fire
protection
Fire alarms
Notifies occupants of the building and, when
required, emergency forces
Automatic fire department notification is
required for:
Wet standpipes
Wet standpipes required for the following:
Aseembly occupancies with at least 1,000 occupant load
Schools, hospitals, businesses, hotels, etc. 4 storeys or
taller
Hazardous occupancies exceeding 1,860 sqm per floor
Exceptions:
Buildings with an approved sprinkler system
Wet standpipes
All portions of the building must be within 6
meters of a nozzle attached to a 22.00m long
hose
Minimum of 64mm diameter
Places of assembly
Occupant load
Concentrated use without fixed seats, such
as auditoriums, places of worship, dance
floors: 0.65 sqm/person
Less concentrated use such as conference
rooms, dining rooms, gyms: 1.40sqm/person
Standing rooms/waiting space:
0.28sqm/person
Seating
Rows of seats back to back: 830mm
At least 300mm from back of one seat to
front of the next seat
Seats between aisles: 14 maximum
Seats between wall and aisle: 7
Seats without arms: Allot 600mm/person
Educational
occupancies
Occupant loads
Classroom: 1.80sqm/person
Shops, laboratories: 4.60sqm/person
Dry nurseries with sleeping facilities:
3.30sqm/person
Rooms with greater than 50 occupants
shall be treated as a place of assembly
Number of exits
At least two exits from any room with
capacity of 50 or more persons, or area
of more than 93 sqm.
Healthcare
Occupant loads
Sleeping departments: 11.1sqm/person
In-patient treatment departments:
22.3sqm/perosn
Door widths
1120mm: sleeping rooms, diagnostic and
treatment rooms (surgery. X-Ray, PT, etc.)
910mm: All other rooms
Detention and
correctional
Occupant load
11.1sqm/peron
Residential
Occupant load
18.60sqm/person
Except for single and two-family dwellings
Hotels
Minimum corridor width: 1120mm
Minimum umber of exits: 2 for every floor
Travel distance to exits:
From room door to exit: 30.00m
From guest suite to corridor door: 23.00m (w/o
sprinklers)
From guest suite to corridor door: 38.00m (w/
sprinklers)
Apartment buildings
Minimum corridor width
For less than 50 persons: 910mm
Fore more than 50 persons: 1120mm
Mercantile
Mercantile
Stores, markets, malls, supermarkets,
department stores, restaurants of less than 50
occupants
Class A: Gross area of 2,787sqm or more, 3 floors
Class B: Gross area of 287-2,787sqm, 2 floors
Class C: Gross area less than 287sqm, street floor only
Occupant load
Business
Business
Businesses other than mercantile
Businesses that typically involve services and
not the display and sale of merchandise
Examples: Doctor/lawyer/dentists office,
internet shops, barbershops, general offices
Occupant load
9.30sqm/person
Sprinkler requirements
All high rise buildings shall be provided with a
fully electrically supervised sprinkler system
Other occupancies
Industrial
Occupant load: 9.30sqm/person
Minimum corridor width: 1120mm
Travel distance:
31.00m if no sprinklers
46.00m if with sprinklers
Exit capacity
The capacity of an exit is measured in terms
of its width
Width of level components (corridors/ramps)
Width of non-level components (stairways)
Occupant load
Maximum number of persons allowed to
occupy a space at any time
Floor area/occupant load factor
Occupant load
Maximum number of persons allowed to
occupy a space at any time
Floor area/occupant load factor
Features of fire
protection
Places of assembly
Educational
occupancies
Healthcare
Healthcare