LG Checkpoint-codes
Versie 2.4P-M
vervangt U02.3.M
Hoofdstukindeling
Single A (vloer- & plafond UV / cassette UT / kanaal UB)........................................04
- Aan / Uit - Inverter
UU..(W)
- Variabel (aan/uit)..........................................................................................................26
AT-C.. / AT-H.. / LB-C.. / LB-D.. / LB-G.. / LB-H.. / LT-B.. / LT-C.. / LT-D.. / LT-E.. /
LV-B.. / P..AH
Multi-split ......................................................................................................................39
- Inverter
FM..AH
- Variabel (aan/uit)..........................................................................................................92
M..AC/AH
LG
5. Trouble Shooting
Title
Cause of error
01
02
06
Check the
Connector connection
Is the voltage of
the sensor 2.5Vdc
at 25C
No
Correct connection
Yes
Is it normal ?
No
Correct connection
Unplugged
Yes
Plugged
No
Correct connection
10k
2.5Vdc
5. Trouble Shooting
03
Title
Cause of error
Communication Error
(Wired remote controller)
Connector connection
error
Faulty PCB / Remote
controller
Connection wire break
Connection of wire
Main PCB Volt. DC12V
Noise interference
No
Correct connection
Or change connection wire
No
Re-soldering component
Or change the PCB
Wired R/C
Indoor Unit
S 12V GND
(YL) (RD) (BR)
12V S GND
(RD) (YL) (BR)
No
Correct connection
Or change the PCB
12Vdc
12Vdc
No
Adjust the state
of installation
- 68 -
5. Trouble Shooting
Title
04
Drain pump
/ Float switch
Cause of error
Float switch open.
(Normal : short)
Water over flow
CN-Float
No
Check Drain Pump
CN-Float
Yes
Is the float
switch clean ?
No
Clean float switch
Yes
Is it normal ?
Is it normal ?
Yes
Is the resistance of f
loat switch normal
(short) ?
No
Correct connection
Or re-soldering PCB
Yes
No
Change the float switch
Is the resistance of
Drain Pump? Normal
( about 400 ) ?
No
Correct connection
Or re-soldering PCB
No
Change the Drain Pump
Yes
Is the drain
pump clean ?
No
Clean drain pump
Yes
Check drain tube
installation
- 69 -
5. Trouble Shooting
Title
09
EEPROM
Check sum (Indoor)
10
BLDC motor
fan lock (Indoor)
Cause of error
No
Remove obstruction
Yes
Check the connection
status between PCB and
fan motor
Is it normal ?
No
Correct connection Or re-soldering PCB
Yes
Check the DC Motor
signal
Is it normal ?
No
Change Indoor Motor
- 70 -
5. Trouble Shooting
05
/
53
Title
Communication
(IndoorOutdoor)
Cause of error
Is the connection of
GND,GND1,GND2,
correctly connected?
No
Correct connection
Yes
No
Needs electric work
Change PCB
Yes
Check the communication
wires are correctly
connected.
Is it normal ?
Yes
Check the resistance
between communication
line and GND.
(Normal : Over 2M)
Is it normal ?
No
Adjust the connection
of wire Confirm the
wire of "Live",
"Neutral", "Signal"
No
Correct connection
Yes
Is connector for
communication
correctly connected?
- 71 -
5. Trouble Shooting
21
Title
DC Peak
Cause of error
Is it normal ?
Yes
Is it normal ?
(1 Ph : 230V 10%
3 Ph : 400V 10% )
Yes
No
Correct
connection
Check DC link
capacitor Is it normal?
(Refer to belows)
Yes
Check Over load condition
- Overcharging of
refrigerant
- Pipe Length
- Condenser is blocked
- Outdoor fan is locked
No
Change
Compressor
No
Needs electric work
No
Change DC link
capacitor
Or Main PCB
Remove obstruction
Change outdoor fan
or motor
Change refrigerant
No
Change Main PCB
No
Change
Compressor
3 Phase
DC Link Voltage
Type
Operating
DC280V 10%
DC280V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%
PFC
DC300V 10%
DC380V 10%
PSC
PFC
PFC
DC540V 10%
DC540V 10%
DC540V 10%
DC500V 10%
DC680V 10%
DC680V 10%
PFC
DC540V 10%
DC680V 10%
PSC
PSC
PFC
PFC
PFC
PFC
PFC
AUUW606D
AUUW368D
AUUW428D
AUUW488D
AUUW608D
- 72 -
Non operating
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
AUUW126C
AUUW186C
AUUW246D
AUUW306D
AUUW366D
AUUW426D
AUUW486D
10
5. Trouble Shooting
Title
22
Max. C/T
Cause of error
Malfunction of compressor
Blocking of pipe
Low voltage input
Refrigerant, pipe length, blocked,
Over current
Is it normal ?
Yes
Is it normal ?
(1 Ph : 230V 10%
3 Ph : 400V 10% )
Yes
No
Correct
connection
Check DC link
capacitor Is it normal?
(Refer to belows)
Yes
Check Over load condition
- Overcharging of
refrigerant
- Pipe Length
- Condenser is blocked
- Outdoor fan is locked
No
Change
Compressor
No
Needs electric work
No
Change DC link
capacitor
Or Main PCB
Remove obstruction
Change outdoor fan
or motor
Change refrigerant
No
Change Main PCB
No
Change
Compressor
3 Phase
DC Link Voltage
Type
Operating
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC280V 10%
DC280V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%
PFC
DC300V 10%
DC380V 10%
PSC
PFC
PFC
DC540V 10%
DC540V 10%
DC540V 10%
DC500V 10%
DC680V 10%
DC680V 10%
PFC
DC540V 10%
DC680V 10%
AUUW126C
AUUW186C
AUUW246D
AUUW306D
AUUW366D
AUUW426D
AUUW486D
PSC
PSC
PFC
PFC
PFC
PFC
PFC
AUUW606D
AUUW368D
AUUW428D
AUUW488D
AUUW608D
- 73 -
Non operating
11
5. Trouble Shooting
40
C/T
Internal circuit
Cause of error
Display
code
No
Correct connection
Yes
Check C01N
Is it normal (4.0Vdc )?
C01N
No
Change Main PCB
Yes
Check Check TRANS
Is it normal?
No
Change TRANS
Yes
Change main PCB
- 74 -
12
5. Trouble Shooting
Title
23
DC Link
Low voltage.
28
DC Link
High voltage
25
Input voltage
Cause of error
Is it normal ?
Yes
Is it normal ?
Yes
No
Correct
connection
Check TRANS1
No
Change
Compressor
CN_TRANS 1
No
Change
Compressor
Model
1 Phase
3 Phase
DC Link Voltage
Type
Operating
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC280V 10%
DC280V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%
PFC
DC300V 10%
DC380V 10%
PSC
PFC
PFC
DC540V 10%
DC540V 10%
DC540V 10%
DC500V 10%
DC680V 10%
DC680V 10%
PFC
DC540V 10%
DC680V 10%
AUUW126C
AUUW186C
AUUW246D
AUUW306D
AUUW366D
AUUW426D
AUUW486D
PSC
PSC
PFC
PFC
PFC
PFC
PFC
AUUW606D
AUUW368D
AUUW428D
AUUW488D
AUUW608D
- 75 -
Non operating
13
5. Trouble Shooting
Title
24
Cause of error
Switch
Spec
Model
Yes
Is the soldering
state of connector is
normal?
No
Re-soldering component
Yes
Is the SVC Valve
opened ?
No
Open SVC Valve
Yes
CN_PRESS
Yes
No
Re-vaccuming system
& Re-charging
- 76 -
14
5. Trouble Shooting
Title
26
DC Compressor
Position
Compressor
position detect error
27
PSC Fault
PFC Fault
Over current at
IGBT/PFC module
Cause of error
Is it normal ?
Yes
Is it normal ?
(1 Ph : 230V 10%
3 Ph : 400V 10% )
Yes
No
Correct
connection
Check DC link
capacitor Is it normal?
(Refer to belows)
Yes
Check Over load condition
- Overcharging of
refrigerant
- Pipe Length
- Condenser is blocked
- Outdoor fan is locked
No
Change
Compressor
No
Needs electric work
No
Change DC link
capacitor
Or Main PCB
Remove obstruction
Change outdoor fan
or motor
Change refrigerant
No
Change Main PCB
No
Change
Compressor
3 Phase
DC Link Voltage
Type
Operating
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC280V 10%
DC280V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%
PFC
DC300V 10%
DC380V 10%
PSC
PFC
PFC
DC540V 10%
DC540V 10%
DC540V 10%
DC500V 10%
DC680V 10%
DC680V 10%
PFC
DC540V 10%
DC680V 10%
AUUW126C
AUUW186C
AUUW246D
AUUW306D
AUUW366D
AUUW426D
AUUW486D
PSC
PSC
PFC
PFC
PFC
PFC
PFC
AUUW606D
AUUW368D
AUUW428D
AUUW488D
AUUW608D
- 77 -
Non operating
15
4. Trouble Shooting
Display
code
29
Title
Cause of error
1. Overload operation
(Pipe clogging/Covering/EEV defect/Ref. overcharge)
Inverter compressor input
2. Compressor damage(Insulation damage/Motor
current is over 30A
damage)
3. Input voltage low
4. ODU inverter PCB assembly damage
No
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
Is compressor
Wire connection
condition normal?
No
Yes
No
Check
L~N phase is 220V 15%
Check connection condition and wiring if power is
abnormal
No
Yes
Yes
Recheck power and installation condition
- 90 -
16
5. Trouble Shooting
32
D-pipe (Inverter)
temp. high
(105C )
33
D-pipe (Constant)
temp. high
(105C )
Display
code
Cause of error
Discharge sensor
(Inverter) temp. high
Discharge sensor
(Cons.) temp. high
No
Remove obstruction
Change outdoor fan
or motor
Change refrigerant
Yes
Plug the sensor
on Indoor unit PCB
Check the
Connector connection
Is it normal ?
No
Change the sensor
Yes
Is the voltage of the
sensor is
4.5Vdc at 25C
No
Correct connection
Yes
Yes
Repair or Change the PCB.
No
Change the sensor
- 78 -
17
Title
39
Transmission Error
Between (PFC Micom
INV Micom)
Cause of error
4. Trouble Shooting
Communication Error
Between PFC Micom
and INV Micom.
No
Yes
No
Yes
- 115 -
18
5. Trouble Shooting
6.18 Check code Trouble shooting CH41, CH44, CH45, CH46, CH47, CH65
Display
code
Title
41
47
D-pipe sensor(Inv)
D-pipe sensor(Cons)
44
Air sensor
45
46
65
Heat sink
sensor
Cause of error
Check the
Connector connection
No
Change the sensor
Yes
Is it normal ?
No
Correct connection
Yes
Unplugged
Plugged
No
Change the sensor
Yes
10k
2.5Vdc
- 79 -
19
5. Trouble Shooting
Title
51
Over capacity
60
EEPROM
Check sum
Cause of error
Over capacity
Combination
Check the
indoor unit combination
Check the outdoor
unit max combination
Is it normal ?
No
Correct connection
Yes
Check PCB
Is it normal ?
No
Correct connection
Yes
Change EEPROM
- 80 -
20
Title
Cause of error
52
Transmission error
between (Inverter PCB
Main PCB)
4. Trouble Shooting
No
No
Yes
Yes
Is transmission cable
connected correctly?
No
Re-connect transmission cable
Yes
No
Is MAIN PCB normal?
Yes
Check Point
- Check the Transmission connector and LED (Main & Inverter)
48/56k
<Inverter PCB>
<MAIN PCB>
- 93 -
21
Troubleshooting Guide
Title
54
Cause of error
Check Point
1. Check the connection condition of R,S,T wire.
2. Check the connection condition of CN_Phase.
3. Check the outdoor main fuse.
22
5. Trouble Shooting
Title
61
Condenser
pipe sensor
temp. high
condenser pipe
sensordetected high
temp.(65C)
62
Cause of error
Is the resistance of
the Sensor is 5k
/10k at 25C?
No
Remove obstruction
Change outdoor fan
or motor
Change refrigerant
Yes
Plug the sensor
on Indoor unit PCB
Check the
Connector connection
Is it normal ?
No
Change the sensor
Yes
Is the voltage of the
sensor is 4.5Vdc /
2.5Vdc at 25C
No
Correct connection
Yes
Yes
Repair or Change the PCB.
No
Change the sensor
- 81 -
23
4. Trouble Shooting
Display
code
73
Title
Cause of error
No
Yes
No
Check
L~N phase voltage is 220V 10%
Check connection condition and wiring if power is abnormal
No
No
Yes
Is compressor
Wire connection
condition normal?
Yes
No
Check inverter PCB assembly IPM normality
Replace inverter PCB assembly
Yes
Recheck power and
installation condition
- 102 -
24
Troubleshooting Guide
Title
Cause of error
67
Outdoor fan
lock
105
Communication error
between main PCB and
fan PCB
Communication error
between main PCB
and fan PCB
Check Point
CH 67
CH 105
25
Single A
Aan / uit, Single-split
AT-C.. / AT-H..
LB-C.. / LB-D.. / LB-E.. / LB-G.. / LB-H..
LT-B.. / LT-C.. / LT-D.. / LT-E..
LV-B..
P03AH / P05AH / P08AH
26
Troubleshooting Guide
Title
01
Open / Short
Soldered poorly
Internal circuit error
02
Open / Short
Soldered poorly
Internal circuit error
Open / Short
Soldered poorly
Internal circuit error
06
Cause of error
10k.
2.5Vdc
Check Point
27
Troubleshooting Guide
2) Troubleshooting CH03
Display
code
Title
03
Communication
Wired R/C
Cause of error
Wired R/C
12V
Open / Short
Wrong connection
Indoor Unit
GND
12V
Connection of wire
Main PCB Volt. DC12V
Noise interference
CN-REMO
GND
12Vdc
12Vdc
Check Point
28
Troubleshooting Guide
3) Troubleshooting CH04
Display
code
Title
04
Drain pump
/ Float switch
Cause of error
Float switch Open.
(Normal : short)
CN Float
CN-D/PUMP
CN-Float
0.
.
Check Point
1. Check the wire connection. (Open, Soldered poorly) Repair the connection or change the PCB.
2. Check the resistance of float switch (Abnormal : Open, Normal : short) Check the float switch.
3. Check the level of water
4. Check the volt. Of Drain pump power supply. (AC 230V) Repair or Change the main PCB.
29
Troubleshooting Guide
Title
Communication
(Indoor Outdoor)
Cause of error
Communication poorly
Check Point
30
Troubleshooting Guide
5) Troubleshooting CH21
Display
code
Title
21
Cause of error
DC Peak
Comp
U
Terminal
U-V
V-W
W-U
Comp
Resistance(. ) at 20C
.
Copper
pipe
Inverter Constant
comp.
comp.
0.64
0.64
0.64
0.8
0.8
0.8
Resistance(. ) at 20C
.
Terminal
U-GND
V-GND
W-GND
Inverter Constant
comp.
comp.
2M.
2M.
2M.
2M.
2M.
2M.
Check Point
31
Troubleshooting Guide
Title
Cause of error
21
Max. C/T
22
C/T
Internal circuit
Malfunction of compressor
Blocking of pipe
Low voltage input
Refrigerant, pipe length, blocked,
Check Point
1. Check the power source.
Troubleshooting Guide
Title
24
25
Input voltage
Cause of error
TRANS1
50Hz, DC12V
CN PRESS
CN TRNAS1
Check Point
CH 24
CH 25
Troubleshooting Guide
Title
32
D-pipe (Inverter)
temp. high
(105C )
33
D-pipe (Constant)
temp. high
(105C )
Cause of error
Discharge sensor
(Inverter) temp. high
Discharge sensor
(Cons.) temp. high
D-Pipe temp.
Toff(105) C
T2(95) C
T1(90) C
COMP Frequency
Normal
(Hz)
LEV Openness
(Pulse)
Normal
Normal
OFF
Normal
OFF Control
Check Point
CH 32
CH 33
34
Troubleshooting Guide
Title
41
Open / Short
Soldered poorly
Internal circuit error
44
Air sensor
Open / Short
Soldered poorly
Internal circuit error
45
Open / Short
Soldered poorly
Internal circuit error
46
Open / Short
Soldered poorly
Internal circuit error
Open / Short
Soldered poorly
Internal circuit error
Open / Short
Soldered poorly
Internal circuit error
47
65
Cause of error
Check Point
35
Troubleshooting Guide
Title
51
Over capacity
60
EEPROM
Check sum
Cause of error
Over capacity
Combination
Model
AUUW126B
21k
12k
AUUW186B
AUUW246B
24k
12K
AUUW306B
AUUW366B
33k
18K
AUUW4860
39k
18K
AUUW6060
52k
24K
Check Point
CH 51
CH 60
36
Troubleshooting Guide
Title
Cause of error
61
Condenser
pipe sensor
temp. high
62
COMP Frequency
Normal
(Hz)
Normal
Check Point
OFF
Normal
CH 61
CH 62
37
Troubleshooting CH54
Display
code
Title
54
Phase error
Cause of error
Phase change
Phase_A
5.3 msec
Phase_B
Phase_C
1
0
1
1
0
0
1
1
0
0
1
0
0
1
1
0
0
1
Check Point
1. Check the Main power.
2. Check the connecting state of connector CN_3PHASE on the outdoor pcb ass'y.
38
LG
Multi-split
Inverter
FM..AH
39
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Title
01
Open / Short
Soldered poorly
Internal circuit error
02
Open / Short
Soldered poorly
Internal circuit error
06
Open / Short
Soldered poorly
Internal circuit error
Cause of error
10k
2.5Vdc
Check Point
1. Unplug the sensor on Indoor unit PCB.
2. Estimate the resistance of each sensor.
3. If the resistance of the sensor is 10K/ 5K at 25C, then sensor is normal.
4. If the resistance of the sensor is 0 K or , then sensor is abnormal. Change the sensor.
5. Plug the sensor on Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc at 25C, then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. Repair or Change the PCB.
- 59 -
40
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Display
code
Title
03
Communication
Wired R/C
Cause of error
Wired R/C
12V
Open / Short
Wrong connection
Indoor Unit
GND
12V
Connection of wire
Main PCB Volt. DC12V
Noise interference
CN-REMO
GND
12Vdc
12Vdc
Check Point
1. Check the wire connection. (Open / Short) Repair the connection
2. Check the soldering state of connector. (Soldered poorly) Repair or Change the PCB.
3. Check the volt. Of main PCB power source. (DC 12V, DC 5V) Repair or Change the main PCB.
4. Check the installation of wired remote controller. (Noise interference) Adjust the state of installation
- 60 -
41
Multi-split: Inverter
FM..AH
Display
code
Title
04
Drain pump
/ Float switch
Cause of error
4. Trouble Shooting
Check point & Normal condition
CN Float
CN-D/PUMP
CN-Float
Check Point
1. Check the wire connection. (Open, Soldered poorly) Repair the connection or change the PCB.
2. Check the resistance of float switch (Abnormal : Open, Normal : short) Check the float switch.
3. Check the level of water
4. Check the volt. Of Drain pump power supply. (AC 230V) Repair or Change the main PCB.
- 61 -
42
4. Trouble Shooting
Multi-split: Inverter
FM..AH
Display
code
05
/
53
Title
Communication
(Indoor Outdoor)
Cause of error
Communication poorly
Check Point
1. Check the input power AC230V. (Outdoor, Indoor unit)
2. Check the communication wires are correctly connected.
Adjust the connection of wire
Confirm the wire of Live, Neutral
3. Check the resistance between communication line and
GND. (Normal : Over 2M)
4. Check the connector for communication is correctly
connected.
5. Check the connection of GND1, GND2, and main GND.
6. If one indoor unit is operated normally, outdoor PCB is no
problem.
Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.
- 62 -
43
Multi-split: Inverter
FM..AH
4. Trouble Shooting
FM27AH t/m FM57AH
Display
code
Title
05
/
53
Title
Communication
(Indoor Outdoor)
Cause of error
Communication poorly
Check Point
1. Check the input power AC230V. (Outdoor, Indoor unit)
2. Check the communication wires are correctly connected.
Adjust the connection of wire Confirm the wire of "Live",
"Neutral"
3. Check the resistance between communication line and
GND. (Normal : Over 2M)
4. Check the connector for communication is correctly connected.
5. If one indoor unit is operated normally, outdoor PCB is no
problem.
Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at
outdoor unit.
6. If all indoor unit is displayed CH05 but outdoor PCB not
display
CH53 : Check the CN_COM and CN_POWER is correctly
connected.
27/30/40k
1. In Case of CH53, Check the Connection L , N at the terminal block
48/56k
1. In Case of CH05, Check the Connection CN-POWER,
CN-COMM at the Main PCB
2. In Case of CH53, Check the Connection CN-COMM at
the Main PCB L , N at the terminal block
N
L
CN-COMM
CN-Power
< MAIN PCB >
- 72 -
44
Multi-split: Inverter
FM..AH
Title
Cause of error
DC PEAK
(IPM Fault)
21
No
Is installation
condition normal?
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
Is compressor
Wire connection
condition normal?
No
No
Yes
Yes
Recheck power and installation condition
Resistance() at 20C
Comp
Copper
pipe
Terminal
Inverter
comp.
U-V
V-W
W-U
1.083
1.123
1.096
Resistance() at 20C
Terminal
Inverter
comp.
U-GND
V-GND
W-GND
50M
50M
50M
45
Multi-split: Inverter
FM..AH
4. Trouble Shooting
1. Wait until inverter PCB DC voltage is discharged after main power off.
2. Pull out CN-L1(R), CN-L2(S), CN-L3(T) and CN-COMP Connector.
3. Set multi tester to resistance mode.
4. If the value between P and N terminal of IPM is short(0) or open(hundreds M), PCB needs to be replaced.(IPM damaged)
5. Set the multi tester to diode mode.
6. In case measured value is different from the table, PCB needs to be replaced.(PCB damaged).
P
Nu Nv Nw
Nu Nv Nw
27
26
25
24
23 22 21
27
26
25
24
23 22 21
0.4 ~ 0.6 V
0.4 ~ 0.6 V
PFC_IPM check
U, V, W R S T
CAUTION
In case that the control box is opend and before checking electrical parts, it should be checked that the
LED 01M, 02M turned off(wait 7 minutes after main power OFF), otherwise it may cause electrical shock.
46
Multi-split: Inverter
FM..AH
Title
Cause of error
DC PEAK
(IPM Fault)
21
4. Trouble Shooting
Check point & Normal condition
No
Is installation
condition normal?
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
Is compressor
Wire connection
condition normal?
No
No
Yes
Yes
Recheck power and installation condition
Resistance() at 20C
U-V
V-W
W-U
Comp
Terminal
Copper
pipe
Inverter Constant
comp.
comp.
0.64
0.64
0.64
0.8
0.8
0.8
Resistance() at 20C
Terminal
U-GND
V-GND
W-GND
Inverter Constant
comp.
comp.
2M
2M
2M
2M
2M
2M
- 73 -
47
Multi-split: Inverter
FM..AH
4. Trouble Shooting
FM27AH t/m FM41AH
LED01M
LED02M
U,V,W CONNECTOR
U
V
W
1. Wait until inverter PCB DC voltage is discharged after main power off.
2. Pull out V, V, W COMP connector.
3. Set multi tester to resistance mode.
4. If the value between P and N terminal of IPM is short(0) or open(hundreds M), PCB needs to be replaced.(IPM damaged)
5. Set the multi tester to diode mode.
6. In case measured value is different from the table, PCB needs to be replaced.(PCB damaged).
P
Nu Nv Nw
Nu Nv Nw
27
26
25
24
23 22 21
27
26
25
24
23 22 21
0.4 ~ 0.6 V
0.4 ~ 0.6 V
PFC_IPM chec
U, V, W R S
CAUTION
In case that the control box is opend and before checking electrical parts, it should be checked that the
LED 01M, 02M turned off(wait 7 minutes after main power OFF), otherwise it may cause electrical shock.
48
Multi-split: Inverter
FM..AH
4. Trouble Shooting
U
V
W
LED01M
LED02M
CN(L)_BRWON
CN(N)_BLUE
U,V,W CONNECTOR
1. Wait until inverter PCB DC voltage is discharged after main power off.
2. Pull out CN(L), CN(N) connectors and U,V,W COMP Connector.
3. Set multi tester to resistance mode.
4. If the value between P and N terminal of IPM is short(0) or open(hundreds M), PCB needs to be replaced.(IPM damaged)
5. Set the multi tester to diode mode.
6. In case measured value is different from the table, PCB needs to be replaced.(PCB damaged).
P
Nu Nv Nw
Nu Nv Nw
27
26
25
24
23 22 21
27
26
25
24
23 22 21
0.4 ~ 0.6 V
0.4 ~ 0.6 V
PFC_IPM chec
U, V, W R S
CAUTION
In case that the control box is opend and before checking electrical parts, it should be checked that the
LED 01M, 02M turned off(wait 7 minutes after main power OFF), otherwise it may cause electrical shock.
- 75 -
49
Multi-split: Inverter
FM..AH
Title
Max. C/T
22
Cause of error
No
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
Is compressor
Wire connection
condition normal?
No
Yes
No
No
Check
R~S/S~T/T~R phase voltage is 380V 10%
R~N/S~N/T~N phase voltage is 220V 10%
Check connection condition and wiring if power is
abnormal.
No
Yes
Yes
Yes
Recheck power and installation condition
- 108 -
50
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Check Point
1. Check the power source.(200~240V)
2. Check the fan operation is right.
3. Check the current.
4. Check the install condition.
5. Check the CT Sensor Output signal (Check output pin 1.2 of the CT Sensor : 5V )
Tester
CT Sensor Output
(at the INVERTER PCB)
- 109 -
51
Multi-split: Inverter
FM..AH
22
Title
Cause of error
Max. C/T
Input Over
Current(27/30/40k-17A
48/56k-29A )
Is installation
condition normal?
No
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
Is compressor
Wire connection
condition normal?
No
Yes
No
No
Check
L~N phase is 220V 15%
Check connection condition and wiring if power is
abnormal
No
Yes
Yes
Yes
Recheck power and installation condition
- 76 -
52
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Check Point
1. Check the power source.(220V 15%)
2. Check the fan operation is right.
3. Check the current.
4. Check the install condition.
5. Check the CT Sensor Output signal
(27/30/40k - Check output the CT Sensor : DC 2.50.2V)
(48/56k - Check output pin 1.2 of the CT Sensor : 5V )
Vdc
< Input Power Source Check Point >
- 77 -
53
Multi-split: Inverter
FM..AH
23
Title
Cause of error
No
Yes
No
No
Yes
Yes
No
Yes
Recheck power and installation condition
- 110 -
54
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Check Point
1. Check the Tab1 connection condition. (Refer to outdoor wiring diagram)
2. Check the CN_L1(R), CN_L2(S), CN_L3(T) connection condition
3. Check the DC Link voltage at not operating(380V )
4. Check the DC Link voltage at Comp operating(500V )
5. Check DC Link Sensing Signal (Refer the Picture)
Vdc
500Vdc 10%
+
GND
<INVERTER PCB>
GND
Tester
DC Link Voltage
oltage INV
- 111 -
55
23
Multi-split: Inverter
FM..AH
Title
Cause of error
Yes
No
Is Inverter PCB Normal?
Yes
Recheck power and installation
condition
- 78 -
56
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Check Point
1. Check the WCN_P(L),P(N) Connection condition at the Main PCB.(Refer to outdoor wiring diagram)
2. Check the DC Link voltage at not operating(280V )
3. Check the DC Link voltage at Comp operating(340V )
4. Check DC Link Sensing Signal :2.4~2.8V (Refer the Picture)
Vdc
< Main PCB>
Vdc
- 79 -
57
Multi-split: Inverter
FM..AH
4. Trouble Shooting
N
GND
Vdc
DC_LINK
GND
- 80 -
58
Multi-split: Inverter
FM..AH
Display
code
Title
24
Cause of error
4. Trouble Shooting
Check point & Normal condition
No
Connect securely
Yes
No
Yes
No
Yes
Is this error appeared
again after reset?
No
Re-check momentary
problem or not
Yes
Is high pressure
more than 2500kPa
at manifold gauge?
No
Replace PCB
Yes
Is high pressure of
LGMV similar as
at manifold gauge?
No
Yes
Check pipe is blocked or
not and take measure
- 81 -
59
4. Trouble Shooting
Multi-split: Inverter
FM..AH
Check Point
1. Check the connection of H/press switch
2. Check short or not at the connector of high pressure switch (Normal open)
27/30/40k
48/56k
- 82 -
60
Multi-split: Inverter
FM..AH
Title
25
Input voltage
Cause of error
Abnomal Input Voltage
(R,S,T -N /140Vac ,
300Vac )
No
Yes
No
Yes
Recheck power and installation condition
<INVERTER PCB>
Tester
GND
INPUT VOLTAGE
VOL AGE INV
- 112 -
61
Multi-split: Inverter
FM..AH
Title
Cause of error
25
Input voltage
4. Trouble Shooting
Check point & Normal condition
No
Yes
Is Inverter PCB Normal?
No
Yes
Recheck power and
installation condition
Check Point
1. Check the Input Voltage (LN 220V10%)
2. Check Input Voltage Sensor output voltage (2.5Vdc10%)
- 83 -
62
4. Trouble Shooting
Multi-split: Inverter
FM..AH
Vdc
Vdc
INPUT(V)
GND
- 84 -
63
Multi-split: Inverter
FM..AH
Title
26
DC Compressor
Position
Cause of error
Compressor
Starting fail error
4. Trouble Shooting
Check point & Normal condition
Is installation
condition normal?
No
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
Is compressor
Wire connection
condition normal?
No
No
Yes
Yes
Recheck power and installation condition
- 85 -
64
Multi-split: Inverter
FM..AH
Title
26
DC Compressor
Position
Cause of error
Compressor
Starting fail error
4. Trouble Shooting
Check point & Normal condition
Is installation
condition normal?
No
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
Is compressor
Wire connection
condition normal?
No
No
Yes
Yes
Recheck power and installation condition
Check Point
1. Check the connection condition of PCB.
2. Check the connection condition of Comp. U,V,W wire.
3. Check the comp resistor and insulation resistance .
WVU
- 113 -
65
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Display
code
27
Title
Cause of error
No
Yes
No
Check
L~N phase voltage is 220V 15%
Check connection condition and wiring if power is abnormal
No
No
Yes
No
Check inverter PCB assembly PFCM normality
Replace inverter PCB assembly
Yes
Recheck power and
installation condition
Signal pin
CAUTION
PFCM module No.4,5 pins are internal short state.
8
- 86 -
66
Multi-split: Inverter
FM..AH
Title
Cause of error
28
4. Trouble Shooting
Check point & Normal condition
Yes
Is Inverter PCB assembly
Power connection normal?
No
Yes
No
Is Inverter PCB Normal?
- 87 -
67
Multi-split: Inverter
FM..AH
Check Point
1. Check the CN_(L),CN_(N) Connection condition at the Inverter PCB.(Refer to outdoor wiring diagram)
2. Check the DC Link voltage at not operating(280V )
3. Check the DC Link voltage at Comp operating(340V )
4. Check DC Link Sensing Signal : 2.4~2.8V (Refer the Picture)
Vdc
< Main PCB>
Vdc
- 88 -
68
Multi-split: Inverter
FM..AH
4. Trouble Shooting
48/56k
Vdc
N
GND
Vdc
DC_LINK
GND
- 89 -
69
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Display
code
29
Title
Cause of error
1. Overload operation
(Pipe clogging/Covering/EEV defect/Ref. overcharge)
Inverter compressor input
2. Compressor damage(Insulation damage/Motor
current is over 30A
damage)
3. Input voltage low
4. ODU inverter PCB assembly damage
No
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
Is compressor
Wire connection
condition normal?
No
Yes
No
Check
L~N phase is 220V 15%
Check connection condition and wiring if power is
abnormal
No
Yes
Yes
Recheck power and installation condition
- 90 -
70
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Display
code
Title
32
D-pipe (Inverter)
temp. high
(105C )
33
D-pipe (Constant)
temp. high
(105C )
Cause of error
Discharge sensor
(Inverter) temp. high
Discharge sensor
(Cons.) temp. high
D-Pipe temp.
Toff(105) C
T2(95) C
T1(90) C
COMP Frequency
Normal
(Hz)
LEV Openness
(Pulse)
Normal
Normal
OFF
Normal
OFF Control
Check Point
CH 32
CH 33
- 68 -
71
Multi-split: Inverter
FM..AH
Display
code
Title
39
Transmission Error
Between (PFC Micom
INV Micom)
Cause of error
4. Trouble Shooting
Check point & Normal condition
Communication Error
Between PFC Micom
and INV Micom.
No
Yes
No
Yes
- 115 -
72
Multi-split: Inverter
FM..AH
40
Title
C/T
Sensor Error
Cause of error
No
No
Yes
Tester
CT Sensor Output
(at the INVERTER PCB)
GND
COMP CURRENT
U,V ,W
U,V,W
<INVERTER PCB>
INPUT
VOL AGE INV
VOLTAGE
<INPUT VOLTAGE Check Point>
- 116 -
73
Multi-split: Inverter
FM..AH
Title
C/T
Sensor Error
40
4. Trouble Shooting
Cause of error
No
Yes
Is Inverter PCB Normal?
No
Yes
Recheck power and
installation condition
Check Point
1. Check the Input Voltage (LN 220V10%)
2. Check Input Voltage Sensor output voltage (2.5Vdc10%)
- 91 -
74
4. Trouble Shooting
Multi-split: Inverter
FM..AH
Vdc
1
2
3
Vdc
INPUT(CT)
GND
- 92 -
75
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Display
code
Title
41
Open / Short
Soldered poorly
Internal circuit error
44
Air sensor
Open / Short
Soldered poorly
Internal circuit error
45
Open / Short
Soldered poorly
Internal circuit error
46
Open / Short
Soldered poorly
Internal circuit error
47
Open / Short
Soldered poorly
Internal circuit error
65
Open / Short
Soldered poorly
Internal circuit error
Cause of error
Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance of the sensor is 0 k or , then sensor is abnormal.
- 69 -
76
Multi-split: Inverter
FM..AH
Title
51
Over capacity
60
EEPROM
Check sum
Cause of error
Over capacity
Combination
Model
A2UW146FA3
21k
A2UW166FA0
A2UW166FA1
24k
12k
A3UW186FA0
A3UW216FA3
A4UW246FA3
33k
18k
Check Point
CH 51
CH 60
- 70 -
77
Multi-split: Inverter
FM..AH
Title
51
Over capacity
Over capacity
60
Over capacity
Cause of error
Model
A7UW428FA3
54k
A8UW488FA3
62k
A9UW548FA3
73k
Check Point
CH 51
CH 60
- 118 -
78
Multi-split: Inverter
FM..AH
Display
code
Title
Cause of error
52
Transmission error
between (Inverter PCB
Main PCB)
4. Trouble Shooting
Check point & Normal condition
No
No
Yes
Yes
Is transmission cable
connected correctly?
No
Re-connect transmission cable
Yes
No
Is MAIN PCB normal?
Yes
Check Point
- Check the Transmission connector and LED (Main & Inverter)
48/56k
<Inverter PCB>
<MAIN PCB>
- 93 -
79
Multi-split: Inverter
FM..AH
Display
code
Title
54
Cause of error
4. Trouble Shooting
Check point & Normal condition
No
T-N
R
Fuse
R S T
S T
CN-L2(S)
- 119 -
80
60
Multi-split: Inverter
FM..AH
Title
Cause of error
No
Yes
No
Yes
No
Yes
Recheck power and installation condition
Check Point
- Check the EEPROM Check sum & Direction
27/30/40k
<MAIN PCB>
- 94 -
81
Multi-split: Inverter
FM..AH
4. Trouble Shooting
<MAIN PCB>
<Inverter PCB>
- 95 -
82
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Display
code
Title
Cause of error
61
62
Heat sink sensor detect- Check the Heat sink sensor (10k 10% at 25C)
ed high temp.(85C)
Check that outdoor fan is driving rightly
Gd`sRhmj
Snee
8/C
S1
74C
S0
7/C
ZGy\
Gy
Cnvm
Gy
Cnvm
NEE
Gy
Cnvm
No
Yes
Is normal heatsink sensor ?
(10k 10% at 25C)
No
Yes
No
Yes
Recheck power and
installation condition
- 120 -
83
4. Trouble Shooting
Display
code
65
Multi-split: Inverter
FM..AH
Title
Cause of error
Is installation
condition normal ?
No
Yes
Is assemble condition
of INV PCB heatsink normal ?
No
Yes
Is PCB temperature
sensing part normal ?
No
Check Point
1. Check resistance between No.19 pin and NO.20 pin of PCB PFC module
2. Check resistance between No.24 pin and NO.25 pin of PCB PFC module - only 48/56k
3. Resistance value should be in 7k 10%.(at 25C).
4. Check the PFC Module No.19, 20 and IPM Module No.24, 25 pin soldering condition.
- 98 -
84
Multi-split: Inverter
FM..AH
4. Trouble Shooting
PFCM :
Measuring resistance
between No.19,20 pin
PFCM :
Measuring resistance
between No.19,20 pin
- 99 -
IPM :
Measuring resistance
between No.24,25 pin
85
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Display
code
Title
Cause of error
67
Outdoor fan
lock
No
Yes
No
Yes
Replace inverter PCB assembly
- 121 -
86
67
Multi-split: Inverter
FM..AH
Title
Cause of error
No
No
Yes
Yes
Is wire connection of
ODU Fan Motor wire normal?
No
Yes
No
Yes
Recheck power and installation condition
Check Point
1. Check voltage between 1pin and 4pin of Fan Mortor connector (Tester diode mode)
2. Voltage vaule should be in 1V 0.2V.
- 100 -
87
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Fan motor
connector
Tester
<Main PCB>
<Inverter PCB>
- 101 -
88
Multi-split: Inverter
FM..AH
4. Trouble Shooting
Display
code
73
Title
Cause of error
No
Yes
No
Check
L~N phase voltage is 220V 10%
Check connection condition and wiring if power is abnormal
No
No
Yes
Is compressor
Wire connection
condition normal?
Yes
No
Check inverter PCB assembly IPM normality
Replace inverter PCB assembly
Yes
Recheck power and
installation condition
- 102 -
89
Multi-split: Inverter
FM..AH
4. Trouble Shooting
27/30/40k
N
L
- 103 -
90
Multi-split: Inverter
FM..AH
4. Trouble Shooting
48/56k
N
L
- 104 -
91
LG
Multi-split
Variabel (aan/uit)
M..AC/AH
92
Functions
Signal Receptor
Receives the signals from the remote controller.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
: Lights up during the system operation.
: Lights up during Sleep Mode Auto operation.
: Lights up during Timer operation.
: Lights up during Defrost Mode or Hot Start operation (Heat pump model only)
: Lights up during outdoor unit operation. (Cooling model only)
On/Off
Sleep Mode
Timer
Signal
receptor
Defrost Mode
Receives the signals from the remote controller.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
: Lights up during the system operation.
: Lights up during Sleep Mode Auto operation.
Timer
: Lights up during Timer operation.
Defrost Mode
: Lights up during Defrost Mode or Hot Start operation.(Heat pump model only)
Outdoor unit operation : Lights up during outdoor unit operation.(Cooling model only)
PLASMA
: Indicate PLASMA purifier operation.
On/Off
Sleep Mode
Self-diagnosis Function
Error Indicator
The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
After error occurrence, if error is released, error LED is also released simultaneously.
To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
Having or not of error code is different from Model.
Error
Code
1
2
5
Error LED
(Indoor body operation LED)
5sec
(once)
3sec
3sec
3sec
(twice)
3sec
3sec
(5times)
(6times)
3sec
(7times)
Poor communication
Communication line/circuit
3sec
Overload combination
(9times)
3sec
3sec
3sec
45
3sec
51
3sec
44
Error contents
3sec
3sec
: ten digits
: one digits
93
Multi-split
Multi-split tot 2005
A2-C..
A3-C..
A2-H..
A3-H..
LM..
94
Display Function
1. Heating Model
2. Cooling Model
Operation Indicator
Operation Indicator
Cooling, Soft Dry, Fan, Heating
Sleep Mode
Sleep Mode
Timer Indicator
Timer Indicator
Timer Mode
Timer Mode
Compressor on Indicator
Defrost Indicator
OUT
DOOR
Hot-start, Defrost
Self-diagnosis Function
Error Indicator
The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
After error occurrence, if error is released, error LED is also released simultaneously.
To operate again on the occurrence of error code 12, be sure to pull out power cord and then re-insert.
Having or not of error code is different from Model.
Error
Code
1
2
Error LED
(Indoor body operation LED)
Error contents
(once)
3sec
(twice)
3sec
3sec
(3times)
3sec
3sec
3
3sec
(5times)
3sec
Poor communication
5
(once)
3sec
(twice)
(once)
12
3sec
3sec
3sec
(twice)
Communication
line/circuit check
Primarily check
Misconnection of connecting refrigerant pressure
cables
Connecting pipe check
Connecting cable check
95
LG
RAC
Standaard wandunit (aan/uit & Inverter)
Art Cool Deluxe (aan/uit & Inverter) (hoge wand)
Art Cool Panel (aan/uit & Inverter)
96
RAC
Standaard wandunit (aan/uit)
Alle typen/uitvoeringen o.a:
LS-J.. / LS-K.. / LS-L..
S..ACL / S..AH / S..ACP / S..AHP
G..AH
97
Operation
Display Function
1. Heating Model
2. Cooling Model
Operation Indicator
Operation Indicator
Cooling, Soft Dry, Fan, Heating
Deicer Indicator
OUT
DOOR
Hot-start, Deice
Self-diagnosis Function
Error
Code
1
3sec
3sec
Error contents
Indoor room temperature
thermistor open/short
Indoor pipe temperature
thermistor open/short.
98
LG
RAC
Standaard wandunit Inverter
LS-N....
LS-Q....
LS-R....
S..AN
S..AW
99
Troubleshooting Guide
Self-diagnosis function
1. The malfunction indicator of indoor (see the operating LED of the INDOOR)
Error
Code
Malfunction indicator
DC peak error.
10
2. The malfunction indicator of outdoor (see the LED01M on the outdoor PCB assy)
Error
Code
Malfunction indicator
DC peak error.
10
100
RAC
ART COOL Deluxe Inverter
C09AW*
C12AW*
101
Troubleshooting Guide
Self-diagnosis function
1. The malfunction indicator of indoor (see the operating LED of the INDOOR)
Error
Code
Malfunction indicator
DC peak error.
10
2. The malfunction indicator of outdoor (see the LED01M on the outdoor PCB assy)
Error
Code
Malfunction indicator
DC peak error.
10
102
LG
RAC
ART COOL Deluxe Inverter
C18AW*
C24AW*
103
Troubleshooting Guide
Self-diagnosis function
1. The malfunction indicator of indoor (see the operating LED of the INDOOR)
Error
Code
Malfunction indicator
DC peak error.
10
2. The malfunction indicator of outdoor (see the LED01M on the outdoor PCB assy)
Error
Code
Malfunction indicator
DC peak error.
10
104
RAC
ART COOL Panel Inverter
A09AW
A12AW
A09AW1
A12AW1
105
Troubleshooting Guide
Cause of Error
Error Indicator
1time
3 sec
1time
3 sec
1time
3 sec
1time
3 sec
2 times
2 times
2 times
2 times
3 sec
3 sec
3 sec
4 times
4 times
3 sec
3 sec
5times
5times
3 sec
3 sec
6times
6times
3 sec
3 sec
8times
8times
3 sec
9times
9times
3 sec
10 times 10 times
10
3 sec
1time
12
2times
1time
3 sec
1time
13
1time
4 times
3 sec
ON
ON
OFF
DC Peak error
SHUT
DOWN
SHUT
DOWN
OFF
ON
Communication error
ON
1time
OFF
ON
3 times
PSC Error
- PSC Fault Error
ON
4 times
ON
3 sec
3 times
EEPROM Error
- EEPROM Check sum Error
3 sec
1time
14
2times
Indoor
Operation
7times
7times
Display
Indoor Outdoor
106
Troubleshooting Guide
Description
Check flow
Cause of error
Indoor TH. (sensor) is short or open
Indoor TH. (sensor) is not connected to the indoor pcb assembly
Damage or defect on the sensing circuit of indoor pcb assembly.
(R01H, R02H, R03H, R04H, C01H, C02H)
YES
YES
Sensing circuit of indoor
pcb is right ?
No
No
Check Indoor TH.
- Measure resistance of TH.
(air : about 10k . at 25 C,
pipe : about 5k . at 25 C)
- Connect to CN-TH1 in
indoor pcb assembly
Error code
Description
Check flow
Outdoor TH. is connected to
outdoor pcb assembly ?
No
- Connect to CN-TH1 in
outdoor pcb assembly
No
Cause of error
Outdoor TH. (sensor) is short or open
Outdoor TH. (sensor) is not connected to the outdoor pcb assembly
Damage or defect on the sensing circuit of outdoor pcb assembly.
(R03H~R06H, C02H, C03H)
YES
YES
Outdoor TH. is right ?
No
Check outdoor TH.
- Measure resistance of TH.
(air : about 10k . at 25 C,
pipe : about 5k . at 25 C)
107
Troubleshooting Guide
9K / 12K
Description
Error code
Cause of error
Check flow
Heat-sink TH is connected to
outdoor PCB assembly?
No
- Connect to CN-TH2 in
outdoor PCB assembly
YES
YES
Heat-sink TH. in INV-IC is
Right ?
No
108
Error code
Cause of error
Wrong or missing wiring between indoor and outdoor unit cable
Defect of communication components in indoor pcb assembly
Defect of communication components in outdoor pcb assembly
Defect of power supply components in outdoor pcb assembly
No ground connection in air conditioner unit
(affected by noise in power source)
Communication Error
Check flow
YES
No
Indoor
1(BR)
2(BL)
3(GN/YL)
4(RD)
YES
Is the voltage of T/Block
,
in outdoor about
AC 220/240V ?
Wiring connection
Is right ?
No
Outdoor
1(BR)
2(BL)
3(GN/YL)
4(RD)
Troubleshooting Guide
No
YES
YES
Communication circuit of indoor
& outdoor pcb Is right ?
No
Earth port
109
Troubleshooting Guide
Error code
Cause of error
Description
DC Peak Error
Check flow
YES
Supplied voltage to
Outdoor pcb is about
AC 220/240V ?
YES
Is connector (CN-U,V,W)
connected to compressor and
inserted to pcb in right position ?
No
No
No
YES
YES
Inverter components in outdoor
right ?
No
Check resistance
Between U-V, V-W, U-W port.
Short / Open circuit
(Comp.motor coil error)
normal : 1 ~2 .
Between U,V,W and Body
normal : over10M .
* 9 K/12K Model
Check
Short of SPM3 pins (GND - P, U, V, W pin)
Direction of D01Z~D03Z, C08Z,10Z,12Z,16Z
Assembling state of R01P ~ R21P & IC01P
Assembling state of screw between INV-IC &
Heat-sink
DC 15V output of Power module.
U
.
V
* 18 K Model
Check
Short of SPM2 pins (GND P, U, V, W pin)
Direction of D01Z~D03Z, C08Z,10Z,12Z,16Z
Assembling state of R01P ~ R21P & IC01P
Assembling state of screw between INV-IC &
Heat-sink
DC 15V output of Power module.
110
Description
Check flow
Cause of error
Supplied power is not normal
Indoor/outdoor fan is locked
Too much refrigerant
Defect in current sensing circuit in outdoor pcb assembly
YES
YES
Supplied voltage to
Outdoor pcb is about
AC 220/240V ?
No
No
Check indoor / outdoor fan and
adjust.
Troubleshooting Guide
YES
Current sensing circuit is right ?
No
Check current sensing circuit.
- check CT is damaged in outdoor pcb
(output wire is disconnected to pin or not)
- BD01N is inserted in right position
(refer marking on pcb and component)
- Spec of R01N (1k. ), R02N (1.65k. ) is correct
- Direction of diode (D01N, D02N) is right
111
Troubleshooting Guide
Error code
Description
Check flow
Cause of error
Indoor fan is locked or separated
Fan connector is not connected to indoor pcb assembly
Defective in DC-fan driving circuit
YES
YES
Indoor fan is rotating ? (2)
No
No
Description
Error code
Check flow
No
Cause of error
Outdoor fan is locked by an obstacle (ex : branch of tree, baretc)
Fan connector is not connected to outdoor pcb assembly
Defective in DC-fan driving circuit
YES
YES
Outdoor fan is rotating ? (2)
No
Check connector is not
connected to outdoor pcb
assembly (CN-FAN2)
112
10
Description
Cause of error
Check flow
D_PIPE TH. is connected to
Outdoor pcb assembly ?
No
Connect to CN-D_PIPE
in outdoor pcb assembly
Troubleshooting Guide
YES
YES
D_PIPE TH. is right ?
No
113