Professional Documents
Culture Documents
kV=220)
.5
10
30
50
100
300
500
1K
3K
5K
1K
10K
1K
500
500
300
300
100
100
50
50
30
30
D14-RP - G
OC1
220kV B/S
ABB
REF615
CT Ratio 3000:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.35
3x = 2.21 s, 5x = 1.5 s, 8x = 1.15 s
Seconds
10
10
.5
.5
.3
D05-RP - G
OC1
.3
.1
120MVA T/F
ABB
REF615
CT Ratio 600:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.25
3x = 1.58 s, 5x = 1.07 s, 8x = 0.824 s
.1
.05
.05
.03
.03
.01
.5
10
30
50
100
300
500
1K
3K
CASE:1.2-EF
Date:
SN:
Rev:
Fault:
Circuit:
21-01-2016
LARSENTRN2
Base
Ground
220kVB/S, 120MVA T/F
5K
.01
10K