The MiCOM ALSTOM P746 centralised numerical busbar protection provides complete protection for all
voltage levels up to extra voltage busbar configurations. Proven techniques and dynamic topology
processing algorithms offer a combination of security, speed and high sensitivity.
[With atypical operating time of 12 ms with changing topology of che busbar, which
HB/HS contact option, or 17 ms with can be displayed on any PC via the
standard contacts, the P746 protection is substation realtime dynamic monitoring
ane ofthe fastest in its class. Moreover, the toa
trips can be synchronous or sequential
Folly compatible with the IEC 61850-, The MICOM ALSTOM P746 differential
Courier, DNP3.0, Modbus and IEC103, busbar protection provides a centralised 2
protocols, the P746 is easily integrated into ‘box or 3-box architecture and is very simple
any substation system. The substation to use: It doesnot need to be heavy
replica processing algorithms ensure that engineered and supports easy operations
the P746 adapts to the dynamically and maintenance ofthe busbar.
Customer Benefits
+ Fast fault trip (typically 21-15ms and
arms)
+ Synchronous or sequential trip
+ Adapted to simple busbar configurations
IEC 61850-8.1 compliant
+ Can operate with differen types of CT
+ Programmable function keys, hotkeys
and tr-colour LEDsNumerical busbar protection | PROTECTION
Application
‘The MiCOM ALSTOM Pras centralised
numerical usbar protection has been
designed to protect a wide range of busbar
«configurations:
‘box made - Pras
+ 3-box mode ~ one P746 per phase
(Inthe 3-box mode, the units are totaly
independent and not linked to each other.)
‘The MICOM ALSTOM Pras can
‘accommodate:
Up to 2 zones plus check zone for 3 or
'3-box mode and up to 4 zones fer dual 2 or
+3-box modes:
-1.VI, up to 6 CTs, 6 breakers and 12
Isolators withthe 1-box mod solution
+ 2VTs, upto 12 CTs, 12 breakers and 24
‘solators withthe dual 2-box mode
solution
+ 2VIs, upto 18 CTs, 18 breakers and 36
Isolators withthe 3-box mode solution
+2VT5, up to 36 CTs, 36 breakers and 72
isolators withthe dual 3-box mode
solution
‘The MICOM ALSTOM P7A6 is associated
with each CT location, usually one per
incomer/feeder and one or two for each bus
coupler /ous section. The P46 acquires the
analogue signals from the associated CT and
the binary signals from the auxiliary
contacts ofthe circuit breakers and
isolators.
‘The P746 also incorporates the main circuit
breaker fllure logic together with addtional
protection Functions (dead zone,
overcurrent, etc.) The P746, particularly
useful in double busbar applications, allows
{high numberof opto inputs (yp to 40) and
relay outpts (upto 32), function keys and
offers ethernet or a second rear port board
option
Topology scheme examples
Cost optimised to suit simple busbar configurationsNeco Ba
eed
ANSI ec61850 new Pras.
e7aB/P ___PhsPOIF Phase segregated biased current differential high speed busbar protection
e7cz/P_GaPPOIF (Check zone segregated biased phase current diferential high speed
busbar protection
S0/si/P __OcpPTOC Phase overcurrent protection (2 stages)
50/52 /N _EfmPTOC Earth overcurrent protection (2 stages)
SOST/P __DzpPhsPTOC Dead zone phase protection (short zone between CT and open CBs)
os Current transformer supervision
vis Voltage transformer supenision
508F RBRF Breaker failure protection (LBB)
ISL isolator discrepancy alarm
Opt6cIO Digital inputs Tete
RWVEGIO Output relays ewe
Front communications por (RS232)
Rear coramurications port (Kbus/EIA(RS)4a5)
Rear communications port (ethernet) * Option
Time synchronisation port (RIG-B)* Option |
FakGGIO Function keys 30
TedGGI0 Programmable t-colour LEDS i
* Refer datasheet for model selection
Management functions Functional overview
In addition tothe protection and control
elements, the P746 provides a wide range of
measurement, monitoring, post fault
“analysis and self diagnostic features:
+ Tip circuit supervision (using PSL)
+ On-line measurement
+ Plant status monitoring
« balternative settings groups
- Programmable logic (PSL)
+ Sequence of event recording (SOE)
+ Comprehensive faut records
Comprehensive disturbance recording
(waveform capture)
+ User configurable function keys & hotkeys
+ User configurable tr-colour LEDs
+ Local and remote communications ports
+ Time synchronisation
+ Fully customisable menu texts
+ Muitlevl password protection
Test facilities
+ Power-up diagnostics and continuous se
monitoring of relay
+ User friendly settings, analysis and
monitoring softwareNumerical busbar protection | PROTECTION
‘The primary protection element ofthe P74
isthe phase segregated biased current
differemtal protection. The technique is
based on the numerical application of
Kirchof's Law for the selective detection
and high-speed isolation of a faulty section
‘ofthe busbar. To ensure the adaptability of
the relay to any type of busbar
configuration, the P46 is but with 2
riversal topology processing algorithm.
This algorithm determines the optimum
tripping zone based on the current status of
the plant isolators or/and circuit breakers.
‘The P746 employs biased differential
algorithms where te differential curtent is
‘compared with a bias current. This
characteristic ensures the stability of the
protection for external faults, even with
differing CT tolerance and errors which
ould lead to spurious operation.
Tolincrease the security ofthe differential
protection, the based differential element is
supervised by a biased global check zone
clement. This ensures stability even under
‘erroneous status ofthe aviary contact of
Plant isolators and circuit breakers.
‘The MiCOM ALSTOM P46 also employs CT
‘supervision and an innovative external fault
detection algorithm - the current phase
‘comparison. Ths ensures stably when CTs
become saturated. This technique is heavy
CT saturation proof and stl ips on
‘evolving to an internal fault.
Multiple tripping criteria
‘The P76 maintains the highest level of
stability under al conditions, including
hardware failure and incoherent signals
applied from external plat or generated by
the power system. Any vipping order must
therefore be made conditional tothe
Simultaneous occurrence of atleast five
criteria:
(Magnitude criteria
Confirmation of two simultaneous
‘thresholds per zone:
+ Exceeding te bias slope characteristic (k2)
« Exceeding differential operating current
threshold (1022)
f(t)
loca
to?
loot
eneeccet arnt yoy + he
nergaret Hafan (tf [2]
Universal online topolog
(Check zone supervision
‘The zone element(s) are only permitted to
trip f the order is confirmed by the check
zone element:
+ Exceeding the bias slope characteristic
(Kez)
+ Exceeding differential operating current
threshold (1OCZ>2)
Current phase comparison criteria,
Optional voltage criteria
- Undervoltage Ue OR, Vie OR
- Negative sequence overvltage V2> OR
+ Tero sequence avervoltage 3V0>
eee: Hua Babe leo BeeNumerical busbar protection | PROTECTION
Synchronus or sequential tripping
‘The P746 allows delaying every or each
‘ringing contact. This is highly
recommended for highspeed disconnection
‘ofthe bar from the grid and delayed trip of
the generation feeders.
Dead zone or blind spot protection
‘The curent transformers ar the open
isolators surrounding the busbars define the
limits of the main zones. When a feeder
isolators opened, @ dead zone or blind spot
is created tothe associated CT. The P746
detect tis condition automatically and
provides protection for this zone. One stage
of definite time delayed overcurrent and
‘earth faut protection i also provided.
Continuous supervision of current
circuits
‘The P74s detects any abnormality in the
current circuit by continuously monitoring it
Under normal operating conditions the
differential current willbe negligible. An
anomaly is detected by a threshold, D>,
which can be set to alarm from 10.8
primary.
Continuous supervision of current
transformers,
Curent transformer supervision is provided
to detect loss of phase CT input signals.
Using the “differential CTS" feature
(patented), the relay performs an inteligent
‘comparison of the negative sequence
‘current imbalance at all T terminals to
determine which, if any, CTs have failed.
This comparison detects all CT shorts, open
Greuits and wiring disconnections without
‘an inherent time delay. Operation ofthe
ifferetial protection can be blocked during
the failure, or alternatively, temporarily
desenstsed to avoid an unwanted trip. The
CTS thus assures real-time stability of
ifferental elements.
Differential current settings Circuit breaker failure protection
‘When switching operations are carried out. (LBB)
inthe substation, incorrect topology replicas The P746 offers an in-uilt integrated
may occur. In this case acfferental current solution for breaker failure protection
‘appears. The diferential elements of the In general the breaker failure protection is
MiCOM ALSTOM P7«6 are allowed to ‘executed on a per phase basis which
‘operate only ifthe ferential current involves the possibilty of receiving tripping
reaches a threshold ID>2, whichis normally orders ona per pole bass, The MICOM
set above the highest load current when no ALSTOM P76 busbar protection can also
voltage criteria is used.
‘work in co-ordination with external breaker
failure protection relays. In this
Phase overcurrent and earth fault «configuration, the receipt of an external
protection breaker failure command results in the
‘Two independent stages of phase tripping of all the adjacent circuit breakers,
‘overcurrents and earth fault protection are via the topological recognition system
provided in the MICOM ALSTOM P76, knowing wich breaker is connected to
These elements provide additional which zone,
protection for the individual circuits. The
‘two stages can be programmed as: Current transformer mixing correction
‘The MiCOM ALSTOM Pras can correct @
«Fits stage can be programmed as definite ‘mix between current transformer ratios over
time (BT) delay or one ofthe nine inverse _@ Very wide range (upto 20). Is associated
‘ime (IDMT) curves (IEC/ UK and user interface provides a range between 2 A
IEEE/ US), ‘and 30 000 A primary. Since the current
‘transformer ratings ina substation
«Second stage can only be programmed as __—_-may be of mixed ratios, the P746 uses a
efnite time, virtual CT rato equa ta setable reference
current/, irrespective of the feeder section,
concerned
Isolator closed Isolator closed
CB open
Dead Zone
746
Feeders not connected
Dead zone ratNumerical busbar protection | PROTECTION
Isolation and maintenance operating Programmable scheme logic Remote HMI
mode Powerful programmable leg (PSL) allows The realtime remete HMI software alows
the user to customise the protection and the user to monitor the position of CBs and
For ease of operation or maintenance of the
busbar protection sytem, the P746 can «control functions. Its also usedto program isolators in the busbar scheme, as well as,
receive specie commands designed to the functionality ofthe optcaly slated currents alarms, et.
«allow system testing or other interventions inputs, relay outputs and tr-colour LED
without any danger of unwanted tiping indications. The programmable logic Measurement and recording facilities
Inthe MiCOM ALSTOM P746, centralised comprises gate logic and general purpose The 9746 is capable of measuring and
‘command to isolate the busbarscan be timers. The gate ogicincludes OR, AND and sorng the values associated with a ful. ll
selectively applied per zone: majority gate functions, with the ably to the event, fault records and disturbance
invert the inputs and outputs end provide records are time tagged ta ms using an
+ Differential protection (8788) and circuit _‘feedback The programmable logic is internal realtime clock. An optional
breaker failure protection (S0BF) blocked «configured using the graphical MiCOM IRIG-8 ports aso provided for accurate
~The additional loca protection functions ALSTOM St PC based support software. time synchronisation. A lithium battery
(64, 51N, et.) remain operational provides aback up forthe rea time clock
Plant status and all record in the event of supply failure
‘Checks and monitoring ofthe plat status
‘an be made and an alarm raised for any
discrepancy condition between the open and
closed auxliary contacts of the isolators and
circuit breakers
=z
=EEE
— vee
eam oe
Programmable scheme lgic eit
(wicom atsToM s1)
Remote HMINumerical busbar protection | PROTECTION
Measurement
‘The measurements provided, which may be
viewed in primary or secondary values, can
be accessed via the back it liquid crystal
cisplay. They are also accessible via the
‘communications ports. The following
instantaneous parameters can be viewed:
“Phase current magnitude i and/or 1B
and/or iC
+ Phase curent angle i and/or 1B and/or IC
+ Voltage magnitude and angle
+ Frequency
= Differential curentIdff/ phase / zone
«Bias current bias / phase / zone
“Check zane If / phase
+ Check zone Ibias / phase
Event recorder
Up to 512 time tagged event records are
stored in battery backed memory and can be
‘extracted va the communications port or be
viewed on the front panel display.
Fault recorder
Records ofthe last five faults are stored in
the battery backed memory. Each fault
record includes:
+ Faulted phase
+ Indication ofthe faulty zone
«Date and time
+ Active setting group
+ Fault duration|
+ Cutrents, frequency and voltage
Distrubance recorder
‘The P746 has an independent disturbance
recording facility. Itcan record 18 analogue
‘and 32 digital channels in addition to 2 time
channel
Specific analogue channels:
+ VAN, VBN and VEN
“1A, IC for each CT in 2-box mode
Ix; to bee (cis A oF B ar C) in 3-box made
Disturbance record viewed in Sa
‘Maximum duration of one record and
numberof record: upto 10.5 sper record
and minimum of 50 records, 2.5 s (memory
of 755).
Disturbance records can be extracted from
the relay via the remote communications
and saved in the COMTRADE format. These
records may be examined using $1 or any
other standard COMTRADE viewer.
Fast, sensitive & secure - P746 - the centralised solution for busbar protectionLocal and remote communications
Two communications ports are available as
standard: a rear port providing remote
‘communications and a front port providing
local communications. Asan option, an
«ethernet board can be added in the P74
‘and P743s to use the IEC61850-8.1
protocol
‘The front RS232 pot is designed for use
withthe MiCOM ALSTOM Sa, which fully
‘supports functions within te relay by
proving the ability to program the settings
offline, configure the programmable
scheme logic, extract and view event,
disturbance and fault records, view the
measurement information dynamically and
perform control functions (using the Courier
protocol),
‘The default remote communications
protocol is Courier / RS 485 or bus and
‘can be converted to IEC 60870-5-103. An
‘optional second rear Courier
‘communications port is available, which
may be configured as RS232, RS48S or K
Bus, EC 61850 is available when the
‘optional ethernet port is ordered. IEC 61850
offers high-speed data exchange, per-to
peer communications, reporting,
disturbance record extraction and time
‘smchronsation.
‘Alstom Grid Worldwide Contact Centre
‘wow grd.alstom.com/contactcentre/
Tel: +44 (0) 2785 250070,
wow.gridalstom.com
Nee aero)
e track record
Low impedance biased differential busbar protection, MBCZ, launched in 2988 and over
7000 cubicles sol
since its launch in 1992,
‘Over 200 DIFB, medium impedance biased diferetial busbar protection schemes delivered
‘Medium impedance biased differential busbar protection with near current combination,
DIFB Cl, launched in 1996, Over 70 cubicles delivered.
Diagnostics
‘Automatic tests performed, including power
‘on diagnostics and continuous sf
‘monitoring, ensure a high degree of
reliability, The results ofthe self-test
functions are stored in battery backed
memory. Test features avaiable va the user
interface provide examination of input
‘quantities and states ofthe digital inputs
and relay autputs. A local monitor port
provides digital outputs selected from 2
presrived list of signals, including the
status of protection elements
GRID
Since the launch ofthe P740, over 700 systems have been delivered
Hardware
The MICOM ALSTOM P746 includes:
=A backlit quid crystal display
LEDs: 18 tr-colour
+ Function keys
+ Hotkeys
+ RS232 (front port) & RSHES /K:bus (rear
port)
Optional ethernet rear communications
board or
+ Optional second rear communications
board
+ Optional 1R\G-8 port
= Download/monitor por.
«= Battery (supervised)
+ N/O and C/0 watchdog contacts
+ Supervised +48 V field vokage
+ CTinputs 1 Aand 5 A
+ Universal opto inputs with programmable
voltage threshold. The optically coated
inputs are independent and may be
powered from the +48 V field voltage.