Professional Documents
Culture Documents
CHAPTER 2 Psychrometry and Air-Conditioning
CHAPTER 2 Psychrometry and Air-Conditioning
2.0 Introduction
Mixtures of air and water vapour are considered moist atmospheric air (i.e. a mixture of dry
air and water vapour).
It is often necessary to provide a controlled atmosphere in buildings where industrial
processes are to be carried out, or to provide air-conditioning in private, public and industry
buildings. The properties of atmospheric air have to be considered in these problems, and this
is a subject which is receiving an increasing amount of attention and application. Another
topic which will be considered is that of the cooling tower by means of which large
quantities of cooling water are cooled for recirculation. These topics come under the title of
psychrometry (sometimes called hygrometry).
2.1
Psychrometric mixtures
, where
ms
ma
ms m s / V s a
ma ma / V a s
PsV
Rs T
Where
and
Rs
ma
PaV
Ra T
Ra
(2.2)
(2.1)
PsV s
P
P
T
18
s 0.622 s
T
PaV a 28.96 Pa
Pa
However,
P Pa Ps
Pa P Ps
or
Ps
Thus, specific humidity, 0.622
P Ps
Relative humidity,
ms
PsV
Rs T
and
(2.3)
ms
ms sat
ms sat
PgV
Rs T
P
g
Percentage saturation, = ratio of the specific humidity of mixture to the specific humidity of
mixture when saturated at same temperature
(2.4)
100
(2.5)
Solutions
From the steam table, at 17C
Ps
Pg
0.6
or
Ps
0.622
P Ps
Pg 0.01936bar
Ps
0.01936
Thus,
Ps= 0.012bar
0.012
0.622
0.0072
1.01326 0.012
1.2 0.8721
Td 5 (10 5)
9.06C
1.276 0.8721
Figure 2.3
Two thermometer situated in a stream of unsaturated air are separated by a radiation screen.
One of them indicates the air temperature and is called the dry bulb temperature. The bulb of
the second is surrounded by a wick which dips into a small reservoir of water and the
temperature indicated is called the wet bulb temperature. As the air stream passes the wet
wick, some of the water evaporates and this produces a cooling effect at the bulb. The
amount of this wet bulb depression depends on the relatives humidity of the air. If the
relative humidity is low, then the rate of evaporation at the wick is high, and hence the wet
bulb depression is high.
Psychrometer Chart
0.622 Pg
( P Pg )
100 100 ( P Pg )
g
0.622 Pg
For a given barometric pressure, P, the percentage saturation is a function of and P g. The
barometric pressures are in the range 0.95 1.05bar.
2.3 Specific Enthalpy, Specific heat capacity, and specific volume of moist air
Specific enthalpy of moist air
The enthalpy of a mixture is the sum of the enthalpies of the individual constituents,
mh ma ha ms hs
h C pat (hg _ at _ t)
For specific heat capacity of moist air, Cp
Cp
ma C pa
m
ms C ps
m
Then, the specific heat capacity of mixture per unit mass of dry air,
C p C pa C ps
For specific volume of the mixture per unit dry air is convenient to use the specific volume of
dry air, a
Ra T
Pa
The sensible heat load the energy added per unit time which increases the dry
bulb temperature
The latent heat load the energy added per unit time due to the enthalpy of the
moisture added plus the heat required to evaporate the moisture added
and
t2 t x
ma (h2 hx ) ma (2 1 )(hg _ at _ t2 )
ma 2 ma 3 ma 4
2 ma 2 3 ma 3 4 ma 4
ma 2 h2 ma 3 h3 ma 4 h4
r
ma 4 3 2 h3 h2
rh2 (1 r )h3 h4
Where r is the mass flow of dry re-circulated air per unit mass flow of dry air supplied to the
room. Thus,
r
h3 h4
h3 h2
Thus, gives:
r 2 (1 r )3 4
Therefore;
r
3 4 h3 h4 line _ 3 4
3 2 h3 h2 line _ 3 2
If the air undergoes sensible cooling in the cooling coil and dehumidification. Point A is
called the apparatus dew point.
The efficiency of the cooler:
Coil bypass factor =
line _ 5 A
line _ 4 A
line _ 4 5
line _ 4 A
Dehumidification may also be achieved by passing the air through a spray cooler supplied
with chilled water. The apparatus dew point is then the water temperature. In this case the
contact factor is usually renamed the spray cooler, or washer, efficiency and is expressed as a
percentage.
2.5 Winter Air-Conditioning
A typical conventional type air-conditioning system for winter use is shown in Figure 2.12
and the corresponding state points are shown on Figure 2.12b. The various parts of the
system are similar to summer air-conditioning system except for the humidifier. The
humidification process 5-6 in the case shown is assumed to be adiabatic and take place at
constant wet bulb if pumped recirculation of the water is used as shown in Figure 2.12a.
h6 h5
6 5
Induced draught
Natural draught
Figure 2.13 Cooling Tower
This is done by spraying the water into the air over a pond, or into the air passing through a
cooling tower. The cooling water can be theoretically be cooled to the wet bulb temperature
of the incoming air, the figure used in design for cooling water leaving the tower is about 8K
above the wet bulb temperature. Induced and natural draught cooling towers are shown in
Figure 2.13. The cooling effect is greater with an induced draught compare to a natural
draught cooling tower due to the increase flow of air.
Example 2.2 :
Water at 40oC enters a cooling tower at a rate of 200kg/s. The water is cooled to 25 oC in the
cooling tower by the air which enters the tower at 1 atm, 20 oC, 60% relative humidity and
leaves saturated at 25 oC. Determine:
(a) The volume flow rate of the air entering the cooling tower
(b) The required mass flow rate of the make-up water
Solutions:
(a) From the conservation of mass and energy:
Dry air : ma1 m a 2 ma
Water : m3 1 ma1 m4 2 ma 2
m3 m4 ma ( 2 1 ) m w
Energy : Q W me he mi hi
ma ( h2 h1 ) ( m3 m w ) h4 m3 h3 0
or
ma
m3 (h3 h4 )
(h2 h1 ) ( 2 1 )h4
ma
200(167.57 104.89)
393.9kg / s
(75 42) (0.02 0.0088) 104.89
3
Volume flow rate, q ma 1 393.9(0.84) 330.9m / s