You are on page 1of 1

Saturday, September 19, 2015, 23:40:55

Electrode sizing report


Station Name

Untitled

Project
Study

Malha de Terra - SE Realeza Sul


Malha2

Parameters
Bus ID
LG Fault Current
Fault Duration
Ambient Temperature

Barramento 138 kV
7660 amps
0.5 secs
40 C

Output Results
Decrement Factor

1.01884

Conductor Sizing (Minimum required)


Conductivity
(%)

Material
Copper commercial hard-drawn

97

Tm
(C)
1084

Kf
7.06809

Area
(mm)
19.76

Nominal Size
2/0AWG

Rod Sizing (Minimum required)


Conductivity
(%)

Material
Copper_clad steel 20%

09/19/15 23:48:28

20

Tm
(C)
1084

Kf
14.6293

Diameter Nominal Size


(mm)
7.21622
1/2"

1/1

You might also like