You are on page 1of 6

TECHNICAL REPORT

TR-BTM-037015

TSR Number:
Customer Name
Customer Group
Contact Person
Address

PT. SMOE INDONESIA


MR. SADLI
KOMPLEK INDUSTRIAL
KABIL

End User

Job No
Make
Equipment Type
Model
Equipment S/N
Customer Unit No.
Location

STAMFORD
GD23-1331695
G13K531336
PT. SMOE (KABIL)
CUMMINS POWER
GENERATOR
-

Application/Use
Last Service

Email
Telephone
Fax

Job Open Date


DIS/ Delivery date
Failure Date
Engine Made
Engine Model
Engine SN
Hour meter
Status
Author

0813 6395 0010

CUMMINS
QSK23-G3
00326081
50.03- HR
Engine trouble
TANDI SURMARGI

Complaint

Engine cant run.


Have alarm shutdown in display engine.

Inspection Result

Check ploblem actual in panel engine.


Problem in fuel card (GCS) connection diode burnt.

correction

Check control GCS in panel generator.


Test calibration GCS. (GCS cant respon callibration)
Check harness engine and panel PCC. (Good condition)
Check fuse in connection harness engine and fuse base card. (Good condition)
Measure actual voltage input/output in panel PCC 24 vdc. (Good condition)
Check connection wiring diagram.
Check connector fuel card, base card and parraling card. (Good condition)
Check connection external charging. (Good condition)
Check condition diode in magnetic switch starter. (Good condition)
Engine photograph for reporting.

Suggestions

Change fuel card new.

Page 1 of 6

Acknowledged By,

Reported By,

( Danang Bayuaji K )

( TANDI S. )

Photo attachment :

Condition harnes engine.

Condition panel after renove GCS

Condition actual diode burnt

Page 2 of 6

Condition actual diode burnt

Condition battery 24

Check diode in connection

Page 3 of 6

Relay in cover GCS

Connector GCS

Data plate Engine

Data plate altenator

Page 4 of 6

Component in display board burnt

Charging external battery

Page 5 of 6

Page 6 of 6