LG Checkpoint-codes
Versie 2.4P-M

vervangt U02.3.M

BEFORE SERVICING THE UNIT, READ THE SAFETY


PRECAUTIONS IN THE SERVICEMANUAL.
ONLY FOR AUTHORIZED SERVICE PERSONNEL.

Hoofdstukindeling
Single A (vloer- & plafond UV / cassette UT / kanaal UB)........................................04
- Aan / Uit - Inverter
UU..(W)
- Variabel (aan/uit)..........................................................................................................26
AT-C.. / AT-H.. / LB-C.. / LB-D.. / LB-G.. / LB-H.. / LT-B.. / LT-C.. / LT-D.. / LT-E.. /
LV-B.. / P..AH
Multi-split ......................................................................................................................39
- Inverter
FM..AH
- Variabel (aan/uit)..........................................................................................................92
M..AC/AH

- Multi-split tot 2005.......................................................................................................94


A2-C.. / A3-C.. / A2-H.. / A3-H.. / LM..
RAC...............................................................................................................................96
- Standaard wandunit (aan/uit)......................................................................................97
LS-J.. / LS-K.. / LS-L.. / S..ACL / S..ACP / S..AH(P) / G..AH
- ART COOL Deluxe / Panel (aan/uit)............................................................................97
LS-P.. / A09AH* / -12- / -18- / C07AH* / -09- / -12- Standaard wandunit Inverter........................................................................................99
LS-N.. / LS-Q.. / LS-R.. / S..AN / S..AW
- ART COOL Deluxe Inverter.........................................................................................101
C09AW* / C12AW*
- ART COOL Deluxe Inverter.........................................................................................103
C18AW* / C24AW*
-ART COOL Panel Inverter............................................................................................105
A09AW* / A12AW* / A09AW1 / A12AW1

LG

Single A (vloer- & plafond UV / cassette UT /


UB kanaal) UU..(W)

Inverter 1-fase (single-split)


Inverter 3-fase (Single-split)
Synchro (master/slave)
Variabel (aan/uit, single-split)

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

5. Trouble Shooting

6.6 Check code Trouble shooting CH01, CH02, CH06


Display
code

Title

Cause of error

Check point & Normal condition

01

Indoor air sensor

Connector connection error


Faulty PCB
Faulty sensor (Open / Short)

Normal resistor : 10K/ at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C(Plugged)
Refer to sensor resistance table.

02

Indoor inlet pipe sensor

Connector connection error


Faulty PCB
Faulty sensor (Open / Short)

Normal resistor : 5K/ at 25C(Unplugged)


Normal voltage : 2.5Vdc / at 25C(Plugged)
Refer to sensor resistance table.

06

Indoor outlet pipe sensor

Connector connection error Normal resistor : 5K/ at 25C(Unplugged)


Faulty PCB
Normal voltage : 2.5Vdc / at 25C(Plugged)
Faulty sensor (Open / Short) Refer to sensor resistance table.

Check Flow Chart

Unplug the sensor


on Indoor unit PCB

Estimate the Voltage


of each sensor.

Check the
Connector connection

Is the voltage of
the sensor 2.5Vdc
at 25C

No
Correct connection

Yes
Is it normal ?

No
Correct connection

Repair or Change the PCB.

Unplugged

Yes

Plugged

Estimate the resistance


of each sensor.
Is the resistance of
the sensor 10 /
5k at 25C?
Yes

No
Correct connection

10k

2.5Vdc

Plug the sensor


on Indoor unit PCB

Check the resistance

Check the voltage

LGE Internal Use Only

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

5. Trouble Shooting

6.7 Check code Trouble shooting CH03


Display
code

03

Title

Cause of error

Check point & Normal condition

Communication Error
(Wired remote controller)

Connector connection
error
Faulty PCB / Remote
controller
Connection wire break

Connection of wire
Main PCB Volt. DC12V
Noise interference

Check Flow Chart


CN-REMO
Check the wire
connection(Open /
Short / Miswirring)
Is it normal ?
Yes
Is the soldering state
of connector is normal?
Yes

No
Correct connection
Or change connection wire

No
Re-soldering component
Or change the PCB

Check the volt. of main


PCB power source.
(DC 12V,DC 5V)
Is it normal ?
Yes

Wired R/C

Indoor Unit

S 12V GND
(YL) (RD) (BR)

12V S GND
(RD) (YL) (BR)

No
Correct connection
Or change the PCB

12Vdc

12Vdc

Check the installation of


wired remote controller.
(Noise interference)
Is it normal ?

No
Adjust the state
of installation

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

Check the Volt.

- 68 -

Check the Volt.

LGE Internal Use Only

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

5. Trouble Shooting

6.8 Check code Trouble shooting CH04


Display
code

Title

04

Drain pump
/ Float switch

Cause of error
Float switch open.
(Normal : short)
Water over flow

Check point & Normal condition


The connection of wire (Drain pump/ Float switch)
Drain pump power input. (220V)
Drain tube installation.
Indoor unit installation. (Inclination)

Check Flow Chart

Check the level of


water (Float moves top
position)
Is it normal ?

CN-Float

No
Check Drain Pump

CN-Float

Yes
Is the float
switch clean ?

No
Clean float switch

Drain pump check

Yes

Check the wire


connection (Open,
Soldered poorly)

Check the wire


connection (Open,
Soldered poorly)

Is it normal ?
Is it normal ?
Yes
Is the resistance of f
loat switch normal
(short) ?

No
Correct connection
Or re-soldering PCB

Yes

No
Change the float switch

Is the resistance of
Drain Pump? Normal
( about 400 ) ?

No
Correct connection
Or re-soldering PCB

No
Change the Drain Pump

Yes
Is the drain
pump clean ?

No
Clean drain pump

Yes
Check drain tube
installation

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 69 -

LGE Internal Use Only

5. Trouble Shooting

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

6.9 Check code Trouble shooting CH09, CH10


Display
code

Title

09

EEPROM
Check sum (Indoor)

10

BLDC motor
fan lock (Indoor)

Cause of error

Check point & Normal condition

Check sum error

Check the poor soldering.


Change PCB

Fan motor break down


Fan motor & PCB poor
contact
Obstruction to the fan

Check the indoor fan motor.


Check the connection status between
PCB and fan motor.

Check Flow Chart

Check the indoor fan


motor. (Fan is locked by
obstruction)
Is it normal ?

No
Remove obstruction

Yes
Check the connection
status between PCB and
fan motor
Is it normal ?

No
Correct connection Or re-soldering PCB

Yes
Check the DC Motor
signal

Is it normal ?

No
Change Indoor Motor

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 70 -

LGE Internal Use Only

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

5. Trouble Shooting

6.10 Check code Trouble shooting CH05, CH53


Display
code

05
/
53

Title

Communication
(IndoorOutdoor)

Cause of error

Check point & Normal condition

The connector for transmission is disconnected.


The connecting wires
are misconnected.
The communication line
is break
Outdoor PCB is
abnormal.
Indoor PCB is abnormal.

Check power input AC 230V. (Outdoor, Indoor)


Check connector for transmission
Check wires are misconnecting.
Check transmission circuit of outdoor PCB
Check transmission circuit of indoor PCB

Check Flow Chart

Check the input power


AC230V (Outdoor,
Indoor unit)
Is it normal ?
( 230V 10% )

Is the connection of
GND,GND1,GND2,
correctly connected?

No
Correct connection

Yes
No
Needs electric work

Change PCB

Yes
Check the communication
wires are correctly
connected.
Is it normal ?
Yes
Check the resistance
between communication
line and GND.
(Normal : Over 2M)
Is it normal ?

No
Adjust the connection
of wire Confirm the
wire of "Live",
"Neutral", "Signal"

CH05 is displayed at indoor unit,


CH53 is displayed at outdoor unit.

No
Correct connection

Yes
Is connector for
communication
correctly connected?

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 71 -

LGE Internal Use Only

5. Trouble Shooting

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

6.11 Check code Trouble shooting CH21


Display
code

21

Title

DC Peak

Cause of error

Check point & Normal condition

Instant over current


Over Rated current
Poor insulation of IPM

An instant over current in the U,V,W phase


- Comp lock
- The abnormal connection of U,V,W
Over load condition
- Overcharging of refrigerant
- Pipe length.
Poor insulation of compressor

Check Flow Chart

Check the wire


connection.(U,V,W)

Is it normal ?
Yes

Is it normal ?
(1 Ph : 230V 10%
3 Ph : 400V 10% )
Yes

No
Correct
connection

Check DC link
capacitor Is it normal?
(Refer to belows)

Check the resistance of


comp. (No difference at
each terminal)
Is it normal ?
Yes

Yes
Check Over load condition
- Overcharging of
refrigerant
- Pipe Length
- Condenser is blocked
- Outdoor fan is locked

No
Change
Compressor

Check the electricity


leakageof the compressor.
(Refer to comp check table)
Is it normal ?
Yes

No
Needs electric work

No
Change DC link
capacitor
Or Main PCB
Remove obstruction
Change outdoor fan
or motor
Change refrigerant

No
Change Main PCB
No
Change
Compressor

Dc link voltage table


Model
1 Phase

Check the input power


(Outdoor, Indoor unit)

3 Phase

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

DC Link Voltage
Type

Operating
DC280V 10%
DC280V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%

PFC

DC300V 10%

DC380V 10%

PSC
PFC
PFC

DC540V 10%
DC540V 10%
DC540V 10%

DC500V 10%
DC680V 10%
DC680V 10%

PFC

DC540V 10%

DC680V 10%

PSC
PSC
PFC
PFC
PFC
PFC
PFC

AUUW606D
AUUW368D
AUUW428D
AUUW488D
AUUW608D

- 72 -

Non operating
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%

AUUW126C
AUUW186C
AUUW246D
AUUW306D
AUUW366D
AUUW426D
AUUW486D

LGE Internal Use Only

10

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

5. Trouble Shooting

6.12 Check code Trouble shooting CH22


Display
code

Title

22

Max. C/T

Cause of error

Check point & Normal condition

Malfunction of compressor
Blocking of pipe
Low voltage input
Refrigerant, pipe length, blocked,

Over current

Check Flow Chart

Check the wire


connection.(U,V,W)

Is it normal ?
Yes

Is it normal ?
(1 Ph : 230V 10%
3 Ph : 400V 10% )
Yes

No
Correct
connection

Check DC link
capacitor Is it normal?
(Refer to belows)

Check the resistance of


comp. (No difference at
each terminal)
Is it normal ?
Yes

Yes
Check Over load condition
- Overcharging of
refrigerant
- Pipe Length
- Condenser is blocked
- Outdoor fan is locked

No
Change
Compressor

Check the electricity


leakageof the compressor.
(Refer to comp check table)
Is it normal ?
Yes

No
Needs electric work

No
Change DC link
capacitor
Or Main PCB
Remove obstruction
Change outdoor fan
or motor
Change refrigerant

No
Change Main PCB
No
Change
Compressor

Dc link voltage table


Model
1 Phase

Check the input power


(Outdoor, Indoor unit)

3 Phase

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

DC Link Voltage
Type

Operating

DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%

DC280V 10%
DC280V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%

PFC

DC300V 10%

DC380V 10%

PSC
PFC
PFC

DC540V 10%
DC540V 10%
DC540V 10%

DC500V 10%
DC680V 10%
DC680V 10%

PFC

DC540V 10%

DC680V 10%

AUUW126C
AUUW186C
AUUW246D
AUUW306D
AUUW366D
AUUW426D
AUUW486D

PSC
PSC
PFC
PFC
PFC
PFC
PFC

AUUW606D
AUUW368D
AUUW428D
AUUW488D
AUUW608D

- 73 -

Non operating

LGE Internal Use Only

11

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

5. Trouble Shooting

6.13 Check code Trouble shooting CH40


Title

40

C/T
Internal circuit

Cause of error

Initial current error

Check point & Normal condition

Malfunction of current detection circuit.


(Open / Short)
The voltage of C01N Is 4.0Vdc (25A) .

Display
code

Check Flow Chart

Check the input power


AC230V
(Outdoor, Indoor unit)
TRANS
Is it normal ?
( 230V10%)

No
Correct connection

Yes

Check C01N
Is it normal (4.0Vdc )?

C01N
No
Change Main PCB

Yes
Check Check TRANS
Is it normal?

No
Change TRANS

Yes
Change main PCB

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 74 -

LGE Internal Use Only

12

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

5. Trouble Shooting

6.14 Check code Trouble shooting CH23, CH28


Display
code

Title

23

DC Link
Low voltage.

1ph : DC link volt. is


140Vdc .
3ph : DC link volt. is
250Vdc .

Check the power source.


Check the components.

28

DC Link
High voltage

1ph : DC link volt. is


140Vdc .
3ph : DC link volt. is
250Vdc .

Check the power source.


Check the components.

25

Input voltage

Abnormal Input voltage


(140Vac , 300Vac )

Check the power source.


Check the components.

Cause of error

Check point & Normal condition

Check DC link voltage

Check Flow Chart

Check the wire


connection.(U,V,W)

Is it normal ?
Yes
Is it normal ?
Yes

No
Correct
connection

Check TRANS1

No
Change
Compressor

CN_TRANS 1

Dc link voltage table


Is it normal ?
Yes

No
Change
Compressor

Model
1 Phase

Check the input power

3 Phase

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

DC Link Voltage
Type

Operating

DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%

DC280V 10%
DC280V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%

PFC

DC300V 10%

DC380V 10%

PSC
PFC
PFC

DC540V 10%
DC540V 10%
DC540V 10%

DC500V 10%
DC680V 10%
DC680V 10%

PFC

DC540V 10%

DC680V 10%

AUUW126C
AUUW186C
AUUW246D
AUUW306D
AUUW366D
AUUW426D
AUUW486D

PSC
PSC
PFC
PFC
PFC
PFC
PFC

AUUW606D
AUUW368D
AUUW428D
AUUW488D
AUUW608D

- 75 -

Non operating

LGE Internal Use Only

13

5. Trouble Shooting

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

6.15 Check code Trouble shooting CH24


Display
code

Title

24

Press S/W Open

Cause of error

Check point & Normal condition

Check the connection of CN_PRESS


Check the SVC V/V open.
Check the leakage of refrigerant.

Low / High press


S/W open.

Check Flow Chart

Is the wire connection


normal ?

Pressure switch table


No
Correct connection

Switch
Spec
Model

Yes
Is the soldering
state of connector is
normal?

No
Re-soldering component

Yes
Is the SVC Valve
opened ?

Low pressure switch


0.03 Mpa
AUUW126C
AUUW186C

High pressure switch


4.3 Mpa
AUUW246D
AUUW306D
AUUW366D
AUUW426D
AUUW486D
AUUW606D
AUUW368D
AUUW428D
AUUW488D
AUUW608D

No
Open SVC Valve

Yes
CN_PRESS

Check the leakage of


refrigerant.
Check Pressure of
suction pipe
Check Pressure of
discharge pipe
Is it normal ?

Yes

No
Re-vaccuming system
& Re-charging

Change main PCB

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 76 -

LGE Internal Use Only

14

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

5. Trouble Shooting

6.16 Check code Trouble shooting CH26, CH27


Display
code

Title

26

DC Compressor
Position

Compressor
position detect error

Check the connection of comp wire U,V,W


Malfunction of compressor
Check the component of IPM, detection parts.

27

PSC Fault
PFC Fault

Over current at
IGBT/PFC module

Check the component of IGBT /PFC module.


Check the components.

Cause of error

Check point & Normal condition

Check Flow Chart

Check the wire


connection.(U,V,W)

Is it normal ?
Yes

Is it normal ?
(1 Ph : 230V 10%
3 Ph : 400V 10% )
Yes

No
Correct
connection

Check DC link
capacitor Is it normal?
(Refer to belows)

Check the resistance of


comp. (No difference at
each terminal)
Is it normal ?
Yes

Yes
Check Over load condition
- Overcharging of
refrigerant
- Pipe Length
- Condenser is blocked
- Outdoor fan is locked

No
Change
Compressor

Check the electricity


leakageof the compressor.
(Refer to comp check table)
Is it normal ?
Yes

No
Needs electric work

No
Change DC link
capacitor
Or Main PCB
Remove obstruction
Change outdoor fan
or motor
Change refrigerant

No
Change Main PCB
No
Change
Compressor

Dc link voltage table


Model
1 Phase

Check the input power


(Outdoor, Indoor unit)

3 Phase

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

DC Link Voltage
Type

Operating

DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%
DC300V 10%

DC280V 10%
DC280V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%
DC380V 10%

PFC

DC300V 10%

DC380V 10%

PSC
PFC
PFC

DC540V 10%
DC540V 10%
DC540V 10%

DC500V 10%
DC680V 10%
DC680V 10%

PFC

DC540V 10%

DC680V 10%

AUUW126C
AUUW186C
AUUW246D
AUUW306D
AUUW366D
AUUW426D
AUUW486D

PSC
PSC
PFC
PFC
PFC
PFC
PFC

AUUW606D
AUUW368D
AUUW428D
AUUW488D
AUUW608D

- 77 -

Non operating

LGE Internal Use Only

15

4. Trouble Shooting
Display
code

29

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

Title

Inverter compressor over


current

Cause of error

Check point & Normal condition

1. Overload operation
(Pipe clogging/Covering/EEV defect/Ref. overcharge)
Inverter compressor input
2. Compressor damage(Insulation damage/Motor
current is over 30A
damage)
3. Input voltage low
4. ODU inverter PCB assembly damage

Error Diagnosis and Countermeasure Flow Chart


Is installation
condition normal?

No

Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?

No

1. Check Pipe clogging/distortion


2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
(0.188 7%)
2. Check insulation resistance between compressor
terminal and pipe (over 50M )
Replace compressor if abnormality found

Yes
Is compressor
Wire connection
condition normal?

No

1. Check inverter PCB assembly U,V,W connector


connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
Reassemble if abnormality found

Yes

Is input voltage normal?

No

Check
L~N phase is 220V 15%
Check connection condition and wiring if power is
abnormal

No

Check inverter PCB assembly IPM normality


Replace inverter PCB assembly

Yes

Is inverter PCB assembly


normal?

Yes
Recheck power and installation condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 90 -

LGE Internal Use Only

16

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

5. Trouble Shooting

6.17 Check code Trouble shooting CH32, CH33


Title

32

D-pipe (Inverter)
temp. high
(105C )

33

D-pipe (Constant)
temp. high
(105C )

Display
code

Cause of error

Check point & Normal condition

Discharge sensor
(Inverter) temp. high

Check the discharge pipe sensor for INV.


Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.
Refer to sensor resistance table.

Discharge sensor
(Cons.) temp. high

Check the discharge pipe sensor for Cons.


Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.
Refer to sensor resistance table.

Check Flow Chart

Check Over load condition


- Refrigerant leakage
- Condenser is blocked
- Outdoor fan is locked
Yes

Is the resistance of the


sensor is 200k
at 25C?

No
Remove obstruction
Change outdoor fan
or motor
Change refrigerant

Yes
Plug the sensor
on Indoor unit PCB

Unplug the sensor


on Outdoor unit PCB

Estimate the Voltage


of each sensor.

Check the
Connector connection

Is it normal ?

No
Change the sensor

Yes
Is the voltage of the
sensor is
4.5Vdc at 25C

No
Correct connection

Yes

Yes
Repair or Change the PCB.

Estimate the resistance


of each sensor.

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

No
Change the sensor

- 78 -

LGE Internal Use Only

17

Single A: Inverter & Synchro


(UU..W & UU72 / 100)
Display
code

Title

39

Transmission Error
Between (PFC Micom
INV Micom)

Cause of error

4. Trouble Shooting

Check point & Normal condition


1. Micom defect/Circuit defect
2. Different Micom S/W Version
3. ODU inverter PCB assembly damage

Communication Error
Between PFC Micom
and INV Micom.

Error Diagnosis and Countermeasure Flow Chart

Is PFC Micom & INV Micom


S/W Program normal?

No

Upgrade Micom Program

Yes

Is Inverter PCB assembly normal?

No

Replace inverter PCB assembly

Yes

Recheck power and installation condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 115 -

LGE Internal Use Only

18

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

5. Trouble Shooting

6.18 Check code Trouble shooting CH41, CH44, CH45, CH46, CH47, CH65
Display
code

Title

41
47

D-pipe sensor(Inv)
D-pipe sensor(Cons)

Connector connection error Normal resistor : 200K/ at 25C (Unplugged)


Normal voltage : 4.5Vdc / at 25C (plugged)
Faulty PCB
Faulty sensor (Open / Short) Refer to sensor resistance table.

44

Air sensor

Connector connection error Normal resistor : 10K/ at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)
Faulty PCB
Faulty sensor (Open / Short) Refer to sensor resistance table.

45
46

Condenser Pipe sensor


Suction Pipe sensor

Connector connection error Normal resistor : 5K/ at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)
Faulty PCB
Faulty sensor (Open / Short) Refer to sensor resistance table.

65

Heat sink
sensor

Connector connection error Normal resistor : 5K/ at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)
Faulty PCB
Faulty sensor (Open / Short) Refer to sensor resistance table.

Cause of error

Check point & Normal condition

Check Flow Chart

Unplug the sensor


on Indoor unit PCB

Estimate the Voltage


of each sensor.

Check the
Connector connection

Is the voltage of the


sensor is 4.5Vdc /
2.5Vdc at 25C

No
Change the sensor

Yes
Is it normal ?

No
Correct connection

Yes

Repair or Change the PCB.

Unplugged

Plugged

Estimate the resistance


of each sensor.
Is the resistance of the
Sensor is 200k/10k
/5k at 25C?

No
Change the sensor

Yes

10k

2.5Vdc

Plug the sensor


on Indoor unit PCB

Check the resistance

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 79 -

Check the voltage

LGE Internal Use Only

19

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

5. Trouble Shooting

6.19 Check code Trouble shooting CH51, CH60


Display
code

Title

51

Over capacity

60

EEPROM
Check sum

Cause of error

Check point & Normal condition

Over capacity
Combination

Check the indoor unit capacity.


Check the combination table.

Check sum error

Check the connection port.


Check the poor soldering.

Check Flow Chart (CH51)

Check the
indoor unit combination
Check the outdoor
unit max combination

Is it normal ?

No
Correct connection

Yes
Check PCB

Check Flow Chart (CH60)


Check the the
connection port.

Is it normal ?

No
Correct connection

Yes
Change EEPROM

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 80 -

LGE Internal Use Only

20

Single A: Inverter & Synchro


(UU..W & UU72 / 100)
Display
code

Title

Cause of error

52

Transmission error
between (Inverter PCB
Main PCB)

Main controller of Master


unit of Master unit cant
receive signal from
inverter controller

4. Trouble Shooting

Check point & Normal condition


1. Power cable or transmission cable is not
connected
2. Defect of outdoor Main fuse/Noise Filter
3. Defect of outdoor Main / inverter PCB

Error diagnosis and countermeasure flow chart


Is transmission
LED (Yellow) of inverter
compressor
PCB on?

No

Is noise filter or fuse


normal?

No

Replace noise filter or fuse

Yes

Yes

Replace inverter compressor PCB

Is transmission cable
connected correctly?

No
Re-connect transmission cable

Yes

No
Is MAIN PCB normal?

Replace MAIN PCB

Yes

Replace inverter compressor PCB

Check Point
- Check the Transmission connector and LED (Main & Inverter)

48/56k

<Inverter PCB>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

<MAIN PCB>

- 93 -

LGE Internal Use Only

21

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

Troubleshooting Guide

14) Troubleshooting CH54


Display
code

Title

54

3-phase wrong wiring


of main outdoor unit

Cause of error

3-phase wrong wiring of


outdoor unit (Reverse
Phase /omission of
phase)

Check point & Normal condition

Abnormal Main PCB


No connection of CN_Phase
Changed R, S, T connection order

Check Point
1. Check the connection condition of R,S,T wire.
2. Check the connection condition of CN_Phase.
3. Check the outdoor main fuse.

22

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

5. Trouble Shooting

6.20 Check code Trouble shooting CH61, CH62


Display
code

Title

61

Condenser
pipe sensor
temp. high

condenser pipe
sensordetected high
temp.(65C)

Check the load condition.


Check the sensor of Condenser pipe sensor.
Normal resistor : 5K/ at 25C (Unplugged)
Normal voltage : 2.5Vdc / at 25C (Plugged)

62

Heat sink sensor


temp. high

heat sink sensor


detected high temp.
(85C)

Check the load condition.


Check the sensor of heat sink.
Normal resistor : 10K/ at 25C (Unplugged)
Normal voltage : 2.5Vdc / at 25C (Plugged)

Cause of error

Check point & Normal condition

Check Flow Chart

Check Over load condition


- Refrigerant leakage
- Condenser is blocked
- Outdoor fan is locked
Yes

Is the resistance of
the Sensor is 5k
/10k at 25C?

No
Remove obstruction
Change outdoor fan
or motor
Change refrigerant

Yes
Plug the sensor
on Indoor unit PCB

Unplug the sensor


on Outdoor unit PCB

Estimate the Voltage


of each sensor.

Check the
Connector connection

Is it normal ?

No
Change the sensor

Yes
Is the voltage of the
sensor is 4.5Vdc /
2.5Vdc at 25C

No
Correct connection

Yes

Yes
Repair or Change the PCB.

Estimate the resistance


of each sensor.

Copyright 2008 LG Electronics. Inc. All right reserved.


Only for training and service purposes

No
Change the sensor

- 81 -

LGE Internal Use Only

23

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

4. Trouble Shooting
Display
code

73

Title

AC input instant over current error


(Matter of software)

Cause of error

Check point & Normal condition

Inverter PCB input power


current is over 48A(peak)
for 2ms

1. Overload operation (Pipe clogging/Covering/EEV


defect/Ref.overcharge)
2. Compressor damage
(Insulation damage/Motor damage)
3. Input voltage abnormal (L, N)
4. Power line assemble condition abnormal
5. Inverter PCB assembly damage
(input current sensing part)

Error Diagnosis and Countermeasure Flow Chart


Is installation
condition normal?

No

Yes

1.Check Pipe clogging/distortion


2.Check Covering (Indoor/Outdoor Unit)
3.Check EEV connector assemble condition/normal operation
4.Check refrigerant pressure
Reassemble or manage if abnormality found

No

Check
L~N phase voltage is 220V 10%
Check connection condition and wiring if power is abnormal

No

1.Check L,N connection condition


2.Check wire disconnection and wiring
Reassemble if abnormality found

No

1.Check inverter PCB assembly U,V,W connector connection condition


2.Check wire disconnection and wiring
3.Check compressor terminal connection condition(bad contact)
Reassemble if abnormality found

Is input voltage normal?

Yes

Is AC input Wire connection


condition normal?
Yes

Is compressor
Wire connection
condition normal?
Yes

Is inverter PCB assembly


normal?

No
Check inverter PCB assembly IPM normality
Replace inverter PCB assembly

Yes
Recheck power and
installation condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 102 -

LGE Internal Use Only

24

Single A: Inverter & Synchro


(UU..W & UU72 / 100)

Troubleshooting Guide

16) Troubleshooting CH67, CH105


Display
code

Title

Cause of error

67

Outdoor fan
lock

Outdoor fan is not operating

Check the fan condition.


Check the fan connector

105

Communication error
between main PCB and
fan PCB

Communication error
between main PCB
and fan PCB

Short or fusing of communication line


Poor outdoor unit PCB
Power input when the DC link capacitor discharges

Check Point

Check point & Normal condition

CH 67

CH 105

1. Check the install condition for fan.

1. Is communication line between the main PCB and the


fan PCB normal?
2. Is the communication LED on?

25

Single A
Aan / uit, Single-split
AT-C.. / AT-H..
LB-C.. / LB-D.. / LB-E.. / LB-G.. / LB-H..
LT-B.. / LT-C.. / LT-D.. / LT-E..
LV-B..
P03AH / P05AH / P08AH

26

Single A: Aan/uit Single-split


(voor modellen, zie pag. 26)

Troubleshooting Guide

1) Troubleshooting CH01, CH02, CH06


Display
code

Title

01

Indoor air sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 10K. / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

02

Indoor inlet pipe sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 5K. / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

Indoor outlet pipe sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 5K. / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

06

Cause of error

Check point & Normal condition

10k.

2.5Vdc

Check the resistance

Check the voltage

Check Point

1. Unplug the sensor on Indoor unit PCB.


2. Estimate the resistance of each sensor.
3. If the resistance of the sensor is 10K. / 5K. at 25C, then sensor is normal.
4. If the resistance of the sensor is 0 K. or 8 , then sensor is abnormal. Change the sensor.
5. Plug the sensor on Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc at 25C, then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. Repair or Change the PCB.

27

Single A: Aan/uit Single-split


(voor modellen, zie pag. 26)

Troubleshooting Guide
2) Troubleshooting CH03
Display
code

Title

03

Communication
Wired R/C

Cause of error

Wired R/C
12V

Open / Short
Wrong connection

Indoor Unit

GND

12V

Connection of wire
Main PCB Volt. DC12V
Noise interference

CN-REMO

GND

12Vdc

12Vdc

Check the Volt.

Check point & Normal condition

Check the Volt.

Check Point

1. Check the wire connection. (Open / Short) Repair the connection


2. Check the soldering state of connector. (Soldered poorly) Repair or Change the PCB.
3. Check the volt. Of main PCB power source. (DC 12V, DC 5V) Repair or Change the main PCB.
4. Check the installation of wired remote controller. (Noise interference) Adjust the state of installation

28

Single A: Aan/uit Single-split


(voor modellen, zie pag. 26)

Troubleshooting Guide

3) Troubleshooting CH04
Display
code

Title

04

Drain pump
/ Float switch

Cause of error
Float switch Open.
(Normal : short)

Check point & Normal condition


The connection of wire(Drain pump/ Float switch)
Drain pump power input. (220V)
Drain tube installation.
Indoor unit installation. (Inclination)

CN Float

CN-D/PUMP
CN-Float

0.
.

Check the resistance

Check Point

1. Check the wire connection. (Open, Soldered poorly) Repair the connection or change the PCB.
2. Check the resistance of float switch (Abnormal : Open, Normal : short) Check the float switch.
3. Check the level of water
4. Check the volt. Of Drain pump power supply. (AC 230V) Repair or Change the main PCB.

29

Troubleshooting Guide

Single A: Aan/uit Single-split


(voor modellen, zie pag. 26)

4) Troubleshooting CH05, CH53


Display
code
05
/
53

Title

Communication
(Indoor Outdoor)

Cause of error

Communication poorly

Check point & Normal condition


Power input AC 220V. (Outdoor, Indoor)
The connector for transmission is disconnected.
The connecting wires are misconnected.
The GND1,2 is not connected at main GND.
The communication line is shorted at GND.
Transmission circuit of outdoor PCB is abnormal.
Transmission circuit of indoor PCB is abnormal.

Check Point

1. Check the input power AC230V. (Outdoor, Indoor unit)


2. Check the communication wires are correctly connected.
Adjust the connection of wire
Confirm the wire of Live, Neutral
3. Check the resistance between communication line and
GND. (Normal : Over 2M. )
4. Check the connector for communication is correctly
connected.
5. Check the connection of GND1, GND2, and main GND.
6. If one indoor unit is operated normally, outdoor PCB is no
problem.
Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.

30

Single A: Aan/uit Single-split


(voor modellen, zie pag. 26)

Troubleshooting Guide

5) Troubleshooting CH21
Display
code

Title

21

Cause of error

Instant over current


Over Rated current
Poor insulation of IPM

DC Peak

Comp
U

Terminal
U-V
V-W
W-U

Comp

An instant over current in the U,V,W phase


- Comp lock
- The abnormal connection of U,V,W
Over load condition
- Overcharging of refrigerant
- Pipe length.
Poor insulation of compressor

Resistance(. ) at 20C
.

Check point & Normal condition

Copper
pipe

Inverter Constant
comp.
comp.
0.64
0.64
0.64

0.8
0.8
0.8

Resistance(. ) at 20C
.

Terminal
U-GND
V-GND
W-GND

Inverter Constant
comp.
comp.
2M.
2M.
2M.

2M.
2M.
2M.

Check Point

1. Check the wire connection. (U,V,W)


2. Check the load condition. (Refrigerant, Pipe length, ) Adjust the load condition
3. Check the electricity leakage of the compressor. Normal : Over 2M. .
4. Check the resistance of compressor. Normal : 0.65. (INV), 0.8. (Cons.) No difference at each terminal.
5. Check the insulation from water at IPM part. Check the trace of water.
6. Check the IPM circuit.

31

Single A: Aan/uit Single-split


(voor modellen, zie pag. 26)

Troubleshooting Guide

6) Troubleshooting CH21, CH22


Display
code

Title

Cause of error

21

Max. C/T

22

C/T
Internal circuit

Check point & Normal condition

Over current (14A )

Malfunction of compressor
Blocking of pipe
Low voltage input
Refrigerant, pipe length, blocked,

Initial current error

Malfunction of current detection circuit.


(Open / Short)
The voltage of C01N Is 4.0Vdc(25A) .

Check Point
1. Check the power source.

2. Check the fan operation is right.

3. Check the current.


4. Check the install condition.
5. Check the internal circuit. (C/T, Diode, Resistor)

108 Universal System Air Conditioner

Troubleshooting Guide

Single A: Aan/uit Single-split


(voor modellen, zie pag. 26)

8) Troubleshooting CH24, CH25


Display
code

Title

24

Press S/W Open

25

Input voltage

Cause of error

Check point & Normal condition

Low / High press


S/W open.

Check the connection of CN_Press.


Check the components.

Abnormal Input voltage


(140Vac , 300Vac .

Check the power source.


Check the components.

TRANS1
50Hz, DC12V

CN PRESS

CN TRNAS1

Check Point
CH 24

CH 25

1. Check the connection of CN_PRESS

1. Check the power source.

2. Check the install condition for over load.

2. Check the components


(Trans1, B/Diode, Diode, Resistance)

3. Check the SVC V/V open.


4. Check the leakage of refrigerant.

110 Universal System Air Conditioner

Troubleshooting Guide

Single A: Aan/uit Single-split


(voor modellen, zie pag. 26)

10) Troubleshooting CH32, CH33


Display
code

Title

32

D-pipe (Inverter)
temp. high
(105C )

33

D-pipe (Constant)
temp. high
(105C )

Cause of error

Check point & Normal condition

Discharge sensor
(Inverter) temp. high

Check the discharge pipe sensor for INV.


Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.

Discharge sensor
(Cons.) temp. high

Check the discharge pipe sensor for Cons.


Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.

D-Pipe temp.
Toff(105) C
T2(95) C
T1(90) C

COMP Frequency
Normal
(Hz)
LEV Openness
(Pulse)

Normal

Normal

OFF

Normal

OFF Control

Check Point
CH 32

CH 33

1. Check the install condition for over load.

1. Check the install condition for over load.

2. Check the SVC V/V open.

2. Check the SVC V/V open.

3. Check the leakage of refrigerant.

3. Check the leakage of refrigerant.


4. Check the constant compressor. (same with CH21)

34

Single A: Aan/uit Single-split


(voor modellen, zie pag. 26)

Troubleshooting Guide

11) Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65


Display
code

Title

41

D-pipe sensor (Inverter)

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 200K. / at 25C (Unplugged)


Normal voltage : 4.5Vdc / at 25C (plugged)

44

Air sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 10K. / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

45

Condenser Pipe sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 5K. / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

46

Suction Pipe sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 5K. / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

D-pipe sensor (Constant)

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 200K. / at 25C (Unplugged)


Normal voltage : 4.5Vdc / at 25C (plugged)

Heat sink sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 10K. / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

47

65

Cause of error

Check point & Normal condition

Check Point

1. Estimate the resistance of each sensor.(Unplugged)


2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance of the sensor is 0 k. or 8 , then sensor is abnormal.

If the voltage of the sensor is 0 V or 5Vdc, then sensor is abnormal.

35

Single A: Aan/uit Single-split


(voor modellen, zie pag. 26)

Troubleshooting Guide

12) Troubleshooting CH51, CH60


Display
code

Title

51

Over capacity

60

EEPROM
Check sum

Cause of error

Check point & Normal condition

Over capacity
Combination

Check the indoor unit capacity.


Check the combination table.

Check sum error

Check the PCB ASM P/No.


Check the poor soldering.

Model

Gross max. capacity

Max. single indoor unit capacity

AUUW126B

21k

12k

AUUW186B
AUUW246B

24k

12K

AUUW306B
AUUW366B

33k

18K

AUUW4860

39k

18K

AUUW6060

52k

24K

Check Point
CH 51

CH 60

1. Check the indoor unit capacity.

1. Check the insertion condition of EEPROM.


2. Check the poor soldering

36

Single A: Aan/Uit Single-split


(voor modellen, zie pag. 26)

Troubleshooting Guide

13) Troubleshooting CH61, CH62


Display
code

Title

Cause of error

61

Condenser
pipe sensor
temp. high

Condenser pipe sensor


detected high
temp.(65C)

Check the load condition.


Check the sensor of Condenser pipe sensor.

62

Heat sink sensor


temp. high

Heat sink sensor


detected high
temp.(85C)

Check the fan is locked.


Check the sensor of heat sink.

Check point & Normal condition

Heat Sink temp.


Toff C
T2 C
T1 C

COMP Frequency
Normal
(Hz)

Normal

Check Point

OFF

Normal

CH 61

CH 62

1. Check the install condition for over load.


(Refrigerant, Pipe length, Blocked, )

1. Check the fan is locked.


2. Check the Outdoor temp. is very high.

37

Single A: Aan/uit Single-split


(voor modellen, zie pag. 26)
Troubleshooting Guide

Troubleshooting CH54
Display
code

Title

54

Phase error

Cause of error

Check point & Normal condition

Check the Main power


Check the CN_PHASE connector

Phase change

Phase_A

5.3 msec

Phase_B
Phase_C
1
0
1

1
0
0

1
1
0

0
1
0

0
1
1

0
0
1

Check Point
1. Check the Main power.
2. Check the connecting state of connector CN_3PHASE on the outdoor pcb ass'y.

38

LG

Multi-split
Inverter
FM..AH

39

Multi-split: Inverter
FM..AH

4. Trouble Shooting

6.6 Troubleshooting Indoor Error


Display
code

Title

01

Indoor air sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 10K/ at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

02

Indoor inlet pipe sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 5K/ at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

06

Indoor outlet pipe sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 5K/ at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

Cause of error

Check point & Normal condition

10k

2.5Vdc

Check the resistance

Check the voltage

Check Point
1. Unplug the sensor on Indoor unit PCB.
2. Estimate the resistance of each sensor.
3. If the resistance of the sensor is 10K/ 5K at 25C, then sensor is normal.
4. If the resistance of the sensor is 0 K or , then sensor is abnormal. Change the sensor.
5. Plug the sensor on Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc at 25C, then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. Repair or Change the PCB.

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 59 -

LGE Internal Use Only

40

Multi-split: Inverter
FM..AH

4. Trouble Shooting
Display
code

Title

03

Communication
Wired R/C

Cause of error

Wired R/C
12V

Open / Short
Wrong connection

Indoor Unit

GND

12V

Connection of wire
Main PCB Volt. DC12V
Noise interference

CN-REMO

GND

12Vdc

12Vdc

Check the Volt.

Check point & Normal condition

Check the Volt.

Check Point
1. Check the wire connection. (Open / Short) Repair the connection
2. Check the soldering state of connector. (Soldered poorly) Repair or Change the PCB.
3. Check the volt. Of main PCB power source. (DC 12V, DC 5V) Repair or Change the main PCB.
4. Check the installation of wired remote controller. (Noise interference) Adjust the state of installation

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 60 -

LGE Internal Use Only

41

Multi-split: Inverter
FM..AH
Display
code

Title

04

Drain pump
/ Float switch

Cause of error

Float switch Open.


(Normal : short)

4. Trouble Shooting
Check point & Normal condition

The connection of wire(Drain pump/ Float switch)


Drain pump power input. (220V)
Drain tube installation.
Indoor unit installation. (Inclination)

CN Float

CN-D/PUMP
CN-Float

Check the resistance

Check Point
1. Check the wire connection. (Open, Soldered poorly) Repair the connection or change the PCB.
2. Check the resistance of float switch (Abnormal : Open, Normal : short) Check the float switch.
3. Check the level of water
4. Check the volt. Of Drain pump power supply. (AC 230V) Repair or Change the main PCB.

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 61 -

LGE Internal Use Only

42

4. Trouble Shooting

Multi-split: Inverter
FM..AH

6.7 Troubleshooting Outdoor Error


FM15AH t/m FM25AH

Display
code

05
/
53

Title

Communication
(Indoor Outdoor)

Cause of error

Communication poorly

Check point & Normal condition


Power input AC 220V. (Outdoor, Indoor)
The connector for transmission is disconnected.
The connecting wires are misconnected.
The GND1,2 is not connected at main GND.
The communication line is shorted at GND.
Transmission circuit of outdoor PCB is abnormal.
Transmission circuit of indoor PCB is abnormal.

Check Point
1. Check the input power AC230V. (Outdoor, Indoor unit)
2. Check the communication wires are correctly connected.
Adjust the connection of wire
Confirm the wire of Live, Neutral
3. Check the resistance between communication line and
GND. (Normal : Over 2M)
4. Check the connector for communication is correctly
connected.
5. Check the connection of GND1, GND2, and main GND.
6. If one indoor unit is operated normally, outdoor PCB is no
problem.
Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 62 -

LGE Internal Use Only

43

Multi-split: Inverter
FM..AH

4. Trouble Shooting
FM27AH t/m FM57AH
Display
code

Title

05
/
53

Title
Communication
(Indoor Outdoor)

Cause of error

Communication poorly

Check point & Normal condition


Power input AC 220V. (Outdoor, Indoor)
The connector for transmission is disconnected.
The connecting wires are misconnected.
The communication line is shorted at GND.
Transmission circuit of outdoor PCB is abnormal.
Transmission circuit of indoor PCB is abnormal.

Check Point
1. Check the input power AC230V. (Outdoor, Indoor unit)
2. Check the communication wires are correctly connected.
Adjust the connection of wire Confirm the wire of "Live",
"Neutral"
3. Check the resistance between communication line and
GND. (Normal : Over 2M)
4. Check the connector for communication is correctly connected.
5. If one indoor unit is operated normally, outdoor PCB is no
problem.
Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at
outdoor unit.
6. If all indoor unit is displayed CH05 but outdoor PCB not
display
CH53 : Check the CN_COM and CN_POWER is correctly
connected.

< TERMINAL BLOCK >

27/30/40k
1. In Case of CH53, Check the Connection L , N at the terminal block
48/56k
1. In Case of CH05, Check the Connection CN-POWER,
CN-COMM at the Main PCB
2. In Case of CH53, Check the Connection CN-COMM at
the Main PCB L , N at the terminal block

N
L

CN-COMM

CN-Power
< MAIN PCB >

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 72 -

LGE Internal Use Only

44

Multi-split: Inverter
FM..AH

FM15AH t/m FM27AH


4. Trouble Shooting
Display
code

Title

Cause of error

Instant over current


Over Rated current
Poor insulation of IPM

DC PEAK
(IPM Fault)

21

Check point & Normal condition


An instant over current in the U,V,W phase
- Comp lock
- The abnormal connection of U,V,W
Over load condition
- Overcharging of refrigerant
Pipe length.
Outdoor Fan is stop
Poor insulation of compressor

Error Diagnosis and Countermeasure Flow Chart


1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
Reassemble or manage if abnormality found

No

Is installation
condition normal?

Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?

1. Check resistance between each terminal of compressor


(1.083~1.123 5%)
2. Check insulation resistance between compressor
terminal and pipe (over 50M )
Replace compressor if abnormality found

No

Yes
Is compressor
Wire connection
condition normal?

No

1. Check inverter PCB assembly U,V,W connector


connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
Reassemble if abnormality found

No

Check inverter PCB assembly IPM normality


Replace inverter PCB assembly

Yes

Is inverter PCB assembly normal?

Yes
Recheck power and installation condition

Comp checking method


Comp
U

Resistance() at 20C

Comp

Copper
pipe

Terminal

Inverter
comp.

U-V
V-W
W-U

1.083
1.123
1.096

Resistance() at 20C

Terminal

Inverter
comp.

U-GND
V-GND
W-GND

50M
50M
50M

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

LGE Internal Use Only

45

Multi-split: Inverter
FM..AH

FM15AH t/m FM25AH

4. Trouble Shooting

1. Wait until inverter PCB DC voltage is discharged after main power off.
2. Pull out CN-L1(R), CN-L2(S), CN-L3(T) and CN-COMP Connector.
3. Set multi tester to resistance mode.
4. If the value between P and N terminal of IPM is short(0) or open(hundreds M), PCB needs to be replaced.(IPM damaged)
5. Set the multi tester to diode mode.
6. In case measured value is different from the table, PCB needs to be replaced.(PCB damaged).
P

Nu Nv Nw

Nu Nv Nw

27

26

25

24

23 22 21

27

26

25

24

23 22 21

0.4 ~ 0.6 V

0.4 ~ 0.6 V

PFC_IPM check
U, V, W R S T

CAUTION
In case that the control box is opend and before checking electrical parts, it should be checked that the
LED 01M, 02M turned off(wait 7 minutes after main power OFF), otherwise it may cause electrical shock.

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

LGE Internal Use Only

46

Multi-split: Inverter
FM..AH

FM27AH t/m FM57AH


Display
code

Title

Cause of error

Instant over current


Over Rated current
Poor insulation of IPM

DC PEAK
(IPM Fault)

21

4. Trouble Shooting
Check point & Normal condition

An instant over current in the U,V,W phase


- Comp lock
- The abnormal connection of U,V,W
Over load condition
- Overcharging of refrigerant
Pipe length.
Outdoor Fan is stop
Poor insulation of compressor

Error Diagnosis and Countermeasure Flow Chart


1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
Reassemble or manage if abnormality found

No

Is installation
condition normal?

Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?

1. Check resistance between each terminal of compressor


(0.34~0.35
7%)
2. Check insulation resistance between compressor
terminal and pipe (over 50M )
Replace compressor if abnormality found

No

Yes
Is compressor
Wire connection
condition normal?

No

1. Check inverter PCB assembly U,V,W connector


connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
Reassemble if abnormality found

No

Check inverter PCB assembly IPM normality


Replace inverter PCB assembly

Yes

Is inverter PCB assembly normal?

Yes
Recheck power and installation condition

Comp checking method


Comp
U

Resistance() at 20C

U-V
V-W
W-U

Comp

Terminal

Copper
pipe

Inverter Constant
comp.
comp.
0.64
0.64
0.64

0.8
0.8
0.8

Resistance() at 20C

Terminal
U-GND
V-GND
W-GND

Inverter Constant
comp.
comp.
2M
2M
2M

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

2M
2M
2M

- 73 -

LGE Internal Use Only

47

Multi-split: Inverter
FM..AH

4. Trouble Shooting
FM27AH t/m FM41AH

LED01M

LED02M

U,V,W CONNECTOR

U
V
W

1. Wait until inverter PCB DC voltage is discharged after main power off.
2. Pull out V, V, W COMP connector.
3. Set multi tester to resistance mode.
4. If the value between P and N terminal of IPM is short(0) or open(hundreds M), PCB needs to be replaced.(IPM damaged)
5. Set the multi tester to diode mode.
6. In case measured value is different from the table, PCB needs to be replaced.(PCB damaged).
P

Nu Nv Nw

Nu Nv Nw

27

26

25

24

23 22 21

27

26

25

24

23 22 21

0.4 ~ 0.6 V

0.4 ~ 0.6 V

PFC_IPM chec
U, V, W R S

CAUTION
In case that the control box is opend and before checking electrical parts, it should be checked that the
LED 01M, 02M turned off(wait 7 minutes after main power OFF), otherwise it may cause electrical shock.

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

LGE Internal Use Only

48

Multi-split: Inverter
FM..AH

4. Trouble Shooting

FM49AH t/m FM57AH

U
V
W

LED01M

LED02M

CN(L)_BRWON

CN(N)_BLUE
U,V,W CONNECTOR

1. Wait until inverter PCB DC voltage is discharged after main power off.
2. Pull out CN(L), CN(N) connectors and U,V,W COMP Connector.
3. Set multi tester to resistance mode.
4. If the value between P and N terminal of IPM is short(0) or open(hundreds M), PCB needs to be replaced.(IPM damaged)
5. Set the multi tester to diode mode.
6. In case measured value is different from the table, PCB needs to be replaced.(PCB damaged).
P

Nu Nv Nw

Nu Nv Nw

27

26

25

24

23 22 21

27

26

25

24

23 22 21

0.4 ~ 0.6 V

0.4 ~ 0.6 V

PFC_IPM chec
U, V, W R S

CAUTION
In case that the control box is opend and before checking electrical parts, it should be checked that the
LED 01M, 02M turned off(wait 7 minutes after main power OFF), otherwise it may cause electrical shock.

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 75 -

LGE Internal Use Only

49

Multi-split: Inverter
FM..AH

FM15AH t/m FM25AH


4. Trouble Shooting
Display
code

Title

Max. C/T

22

Cause of error

Input Over Current

Check point & Normal condition


1. Malfunction of Compressor
2. Blocking of Pipe
3. Low Voltage Input
4. Refrigerant, Pipe length, Blocked...

Error Diagnosis and Countermeasure Flow Chart


Is installation
condition normal?

No

Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?

No

1. Check Pipe clogging/distortion


2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
1.083~1.123 5%
2. Check insulation resistance between compressor
terminal and pipe (over 50M )
Replace compressor if abnormality found

Yes
Is compressor
Wire connection
condition normal?

No

1. Check inverter PCB assembly U,V,W connector


connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
Reassemble if abnormality found

Yes

Is inverter PCB assembly


power connection normal?

No

Check connection between inverter PCB assembly and


bridge diode(misconnection, disconnection)
wiring again if abnormality found

No

Check
R~S/S~T/T~R phase voltage is 380V 10%
R~N/S~N/T~N phase voltage is 220V 10%
Check connection condition and wiring if power is
abnormal.

No

Check inverter PCB assembly IPM normality


Replace inverter PCB assembly

Yes

Is input voltage normal?

Yes

Is inverter PCB assembly


normal?

Yes
Recheck power and installation condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 108 -

LGE Internal Use Only

50

FM15AH t/m FM25AH

Multi-split: Inverter
FM..AH

4. Trouble Shooting

Check Point
1. Check the power source.(200~240V)
2. Check the fan operation is right.
3. Check the current.
4. Check the install condition.
5. Check the CT Sensor Output signal (Check output pin 1.2 of the CT Sensor : 5V )

Tester

CT Sensor Output
(at the INVERTER PCB)

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 109 -

LGE Internal Use Only

51

Multi-split: Inverter
FM..AH

FM27AH t/m FM57AH


4. Trouble Shooting
Display
code

22

Title

Cause of error

Max. C/T

Input Over
Current(27/30/40k-17A
48/56k-29A )

Check point & Normal condition


1. Malfunction of Compressor
2. Blocking of Pipe
3. Low Voltage Input
4. Refrigerant, Pipe length, Blocked...

Error Diagnosis and Countermeasure Flow Chart

Is installation
condition normal?

No

Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?

No

1. Check Pipe clogging/distortion


2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
(0.188 7%)
2. Check insulation resistance between compressor
terminal and pipe (over 50M )
Replace compressor if abnormality found

Yes
Is compressor
Wire connection
condition normal?

No

1. Check inverter PCB assembly U,V,W connector


connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
Reassemble if abnormality found

Yes

Is inverter PCB assembly


power connection normal?

No

Check connection between inverter PCB assembly and


bridge diode(misconnection, disconnection)
wiring again if abnormality found

No

Check
L~N phase is 220V 15%
Check connection condition and wiring if power is
abnormal

No

Check inverter PCB assembly IPM normality


Replace inverter PCB assembly

Yes

Is input voltage normal?

Yes

Is inverter PCB assembly


normal?

Yes
Recheck power and installation condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 76 -

LGE Internal Use Only

52

FM27AH t/m FM57AH

Multi-split: Inverter
FM..AH

4. Trouble Shooting

Check Point
1. Check the power source.(220V 15%)
2. Check the fan operation is right.
3. Check the current.
4. Check the install condition.
5. Check the CT Sensor Output signal
(27/30/40k - Check output the CT Sensor : DC 2.50.2V)
(48/56k - Check output pin 1.2 of the CT Sensor : 5V )

Vdc
< Input Power Source Check Point >

< Main PCB>


<CT Sensing Check Point>

< Inverter PCB>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

<CT Sensing Check Point>

- 77 -

LGE Internal Use Only

53

Multi-split: Inverter
FM..AH

FM15AH t/m FM25AH


4. Trouble Shooting
Display
code

23

Title

DC Link Low voltage

Cause of error

DC Link volt is below


300V

Check point & Normal condition


Check point & Normal condition
Check the TAB1 is connect.
At not operating : DC Link voltage(260V )
At Comp operating : DC Link voltage(500V )

Error Diagnosis and Countermeasure Flow Chart


Is DC Link voltage
under 380V ?

No

Check the DC link Voltage AD Input of Inverter PCB


If AD Input is strange, change the Inverter PCB
(refer the next page.)

Yes

Is input voltage normal ?

No

R~S/S~T/T~R phase voltage is 400V 10%


R~N/S~N/T~N phase voltage is 220V 10%
Check connection condition and wiring if power is
abnormal.

No

Check connection from terminal block to


Inverter PCB assembly CN_L1(R), CN_L2(S), CN_L3(T)

Yes

Is Inverter PCB assembly


Power connection normal?

Yes

Is Inverter PCB Normal?

No

Replace inverter PCB assembly

Yes
Recheck power and installation condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 110 -

LGE Internal Use Only

54

FM15AH t/m FM27AH

Multi-split: Inverter
FM..AH

4. Trouble Shooting

Check Point
1. Check the Tab1 connection condition. (Refer to outdoor wiring diagram)
2. Check the CN_L1(R), CN_L2(S), CN_L3(T) connection condition
3. Check the DC Link voltage at not operating(380V )
4. Check the DC Link voltage at Comp operating(500V )
5. Check DC Link Sensing Signal (Refer the Picture)

Vdc
500Vdc 10%
+

GND

<INVERTER PCB>

<DC Link Voltage Check Point>

GND

Tester

DC Link Voltage
oltage INV

<INPUT VOLTAGE Check Point>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 111 -

LGE Internal Use Only

55

FM27AH t/m FM57AH


4. Trouble Shooting
Display
code

23

Multi-split: Inverter
FM..AH

Title

DC Link Low voltage

Cause of error

DC Link volt is below


140Vdc

Check point & Normal condition


Check point & Normal condition
Check theCN_(L),CN_(N) Connection.
At not operating : DC Link voltage(280V )
At Comp operating : DC Link voltage(340V )

Error Diagnosis and Countermeasure Flow Chart


No
Check L~N Voltage is 220V15%

Is input voltage normal ?


Yes
No
Is Inverter PCB assembly
Power connection normal?

Check connection from terminal block to


Inverter PCB assembly CN(L), CN(N)

Yes
No
Is Inverter PCB Normal?

Replace inverter PCB assembly

Yes
Recheck power and installation
condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 78 -

LGE Internal Use Only

56

FM27AH t/m FM57AH

Multi-split: Inverter
FM..AH

4. Trouble Shooting

Check Point
1. Check the WCN_P(L),P(N) Connection condition at the Main PCB.(Refer to outdoor wiring diagram)
2. Check the DC Link voltage at not operating(280V )
3. Check the DC Link voltage at Comp operating(340V )
4. Check DC Link Sensing Signal :2.4~2.8V (Refer the Picture)

< Input Power Source Check Point >


27/30/40k

Vdc
< Main PCB>

Vdc

<DC_LINK Sensing Check Point>

<DC Link Voltage Check Point>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 79 -

LGE Internal Use Only

57

Multi-split: Inverter
FM..AH

4. Trouble Shooting

FM49AH t/m FM57AH


Vdc

N
GND

< Inverter PCB>

<DC Link Voltage Check Point>

<Connection Check Point>

Vdc

DC_LINK
GND

<DC_LINK Sensing Check Point>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 80 -

LGE Internal Use Only

58

Multi-split: Inverter
FM..AH
Display
code

Title

24

Press S/W Open

Cause of error

Low / High press


S/W open.

4. Trouble Shooting
Check point & Normal condition

Check the connection CN_L/PRESS,H/PRESS


Check the components.

Error diagnosis and countermeasure flow chart


Is high pressure switch
connector connected
to PCB?*

No

Connect securely

Yes

Is high pressure switch


connector short
during off time?**

No

Replace high pressure switch

Yes

Is SVC valve open?

No

Open SVC valve

Yes
Is this error appeared
again after reset?

No

Re-check momentary
problem or not

Yes
Is high pressure
more than 2500kPa
at manifold gauge?

No

Replace PCB

Yes
Is high pressure of
LGMV similar as
at manifold gauge?

No

Replace high pressure sensor

Yes
Check pipe is blocked or
not and take measure

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 81 -

LGE Internal Use Only

59

4. Trouble Shooting

Multi-split: Inverter
FM..AH

Check Point
1. Check the connection of H/press switch
2. Check short or not at the connector of high pressure switch (Normal open)
27/30/40k

< Main PCB : Connection Check Point >

< Checking the Press switch >

48/56k

< Main PCB : Connection Check Point >

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

< Checking the H/press switch >

- 82 -

LGE Internal Use Only

60

Multi-split: Inverter
FM..AH

FM15AH t/m FM25AH


4. Trouble Shooting
Display
code

Title

25

Input voltage

Cause of error
Abnomal Input Voltage
(R,S,T -N /140Vac ,
300Vac )

Check point & Normal condition

Check the power source.


Check the components.

Error Diagnosis and Countermeasure Flow Chart


Is input voltage normal?

No

R~S/S~T/T~R phase voltage is 400V 10%


R~N/S~N/T~N phase voltage is 220V 10%
Check connection condition and wiring if power is
abnormal.

Yes

Is Inverter PCB Normal?

No

Replace inverter PCB assembly

Yes
Recheck power and installation condition

<INVERTER PCB>
Tester

GND

< CH25 Check Point >

INPUT VOLTAGE
VOL AGE INV

<INPUT VOLTAGE Check Point>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 112 -

LGE Internal Use Only

61

Multi-split: Inverter
FM..AH

FM27AH t/m FM57AH


Display
code

Title

Cause of error

25

Input voltage

Abnormal Input voltage


(140Vac , 300Vac)

4. Trouble Shooting
Check point & Normal condition

Check the power source.


Check the components.

Error Diagnosis and Countermeasure Flow Chart


Is input voltage normal ?

No

Check L~N Voltage is 220V15%

Yes
Is Inverter PCB Normal?

No

Replace inverter PCB assembly

Yes
Recheck power and
installation condition

Check Point
1. Check the Input Voltage (LN 220V10%)
2. Check Input Voltage Sensor output voltage (2.5Vdc10%)

< Input Power Source Check Point >

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 83 -

LGE Internal Use Only

62

4. Trouble Shooting

Multi-split: Inverter
FM..AH

FM27AH t/m FM57AH

Vdc

< Inverter PCB>

< Input Voltage Sensing Check Point >

FM49AH t/m FM57AH

Vdc

INPUT(V)
GND

< Input Voltage Sensing Check Point >

< Inverter PCB>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 84 -

LGE Internal Use Only

63

Multi-split: Inverter
FM..AH

FM15AH t/m FM25AH


Display
code

Title

26

DC Compressor
Position

Cause of error

Compressor
Starting fail error

4. Trouble Shooting
Check point & Normal condition

Check the connection of comp wire U,V,W


Malfunction of compressor
Check the component of IPM, detection parts.

Error Diagnosis and Countermeasure Flow Chart

Is installation
condition normal?

No

1. Check Pipe clogging/distortion


2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
Reassemble or manage if abnormality found

Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?

No

1. Check resistance between each terminal of compressor


(0.188 7%)
2. Check insulation resistance between compressor
terminal and pipe (over 50M )
Replace compressor if abnormality found

Yes
Is compressor
Wire connection
condition normal?

No

1. Check inverter PCB assembly U,V,W connector


connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
Reassemble if abnormality found

No

Check inverter PCB assembly IPM normality


Replace inverter PCB assembly

Yes

Is inverter PCB assembly normal?

Yes
Recheck power and installation condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 85 -

LGE Internal Use Only

64

Multi-split: Inverter
FM..AH

FM27AH t/m FM57AH


Display
code

Title

26

DC Compressor
Position

Cause of error

Compressor
Starting fail error

4. Trouble Shooting
Check point & Normal condition

Check the connection of comp wire U,V,W


Malfunction of compressor
Check the component of IPM, detection parts.

Error Diagnosis and Countermeasure Flow Chart

Is installation
condition normal?

No

1. Check Pipe clogging/distortion


2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
Reassemble or manage if abnormality found

Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?

No

1. Check resistance between each terminal of compressor


(1.083~1.123 5%)
2. Check insulation resistance between compressor
terminal and pipe (over 50M )
Replace compressor if abnormality found

Yes
Is compressor
Wire connection
condition normal?

No

1. Check inverter PCB assembly U,V,W connector


connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
Reassemble if abnormality found

No

Check inverter PCB assembly IPM normality


Replace inverter PCB assembly

Yes

Is inverter PCB assembly normal?

Yes
Recheck power and installation condition

Check Point
1. Check the connection condition of PCB.
2. Check the connection condition of Comp. U,V,W wire.
3. Check the comp resistor and insulation resistance .

WVU

4. Check the IPM.(Refer 106 page)


5. Check the pressure of refrigerant.
6. Check the Service Valve Open.

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 113 -

LGE Internal Use Only

65

Multi-split: Inverter
FM..AH

4. Trouble Shooting
Display
code

27

Title

Cause of error

Check point & Normal condition

1. Overload operation (Pipe clogging/Covering/EEV


defect/Ref. overcharge)
2. Compressor damage (Insulation damage/Motor
Inverter PCB input
damage)
current is over100A(peak)
3. Input voltage abnormal (L,N)
for 2us
4. Power line assemble condition abnormal
5. Inverter PCB assembly Damage (input current
sensing part)

AC Input Instant over


Current Error

Error Diagnosis and Countermeasure Flow Chart


Is installation
condition normal?

No

Yes

1.Check Pipe clogging/distortion


2.Check Covering (Indoor/Outdoor Unit)
3.Check EEV connector assemble condition/normal operation
4.Check refrigerant pressure
Reassemble or manage if abnormality found

No

Check
L~N phase voltage is 220V 15%
Check connection condition and wiring if power is abnormal

No

1.Check L,N connection condition


2.Check wire disconnection and wiring
Reassemble if abnormality found

No

1.Check inverter PCB assembly U,V,W connector connection condition


2.Check wire disconnection and wiring
3.Check compressor terminal connection condition(bad contact)
Reassemble if abnormality found

Is input voltage normal?

Yes

Is AC input Wire connection


condition normal?
Yes
Is compressor
Wire connection
condition normal?
Yes

Is inverter PCB assembly


normal?

No
Check inverter PCB assembly PFCM normality
Replace inverter PCB assembly

Yes
Recheck power and
installation condition

PFCM Moudle checking method


Set the multi tester to diode mode.
Check short between input signal pin which are
placed below PFC Module
Replace PCB assembly if it is short between pins
except No.4,5 pins.

Signal pin

CAUTION
PFCM module No.4,5 pins are internal short state.

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

8
- 86 -

LGE Internal Use Only

66

Multi-split: Inverter
FM..AH

FM27AH t/m FM57AH


Display
code

Title

Cause of error

28

Inverter DC link high


voltage error

Inv PCB DC link voltage


supplied over 420V

4. Trouble Shooting
Check point & Normal condition

1. Input voltage abnormal (L~N)


2. ODU inverter PCB damage(DC Link voltage
sensing part)

Error Diagnosis and Countermeasure Flow Chart


No
Is input voltage normal ?

Check L~N Voltage is 220V15%

Yes
Is Inverter PCB assembly
Power connection normal?

No

Check connection from terminal block to


Inverter PCB assembly CN(L), CN(N)

Yes
No
Is Inverter PCB Normal?

Replace inverter PCB assembly

Recheck power and installation


condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 87 -

LGE Internal Use Only

67

FM27AH t/m FM57AH


4. Trouble Shooting

Multi-split: Inverter
FM..AH

Check Point
1. Check the CN_(L),CN_(N) Connection condition at the Inverter PCB.(Refer to outdoor wiring diagram)
2. Check the DC Link voltage at not operating(280V )
3. Check the DC Link voltage at Comp operating(340V )
4. Check DC Link Sensing Signal : 2.4~2.8V (Refer the Picture)

< Input Power Source Check Point >


27/30/40k

Vdc
< Main PCB>

Vdc

<DC_LINK Sensing Check Point>

<DC Link Voltage Check Point>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 88 -

LGE Internal Use Only

68

Multi-split: Inverter
FM..AH

FM27AH t/m FM57AH

4. Trouble Shooting

48/56k
Vdc

N
GND

< Inverter PCB>

<DC Link Voltage Check Point>

<Connection Check Point>

Vdc

DC_LINK
GND

<DC_LINK Sensing Check Point>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 89 -

LGE Internal Use Only

69

Multi-split: Inverter
FM..AH

4. Trouble Shooting
Display
code

29

Title

Inverter compressor over


current

Cause of error

Check point & Normal condition

1. Overload operation
(Pipe clogging/Covering/EEV defect/Ref. overcharge)
Inverter compressor input
2. Compressor damage(Insulation damage/Motor
current is over 30A
damage)
3. Input voltage low
4. ODU inverter PCB assembly damage

Error Diagnosis and Countermeasure Flow Chart


Is installation
condition normal?

No

Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?

No

1. Check Pipe clogging/distortion


2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
(0.188 7%)
2. Check insulation resistance between compressor
terminal and pipe (over 50M )
Replace compressor if abnormality found

Yes
Is compressor
Wire connection
condition normal?

No

1. Check inverter PCB assembly U,V,W connector


connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
Reassemble if abnormality found

Yes

Is input voltage normal?

No

Check
L~N phase is 220V 15%
Check connection condition and wiring if power is
abnormal

No

Check inverter PCB assembly IPM normality


Replace inverter PCB assembly

Yes

Is inverter PCB assembly


normal?

Yes
Recheck power and installation condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 90 -

LGE Internal Use Only

70

Multi-split: Inverter
FM..AH

4. Trouble Shooting
Display
code

Title

32

D-pipe (Inverter)
temp. high
(105C )

33

D-pipe (Constant)
temp. high
(105C )

Cause of error

Check point & Normal condition

Discharge sensor
(Inverter) temp. high

Check the discharge pipe sensor for INV.


Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.

Discharge sensor
(Cons.) temp. high

Check the discharge pipe sensor for Cons.


Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.

D-Pipe temp.
Toff(105) C
T2(95) C
T1(90) C

COMP Frequency
Normal
(Hz)
LEV Openness
(Pulse)

Normal

Normal

OFF

Normal

OFF Control

Check Point
CH 32

CH 33

1. Check the install condition for over load.

1. Check the install condition for over load.

2. Check the SVC V/V open.

2. Check the SVC V/V open.

3. Check the leakage of refrigerant.

3. Check the leakage of refrigerant.


4. Check the constant compressor. (same with CH21)

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 68 -

LGE Internal Use Only

71

Multi-split: Inverter
FM..AH
Display
code

Title

39

Transmission Error
Between (PFC Micom
INV Micom)

Cause of error

4. Trouble Shooting
Check point & Normal condition

1. Micom defect/Circuit defect


2. Different Micom S/W Version
3. ODU inverter PCB assembly damage

Communication Error
Between PFC Micom
and INV Micom.

Error Diagnosis and Countermeasure Flow Chart

Is PFC Micom & INV Micom


S/W Program normal?

No

Upgrade Micom Program

Yes

Is Inverter PCB assembly normal?

No

Replace inverter PCB assembly

Yes

Recheck power and installation condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 115 -

LGE Internal Use Only

72

Multi-split: Inverter
FM..AH

FM15AH t/m FM25AH


4. Trouble Shooting
Display
code

40

Title

C/T
Sensor Error

Cause of error

Check point & Normal condition


Malfunction of current detection circuit.
(Open / Short)
The voltage of "C01N" Is 4.0Vdc(25A) .
Check CT Sensor output voltage : 2.5Vdc
5%

Initial current error

Error Diagnosis and Countermeasure Flow Chart


Is CT Sensor Output is right?

No

If the CT Sensor output is not 2.5Vdc5%


Replace the Inverter PCB

No

Check the input voltage source


(Is nomal the offset of R-N,T-N voltage)

Yes

Is input voltage normal?


Yes
Recheck the Inverter PCB and
installation condition

Tester

CT Sensor Output
(at the INVERTER PCB)

GND

COMP CURRENT
U,V ,W
U,V,W
<INVERTER PCB>

INPUT
VOL AGE INV
VOLTAGE
<INPUT VOLTAGE Check Point>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 116 -

LGE Internal Use Only

73

Multi-split: Inverter
FM..AH

FM27AH t/m FM57AH


Display
code

Title

C/T
Sensor Error

40

4. Trouble Shooting

Cause of error

Check point & Normal condition

Initial current error

Malfunction of current detection circuit.


(Open / Short)
Check CT Sensor output voltage :
2.5Vdc 5%

Error Diagnosis and Countermeasure Flow Chart

Is input voltage normal ?

No

Check L~N Voltage is 220V15%

Yes
Is Inverter PCB Normal?

No

Replace inverter PCB assembly

Yes
Recheck power and
installation condition

Check Point
1. Check the Input Voltage (LN 220V10%)
2. Check Input Voltage Sensor output voltage (2.5Vdc10%)

< Input Power Source Check Point >

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 91 -

LGE Internal Use Only

74

4. Trouble Shooting

Multi-split: Inverter
FM..AH

FM27AH t/m FM41AH

Vdc

1
2
3

< Inverter PCB>

< CT Sensing Check Point >

FM49AH t/m FM57AH

Vdc

INPUT(CT)
GND

< CT Sensing Check Point >

< Inverter PCB>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 92 -

LGE Internal Use Only

75

Multi-split: Inverter
FM..AH

4. Trouble Shooting

Display
code

Title

41

D-pipe sensor (Inverter)

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 200K / at 25C (Unplugged)


Normal voltage : 4.5Vdc / at 25C (plugged)

44

Air sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 10K / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

45

Condenser Pipe sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 5K / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

46

Suction Pipe sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 5K / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

47

D-pipe sensor (Constant)

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 200K / at 25C (Unplugged)


Normal voltage : 4.5Vdc / at 25C (plugged)

65

Heat sink sensor

Open / Short
Soldered poorly
Internal circuit error

Normal resistor : 10K / at 25C (Unplugged)


Normal voltage : 2.5Vdc / at 25C (plugged)

Cause of error

Check point & Normal condition

Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance of the sensor is 0 k or , then sensor is abnormal.

If the voltage of the sensor is 0 V or 5Vdc, then sensor is abnormal.

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 69 -

LGE Internal Use Only

76

Multi-split: Inverter
FM..AH

FM15AH t/m FM25AH


4. Trouble Shooting
Display
code

Title

51

Over capacity

60

EEPROM
Check sum

Cause of error

Check point & Normal condition

Over capacity
Combination

Check the indoor unit capacity.


Check the combination table.

Check sum error

Check the PCB ASM P/No.


Check the poor soldering.

Model

Gross max. capacity

A2UW146FA3

21k

Max. single indoor unit capacity

A2UW166FA0
A2UW166FA1

24k

12k

A3UW186FA0
A3UW216FA3
A4UW246FA3

33k

18k

Check Point
CH 51

CH 60

1. Check the indoor unit capacity.

1. Check the insertion condition of EEPROM.


2. Check the poor soldering

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 70 -

LGE Internal Use Only

77

Multi-split: Inverter
FM..AH

FM41 t/m FM57AH


4. Trouble Shooting
Display
code

Title

51

Over capacity

Over capacity

Check the indoor unit capacity.


Check the combination table.

60

Over capacity

Check sum error

Check the PCB ASM P/No.


Check the poor soldering.

Cause of error

Model

Gross Max. Capacity[Btu/h]

A7UW428FA3

54k

A8UW488FA3

62k

A9UW548FA3

73k

Check point & Normal condition

Max. Single Indoor Unit Capacity[Btu/h]


24k

Check Point
CH 51

CH 60

1. Check the indoor unit capacity.

1. Check the insertion condition of EEPROM.


2. Check the poor soldering

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 118 -

LGE Internal Use Only

78

Multi-split: Inverter
FM..AH
Display
code

Title

Cause of error

52

Transmission error
between (Inverter PCB
Main PCB)

Main controller of Master


unit of Master unit cant
receive signal from
inverter controller

4. Trouble Shooting
Check point & Normal condition

1. Power cable or transmission cable is not


connected
2. Defect of outdoor Main fuse/Noise Filter
3. Defect of outdoor Main / inverter PCB

Error diagnosis and countermeasure flow chart


Is transmission
LED (Yellow) of inverter
compressor
PCB on?

No

Is noise filter or fuse


normal?

No

Replace noise filter or fuse

Yes

Yes

Replace inverter compressor PCB

Is transmission cable
connected correctly?

No
Re-connect transmission cable

Yes

No
Is MAIN PCB normal?

Replace MAIN PCB

Yes

Replace inverter compressor PCB

Check Point
- Check the Transmission connector and LED (Main & Inverter)

48/56k

<Inverter PCB>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

<MAIN PCB>

- 93 -

LGE Internal Use Only

79

Multi-split: Inverter
FM..AH
Display
code

Title

54

3-phase wrong wiring


of main outdoor unit

Cause of error

4. Trouble Shooting
Check point & Normal condition

3-phase wrong wiring of


outdoor unit (Reverse
Phase /omission of
phase)

Abnormal Main PCB


No connection of CN_Phase
Changed R, S, T connection order

Error Diagnosis and Countermeasure Flow Chart


No

Is PCB connection Normal?


Yes

No

Is input voltage normal ?


Yes

1. Check the Connection condition of PCBs


1) Input &Output (R,S,T,N) wire Connection of Noise Filter.
2) Check reverse connecting and non connecting for
CN-L1(R), CN-L2(S), CN-L3(T) of the Inverter PCB
3) Check the CN-AC-220V Connector of the Inverter PCB
and T-N connector of the Noise Filter
2. Check the connection or damage of power source fuses.

R~S/S~T/T~R phase voltage is 380V 10%


R~N/S~N/T~N phase voltage is 220V 10%
Check connection condition and wiring if power is abnormal.

Recheck power and installation condition

T-N
R

Fuse

R S T

S T

<Terminal Block&Fuse Check>


<Noise Filter Connection Check>
CN-L3(T) CN-L1(R)
CN-AC-220V

CN-L2(S)

<INVERTER PCB Connection Check>


Copyright 2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes

- 119 -

LGE Internal Use Only

80

FM27AH t/m FM57AH


4. Trouble Shooting
Display
code

60

Multi-split: Inverter
FM..AH

Title

Cause of error

Check point & Normal condition


1. EEPROM contact defect/wrong insertion
2. Different EEPROM Version
3. ODU Inverter & Main PCB assembly damage

Inverter PCB & Main


EEPROM Access error
EEPROM check sum error and Check SUM error

Error Diagnosis and Countermeasure Flow Chart

Is EEPROM insertion normal?

No

1.Check EEPROM insert direction/connection condition


2.Check EEPROM Check SUM
Replace if abnormality found

Yes

Is inverter PCB assembly normal?

No

Replace inverter PCB assembly

Yes

MAIN PCB assembly normal?

No

Replace MAIN PCB assembly

Yes
Recheck power and installation condition

Check Point
- Check the EEPROM Check sum & Direction

27/30/40k

<EEPROM Direction Check Point>

<MAIN PCB>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 94 -

LGE Internal Use Only

81

Multi-split: Inverter
FM..AH

4. Trouble Shooting

FM49AH t/m FM57AH

<MAIN PCB>

<Inverter PCB>

<EEPROM Direction Check Point>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 95 -

LGE Internal Use Only

82

Multi-split: Inverter
FM..AH

4. Trouble Shooting
Display
code

Title

Cause of error

61

Condenser pipe sensor


temp. high

Condenser pipe sensor


detected high
temp.(65C)

62

Heat sink sensor


temp. high

Check point & Normal condition

Check the load condition.


Check the sensor of Condenser pipe sensor.

Heat sink sensor detect- Check the Heat sink sensor (10k 10% at 25C)
ed high temp.(85C)
Check that outdoor fan is driving rightly

Gd`sRhmj
Snee

8/C

S1

74C

S0

7/C

ZGy\

Gy
Cnvm

Gy
Cnvm

NEE

Gy
Cnvm

Comp frequecy control accoding to heatsink temp.

Comp frequency control according to heat sink temp.


Is normal heatsink sensor
connecting ?

No

Connect the heatsink sensor right

Yes
Is normal heatsink sensor ?
(10k 10% at 25C)

No

Replace the heatsink sensor

Yes

Is normal Inverter PCB ?

No

Replace the heatsink sensor

Yes
Recheck power and
installation condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 120 -

LGE Internal Use Only

83

4. Trouble Shooting
Display
code

65

Multi-split: Inverter
FM..AH

Title

Heatsink High error

Cause of error

Inverter PCB heatsink


sensor is open or short

Check point & Normal condition


1. ODU fan locking
2. Heatsink assembly of INV PCB assemble
condition abnormal
3. Defect of temperature sensing circuit part defect
of INV PCB

Error Diagnosis and Countermeasure Flow Chart

Is installation
condition normal ?

No

1. Check fan locking


2. Check covering of heat exchanger
3. Check distance between ODU and obstacles
4. Check pipe distortion and abnormality
5. Check service valve is opened
Eliminate causes for abnormal condition

Yes

Is assemble condition
of INV PCB heatsink normal ?

No

Check assemble condition between INV PCB heatsink and


PFC & IPM module
Reassemble if abnormality found

Yes

Is PCB temperature
sensing part normal ?

No

Check resistance between NO.19 pin and NO.20 pin


of PFC module
Check resistance between NO.24 pin and NO.25 pin
of PFC module
7K 10%(at 25C)
Replace PCB if abnormality found

Check Point
1. Check resistance between No.19 pin and NO.20 pin of PCB PFC module
2. Check resistance between No.24 pin and NO.25 pin of PCB PFC module - only 48/56k
3. Resistance value should be in 7k 10%.(at 25C).
4. Check the PFC Module No.19, 20 and IPM Module No.24, 25 pin soldering condition.

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 98 -

LGE Internal Use Only

84

Multi-split: Inverter
FM..AH

4. Trouble Shooting

FM27AH t/m FM40AH

PFCM :
Measuring resistance
between No.19,20 pin

FM49AH t/m FM57AH

PFCM :
Measuring resistance
between No.19,20 pin

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 99 -

IPM :
Measuring resistance
between No.24,25 pin

LGE Internal Use Only

85

Multi-split: Inverter
FM..AH

FM15AH t/m FM25AH

4. Trouble Shooting

Display
code

Title

Cause of error

Check point & Normal condition

67

Outdoor fan
lock

Outdoor fan is not operating

Check the fan condition.


Check the fan connector
Check the fan control part of the INVERTER PCB

Error Diagnosis and Countermeasure Flow Chart


CH67(Outdoor fan lock) occurrence

Is fan connector condition right ?

No

Do right fan connector condition

Yes

No

Is Fan motor nomal?

Change abnomal motor

Yes
Replace inverter PCB assembly

<INVERTER PCB connection>

<fan motor middle connection>

<FAN Motor Connection check>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 121 -

LGE Internal Use Only

86

FM27AH t/m FM57AH


4. Trouble Shooting
Display
code

67

Multi-split: Inverter
FM..AH

Title

Fan Lock Error

Cause of error

Check point & Normal condition

1. ODU fan locking


Fan RPM is 10RPM or
2. Heatsink assembly of INV PCB assemble condiless for 5 sec. when ODU
tion abnormal
fan starts or 40 RPM or
3. Defect of temperature sensing circuit part defect
less after fan starting.
of INV PCB

Error Diagnosis and Countermeasure Flow Chart


Is ODU Fan Motor Assemble
condition normal?

No

Check ODU Fan Motor assemble condition and fan locking


Reassemble or replace if abnormality found

No

1. Set the multi tester to diode mode.


2. Check voltage between 1pin and 4pin of Fan Motor
(10.2V)
3. Replace Inverter PCB if abnormality found.

Yes

Is ODU Fan Motor normal?

Yes

Is wire connection of
ODU Fan Motor wire normal?

No

Check wiring between OUD fan motor and Inverter PCB


( Check if Hall Senor and Motor output terminal color is
matched)
Reassemble if abnormality found

Yes

Is Inverter PCB assembly normal?

No

Replace Inverter PCB assembly

Yes
Recheck power and installation condition

Check Point
1. Check voltage between 1pin and 4pin of Fan Mortor connector (Tester diode mode)
2. Voltage vaule should be in 1V 0.2V.

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 100 -

LGE Internal Use Only

87

Multi-split: Inverter
FM..AH

4. Trouble Shooting

FM27AH t/m FM41AH


Check voltage betwen
1pin and 4pin of fan motor

Fan motor
connector
Tester

<Main PCB>

FM49AH t/m FM57AH

<Inverter PCB>

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 101 -

LGE Internal Use Only

88

Multi-split: Inverter
FM..AH

4. Trouble Shooting
Display
code

73

Title

AC input instant over current error


(Matter of software)

Cause of error

Check point & Normal condition

Inverter PCB input power


current is over 48A(peak)
for 2ms

1. Overload operation (Pipe clogging/Covering/EEV


defect/Ref.overcharge)
2. Compressor damage
(Insulation damage/Motor damage)
3. Input voltage abnormal (L, N)
4. Power line assemble condition abnormal
5. Inverter PCB assembly damage
(input current sensing part)

Error Diagnosis and Countermeasure Flow Chart


Is installation
condition normal?

No

Yes

1.Check Pipe clogging/distortion


2.Check Covering (Indoor/Outdoor Unit)
3.Check EEV connector assemble condition/normal operation
4.Check refrigerant pressure
Reassemble or manage if abnormality found

No

Check
L~N phase voltage is 220V 10%
Check connection condition and wiring if power is abnormal

No

1.Check L,N connection condition


2.Check wire disconnection and wiring
Reassemble if abnormality found

No

1.Check inverter PCB assembly U,V,W connector connection condition


2.Check wire disconnection and wiring
3.Check compressor terminal connection condition(bad contact)
Reassemble if abnormality found

Is input voltage normal?

Yes

Is AC input Wire connection


condition normal?
Yes

Is compressor
Wire connection
condition normal?
Yes

Is inverter PCB assembly


normal?

No
Check inverter PCB assembly IPM normality
Replace inverter PCB assembly

Yes
Recheck power and
installation condition

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 102 -

LGE Internal Use Only

89

Multi-split: Inverter
FM..AH

4. Trouble Shooting

27/30/40k

< Noise Filter wiring Check Point >

N
L

< Main PCB wiring Check Point >

< Input Power Source Check Point >

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

- 103 -

LGE Internal Use Only

90

Multi-split: Inverter
FM..AH

4. Trouble Shooting
48/56k

< Noise Filter wiring Check Point >

N
L

< Input Power Source Check Point >

Copyright 2007 LG Electronics. Inc. All right reserved.


Only for training and service purposes

< Inverter PCB wiring Check Point >

- 104 -

LGE Internal Use Only

91

LG

Multi-split
Variabel (aan/uit)
M..AC/AH

92

Multi-split: Aan / Uit


M..AC / AH

Functions

Signal Receptor
Receives the signals from the remote controller.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
: Lights up during the system operation.
: Lights up during Sleep Mode Auto operation.
: Lights up during Timer operation.
: Lights up during Defrost Mode or Hot Start operation (Heat pump model only)
: Lights up during outdoor unit operation. (Cooling model only)

On/Off
Sleep Mode
Timer
Signal
receptor

Defrost Mode

OUT OUTDOOR UNIT


DOOR OPERATION

Operation indication lamps

Receives the signals from the remote controller.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
: Lights up during the system operation.
: Lights up during Sleep Mode Auto operation.
Timer
: Lights up during Timer operation.
Defrost Mode
: Lights up during Defrost Mode or Hot Start operation.(Heat pump model only)
Outdoor unit operation : Lights up during outdoor unit operation.(Cooling model only)
PLASMA
: Indicate PLASMA purifier operation.
On/Off

Sleep Mode

Operation indication lamps

Self-diagnosis Function
Error Indicator
The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
After error occurrence, if error is released, error LED is also released simultaneously.
To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
Having or not of error code is different from Model.
Error
Code

1
2
5

Error LED
(Indoor body operation LED)
5sec

(once)
3sec

3sec

3sec

(twice)
3sec

3sec
(5times)

(6times)
3sec
(7times)

Indoor air temperature thermistor


open/short.

Indoor air TH ass'y check

Indoor inlet pipe temperature thermistor


open/short.

Indoor inlet pipe TH ass'y


check

Poor communication

Communication line/circuit

Indoor outlet pipe temperature


thermistor open/shor

Indoor outlet pipe TH ass'y


check

Defferent Operation (Simultanueous


operation of cooling and heating.

Operate indoor units only


heating or cooling mode.

3sec

Indoor EEP ROM data (Art type only)

Replace main PCB DC ASM

Outdoor air temperature thermistor


open/short

Outdoor air TH ass'y check

Outdoor pipe themperature


thermistor open/short

Outdoor pipe TH ass'y check

Overload combination

Indoor unit combination check


(Refer to Max. capacity)

(9times)

3sec

3sec

3sec

45
3sec

51

SVC check point

3sec

44

Error contents

3sec

3sec

: ten digits
: one digits

93

Multi-split
Multi-split tot 2005
A2-C..
A3-C..
A2-H..
A3-H..
LM..

94

Multi-split: Aan / Uit voor 2005


(modellen, zie pag. 105)

Display Function
1. Heating Model

2. Cooling Model
Operation Indicator

Operation Indicator
Cooling, Soft Dry, Fan, Heating

Cooling, Soft Dry, Fan

Sleep Timer Indicator

Sleep Timer Indicator

Sleep Mode

Sleep Mode
Timer Indicator

Timer Indicator
Timer Mode

Timer Mode
Compressor on Indicator

Defrost Indicator

OUT
DOOR

Hot-start, Defrost

Self-diagnosis Function
Error Indicator
The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
After error occurrence, if error is released, error LED is also released simultaneously.
To operate again on the occurrence of error code 12, be sure to pull out power cord and then re-insert.
Having or not of error code is different from Model.
Error
Code

1
2

Error LED
(Indoor body operation LED)

Error contents

Indoor suction temperature


thermistor open/short.
Indoor TH ass'y check
Indoor pipe temperature
thermistor open/short.
Outdoor suction temperature
thermistor open/short.
Outdoor TH ass'y
Outdoor pipe temperature
check
thermistor open/short.
Abnormal operation of multi
product.
Resetting of remocon
(Simultanueous operation of operating mode
cooling and heating)

(once)
3sec
(twice)

3sec

3sec
(3times)

3sec

3sec

3
3sec
(5times)

3sec

Poor communication

5
(once)

3sec
(twice)

(once)

12
3sec

3sec

3sec

SVC check point

(twice)

Communication
line/circuit check

Primarily check
Misconnection of connecting refrigerant pressure
cables
Connecting pipe check
Connecting cable check

95

LG

RAC
Standaard wandunit (aan/uit & Inverter)
Art Cool Deluxe (aan/uit & Inverter) (hoge wand)
Art Cool Panel (aan/uit & Inverter)

96

RAC
Standaard wandunit (aan/uit)
Alle typen/uitvoeringen o.a:
LS-J.. / LS-K.. / LS-L..
S..ACL / S..AH / S..ACP / S..AHP
G..AH

ART COOL Panel / Deluxe (aan/uit)


LS-P.... ..
A09/12/18AH*
C07/09/12AH*

97

RAC: AAN / UIT


Standaard wandunit, Panel & Deluxe

Operation

Display Function
1. Heating Model

2. Cooling Model
Operation Indicator

Operation Indicator
Cooling, Soft Dry, Fan, Heating

Cooling, Soft Dry, Fan


Compressor on Indicator

Deicer Indicator

OUT
DOOR

Hot-start, Deice

Self-diagnosis Function
Error
Code
1

Error Display LED


(Indoor body operation LED)
(once)
3sec

3sec

3sec

Error contents
Indoor room temperature
thermistor open/short
Indoor pipe temperature
thermistor open/short.

SVC check point


Indoor Thermistor
assembly check

98

LG

RAC
Standaard wandunit Inverter
LS-N....
LS-Q....
LS-R....
S..AN
S..AW

99

RAC: Wandunit Inverter


LS-N/Q/R, S..AN & S..AW

Troubleshooting Guide

Self-diagnosis function
1. The malfunction indicator of indoor (see the operating LED of the INDOOR)
Error
Code

The cause of malfunction

Malfunction indicator

The operating state

Indoor TH. is short or open.

The operating LED will be blinking once.

Keep operating state.

Outdoor TH. is short or open.

The operating LED will be blinking twice.

Keep operating state.

Temp. of Heat sink is over 95C.


/Heat sink TH. is short or open.

The operating LED will be blinking 4 times.

Restart compressor when Heat sink


Temp is 85C below.

Comunication error (serial


comunication).

The operating LED will be blinking 5 times.

The operation is off(enable to restart


by remote controller).

DC peak error.

The operating LED will be blinking 6 times.

Compressor will be turned off immediately.


(not enable to restart by remote controller)

Running current is overloaded. (CT2)

The operating LED will be blinking 7 times.

Compressor will be turned off immediately.


(not enable to restart by remote controller)

Indoor fan lock error


(BLDC fan model)

The operating LED will be blinking 8 times.

The operation is off(enable to restart


by remote controller).

Outdoor fan lock error


(BLDC fan model)

The operating LED will be blinking 9 times.

The operation is off(enable to restart


by remote controller).

D-PIPE TH is short or open.

The operating LED will be blinking 10 times.

Compressor will be turned off immediately.


(restart compressor when D-PIPE TH. is
recovred)

10

Error code , cant be operated unless the power cord is removed.

2. The malfunction indicator of outdoor (see the LED01M on the outdoor PCB assy)
Error
Code

The cause of malfunction

Malfunction indicator

Indoor TH. is short or open.

The LED01M will be blinking


twice.

Keep operating state.

Temp. of Heat sink is over 95C,


or Heat sink TH. is shortor open.

The LED01M will be blinking 4


times.

Restart compressor when heat sink


Temp. is 85C below.

Comunication error (serial


comunication).

The LED01M will be blinking 5


times.

The operation is off(enable to restart


by remote controller).

DC peak error.

The LED01M will be blinking 6


times.

Compressor will be turned off immediately.


(not enable to restart by remote controller)

Running current is overloaded.

The LED01M will be blinking 7


times.

Compressor will be turned off immediately.


(not enable to restart by remote controller)

Outdoor fan lock error


(BLDC fan model)

The LED01M will be blinking 9


times.

The operation is off(enable to restart


by remote controller).

D-PIPE TH is short or open.

The LED01M will be blinking 10


times.

Compressor will be turned off immediately.


(restart compressor when D-PIPE TH. is
recovered)

10

The operating state

100

RAC
ART COOL Deluxe Inverter
C09AW*
C12AW*

101

RAC: ART COOL Inverter


C09AW* & C12AW*

Troubleshooting Guide

Self-diagnosis function
1. The malfunction indicator of indoor (see the operating LED of the INDOOR)
Error
Code

The cause of malfunction

Malfunction indicator

The operating state

Indoor TH. is short or open.

The operating LED will be blinking once.

Keep operating state.

Outdoor TH. is short or open.

The operating LED will be blinking twice.

Keep operating state.

Temp. of Heat sink is over 95C.


/Heat sink TH. is short or open.

The operating LED will be blinking 4 times.

Restart compressor when Heat sink


Temp is 85C below.

Comunication error (serial


comunication).

The operating LED will be blinking 5 times.

The operation is off(enable to restart


by remote controller).

DC peak error.

The operating LED will be blinking 6 times.

Compressor will be turned off immediately.


(not enable to restart by remote controller)

Running current is overloaded. (CT2)

The operating LED will be blinking 7 times.

Compressor will be turned off immediately.


(not enable to restart by remote controller)

Indoor fan lock error


(BLDC fan model)

The operating LED will be blinking 8 times.

The operation is off(enable to restart


by remote controller).

Outdoor fan lock error


(BLDC fan model)

The operating LED will be blinking 9 times.

The operation is off(enable to restart


by remote controller).

D-PIPE TH is short or open.

The operating LED will be blinking 10 times.

Compressor will be turned off immediately.


(restart compressor when D-PIPE TH. is
recovred)

10

Error code , cant be operated unless the power cord is removed.

2. The malfunction indicator of outdoor (see the LED01M on the outdoor PCB assy)
Error
Code

The cause of malfunction

Malfunction indicator

Indoor TH. is short or open.

The LED01M will be blinking


twice.

Keep operating state.

Temp. of Heat sink is over 95C,


or Heat sink TH. is shortor open.

The LED01M will be blinking 4


times.

Restart compressor when heat sink


Temp. is 85C below.

Comunication error (serial


comunication).

The LED01M will be blinking 5


times.

The operation is off(enable to restart


by remote controller).

DC peak error.

The LED01M will be blinking 6


times.

Compressor will be turned off immediately.


(not enable to restart by remote controller)

Running current is overloaded.

The LED01M will be blinking 7


times.

Compressor will be turned off immediately.


(not enable to restart by remote controller)

Outdoor fan lock error


(BLDC fan model)

The LED01M will be blinking 9


times.

The operation is off(enable to restart


by remote controller).

D-PIPE TH is short or open.

The LED01M will be blinking 10


times.

Compressor will be turned off immediately.


(restart compressor when D-PIPE TH. is
recovered)

10

The operating state

102

LG

RAC
ART COOL Deluxe Inverter
C18AW*
C24AW*

103

RAC: ART COOL Inverter


C18AW* & C24AW*

Troubleshooting Guide

Self-diagnosis function
1. The malfunction indicator of indoor (see the operating LED of the INDOOR)
Error
Code

The cause of malfunction

Malfunction indicator

The operating state

Indoor TH. is short or open.

The display show "C1"

Keep operating state.

Outdoor TH. is short or open.

The display show "C2"

Keep operating state.

Temp. of Heat sink is over 95C.


/Heat sink TH. is short or open.

The display show "C4"

Restart compressor when Heat sink


Temp is 85C below.

Comunication error (serial


comunication).

The display show "C5"

The operation is off(enable to restart


by remote controller).

DC peak error.

The display show "C6"

Compressor will be turned off immediately.


(not enable to restart by remote controller)

Running current is overloaded. (CT2)

The display show "C7"

Compressor will be turned off immediately.


(not enable to restart by remote controller)

Indoor fan lock error


(BLDC fan model)

The display show "C8"

The operation is off(enable to restart


by remote controller).

Outdoor fan lock error


(BLDC fan model)

The display show "C9"

The operation is off(enable to restart


by remote controller).

D-PIPE TH is short or open.

The display show "CA"

Compressor will be turned off immediately.


(restart compressor when D-PIPE TH. is
recovred)

10

Error code , cant be operated unless the power cord is removed.

2. The malfunction indicator of outdoor (see the LED01M on the outdoor PCB assy)
Error
Code

The cause of malfunction

Malfunction indicator

Indoor TH. is short or open.

The LED01M will be blinking


twice.

Keep operating state.

Temp. of Heat sink is over 95C,


or Heat sink TH. is shortor open.

The LED01M will be blinking 4


times.

Restart compressor when heat sink


Temp. is 85C below.

Comunication error (serial


comunication).

The LED01M will be blinking 5


times.

The operation is off(enable to restart


by remote controller).

DC peak error.

The LED01M will be blinking 6


times.

Compressor will be turned off immediately.


(not enable to restart by remote controller)

Running current is overloaded.

The LED01M will be blinking 7


times.

Compressor will be turned off immediately.


(not enable to restart by remote controller)

Outdoor fan lock error


(BLDC fan model)

The LED01M will be blinking 9


times.

The operation is off(enable to restart


by remote controller).

D-PIPE TH is short or open.

The LED01M will be blinking 10


times.

Compressor will be turned off immediately.


(restart compressor when D-PIPE TH. is
recovered)

10

The operating state

104

RAC
ART COOL Panel Inverter
A09AW
A12AW
A09AW1
A12AW1

105

RAC: ART COOL PANEL Inverter


A..AW & A..AW1

Troubleshooting Guide

Self diagnosis Function


Error
Code
1 time

Cause of Error

Error Indicator
1time

3 sec

1time

3 sec

1time

3 sec

1time

3 sec
2 times

2 times

2 times

2 times

3 sec

3 sec

3 sec

4 times

4 times

3 sec

3 sec

5times

5times

3 sec

3 sec

6times

6times

3 sec

3 sec
8times

8times

3 sec

9times

9times

3 sec

10 times 10 times

10

3 sec

1time

12

2times

1time

3 sec

1time

13

1time

4 times
3 sec

Outdoor Temp. sensor error


- Sensor open or short

ON

Heat Sink sensor error


- Sensor open or short
- Heat Sink temp is over 95

ON

OFF

DC Peak error

SHUT
DOWN

Over current error (CT2)

SHUT
DOWN

Indoor fan lock error


(BLDC fan model only)

Outdoor fan lock error


(BLDC fan model only)

OFF

D-Pipe TH. is short or open.

ON

Communication error

ON

1time

OFF

ON

3 times

PSC Error
- PSC Fault Error

ON

4 times

Comp Phase Current Error


(180 Driver Comp Control
Model Only)

ON

3 sec

3 times

EEPROM Error
- EEPROM Check sum Error

3 sec

1time

14

2times

Indoor
Operation

Indoor Temp. sensor error


- Sensor open or short

7times

7times

Display
Indoor Outdoor

106

RAC: ART COOL PANEL Inverter


A..AW & A..AW1

Troubleshooting Guide

Troubleshooting for error code


Error code

Description

Indoor TH. is short or


open

Check flow

Cause of error
Indoor TH. (sensor) is short or open
Indoor TH. (sensor) is not connected to the indoor pcb assembly
Damage or defect on the sensing circuit of indoor pcb assembly.
(R01H, R02H, R03H, R04H, C01H, C02H)

YES

Indoor TH. is connected to


Indoor pcb assembly ?

YES
Sensing circuit of indoor
pcb is right ?

Indoor TH. is right ?

No

No
Check Indoor TH.
- Measure resistance of TH.
(air : about 10k . at 25 C,
pipe : about 5k . at 25 C)

- Connect to CN-TH1 in
indoor pcb assembly

Error code

Description

Outdoor TH. is short or


open

Check flow
Outdoor TH. is connected to
outdoor pcb assembly ?
No

- Connect to CN-TH1 in
outdoor pcb assembly

No

- Check soldering state of


R01H ~ R04H, C01H, C02H

Cause of error
Outdoor TH. (sensor) is short or open
Outdoor TH. (sensor) is not connected to the outdoor pcb assembly
Damage or defect on the sensing circuit of outdoor pcb assembly.
(R03H~R06H, C02H, C03H)

YES

YES
Outdoor TH. is right ?
No
Check outdoor TH.
- Measure resistance of TH.
(air : about 10k . at 25 C,
pipe : about 5k . at 25 C)

Sensing circuit of outdoor


pcb is right ?
No

- Check soldering state of


R03H ~ R06H, C02H, C03H

107

Troubleshooting Guide

RAC: ART COOL PANEL Inverter


A..AW & A..AW1

9K / 12K
Description

Error code

Cause of error

Heat-sink Temp. is over


95C
Heat-sink TH.
is open or short

Check flow
Heat-sink TH is connected to
outdoor PCB assembly?
No

- Connect to CN-TH2 in
outdoor PCB assembly

Heat-sink TH. is damaged(short or open).


Heat-sink Temp. is over 95C
Damage or defect on the sensing circuit of outdoor pcb assembly.
(R01H, R02H, C01H)

YES

YES
Heat-sink TH. in INV-IC is
Right ?
No

Check heat-sink TH.


- Measure resistance of TH.
(about 10k . at 25 C)

Sensing circuit of outdoor


pcb is right ?
No

- Check soldering state of


R01H, R02H, C01H

108

RAC: ART COOL PANEL Inverter


A..AW & A..AW1
Description

Error code

Cause of error
Wrong or missing wiring between indoor and outdoor unit cable
Defect of communication components in indoor pcb assembly
Defect of communication components in outdoor pcb assembly
Defect of power supply components in outdoor pcb assembly
No ground connection in air conditioner unit
(affected by noise in power source)

Communication Error

Check flow

YES

No
Indoor
1(BR)
2(BL)
3(GN/YL)
4(RD)

YES
Is the voltage of T/Block
,
in outdoor about
AC 220/240V ?

Wiring connection
Is right ?

Is the voltage of GND & DC5V in


Outdoor pcb about DC 5V ?

No
Outdoor
1(BR)
2(BL)
3(GN/YL)
4(RD)

Troubleshooting Guide

No

Check power connector


Is not connected to the
T/Block in indoor unit.

YES

Check FUSE, NF01/02J, PTC,


Power Module, BD-01S in
Outdoor pcb assembly

YES
Communication circuit of indoor
& outdoor pcb Is right ?
No

Check IC01K, IC02K,D01K~D03K,


ZD01K~ZD03K, R01K~R10K,
C01K~C04K

Ground connection is installed ?


(power outlet or outdoor chassis)
No

Earth port

Install ground connection from outdoor


unit. (In case power outlet has no earth
port)

109

RAC: ART COOL PANEL Inverter


A..AW & A..AW1

Troubleshooting Guide
Error code

Cause of error

Description

DC Peak Error

Check flow

Supplied power is not normal


Comp Connector (CN-U,V,W) is disconnected or inserted to wrong
position
Compressor is damaged (coil short) replace compressor
Too much Refrigerant
Defect in outdoor pcb assembly replace pcb assembly

YES

Supplied voltage to
Outdoor pcb is about
AC 220/240V ?

YES
Is connector (CN-U,V,W)
connected to compressor and
inserted to pcb in right position ?

No

Refrigerant pressure is right ?

No

No

Check CN-U,V,W connector


(U : RD, V : BL, W : YL)

Check power source

YES

Check refrigerant pressure


and adjust.

YES
Inverter components in outdoor
right ?

Is the compressor right ?


No

No

Check resistance
Between U-V, V-W, U-W port.
Short / Open circuit
(Comp.motor coil error)
normal : 1 ~2 .
Between U,V,W and Body
normal : over10M .

* 9 K/12K Model
Check
Short of SPM3 pins (GND - P, U, V, W pin)
Direction of D01Z~D03Z, C08Z,10Z,12Z,16Z
Assembling state of R01P ~ R21P & IC01P
Assembling state of screw between INV-IC &
Heat-sink
DC 15V output of Power module.

U
.
V

pcb assembly are

* 18 K Model
Check
Short of SPM2 pins (GND P, U, V, W pin)
Direction of D01Z~D03Z, C08Z,10Z,12Z,16Z
Assembling state of R01P ~ R21P & IC01P
Assembling state of screw between INV-IC &
Heat-sink
DC 15V output of Power module.

110

RAC: ART COOL PANEL Inverter


A..AW & A..AW1
Error code

Description

Over current Error


(CT2)

Check flow

Cause of error
Supplied power is not normal
Indoor/outdoor fan is locked
Too much refrigerant
Defect in current sensing circuit in outdoor pcb assembly

YES

YES

Supplied voltage to
Outdoor pcb is about
AC 220/240V ?

Does indoor / outdoor fan work


normally ?

No

No
Check indoor / outdoor fan and
adjust.

Check power source

Troubleshooting Guide

Refrigerant pressure is right ?


No
Check refrigerant pressure
and adjust.

YES
Current sensing circuit is right ?
No
Check current sensing circuit.
- check CT is damaged in outdoor pcb
(output wire is disconnected to pin or not)
- BD01N is inserted in right position
(refer marking on pcb and component)
- Spec of R01N (1k. ), R02N (1.65k. ) is correct
- Direction of diode (D01N, D02N) is right

111

RAC: ART COOL PANEL Inverter


A..AW & A..AW1

Troubleshooting Guide
Error code

Description

Indoor fan is locked


(BLDC fan model only)

Check flow

Cause of error
Indoor fan is locked or separated
Fan connector is not connected to indoor pcb assembly
Defective in DC-fan driving circuit

YES

Indoor fan is rotating ? (1)

YES
Indoor fan is rotating ? (2)

No

DCfan driving circuit is right ?

No

Check indoor unit


- remove obstacles in
indoor unit
- fan assembled correctly.

Description

Outdoor fan is locked


(BLDC fan model only)

Outdoor fan is rotating ? (1)


No
Check outdoor unit
- remove obstacles in
outdoor unit

Check DC Fan Driving circuit


(Soldering state & Direction)
- R01F~R09F, C01F~C03F,
IC01F~IC03F, Q01F~Q02F, ZD01F

Check soldering state of


CN-Motor1 & assembling
state of DC Fan connector

Error code

Check flow

No

Cause of error
Outdoor fan is locked by an obstacle (ex : branch of tree, baretc)
Fan connector is not connected to outdoor pcb assembly
Defective in DC-fan driving circuit

YES

YES
Outdoor fan is rotating ? (2)
No
Check connector is not
connected to outdoor pcb
assembly (CN-FAN2)

DCfan driving circuit is right ?


No
Check DC Fan driving circuit
(Soldering state & Direction)
- R01F~R05F, C01F~C03F,
Q01F~Q04F, ZD01F

112

RAC: ART COOL PANEL Inverter


A..AW & A..AW1
Error code

10

Description

Cause of error

D-Pipe TH. is short or


open

Check flow
D_PIPE TH. is connected to
Outdoor pcb assembly ?
No

Connect to CN-D_PIPE
in outdoor pcb assembly

Troubleshooting Guide

D_pipe TH. is short or open


D_pipe TH. is not connected to the outdoor pcb assembly
Damage or defect on the sensing circuit of outdoor pcb assembly

YES

YES
D_PIPE TH. is right ?
No

Check D_PIPE TH.


- Measure resistance of TH.
(about 200k. at 25C.)

Sensing circuit of outdoor


pcb is right ?
No

- Check soldering state of


R07H, R08H, C04H

113