You are on page 1of 1

Amps X 100 11kV Bus-A (Nom. kV=11, Plot Ref.

kV=11)
.5

10

30

50

100

300

500

1K

3K

5K

1K

500

500

300

300

TR1-SBEF - G
OC1

100

100

20MVA SBEF
ABB
REF615
CT Ratio 1200:1
IEC - Normal Inverse
Pickup = 42 (1 - 100 xCT Sec)
Time Dial = 0.44
3x = 2.77 s, 5x = 1.88 s, 8x = 1.45 s

50

30

50

30

K02-RP - G
OC1

10

10

11kV BS
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.27
3x = 1.7 s, 5x = 1.16 s, 8x = 0.89 s

.5

.5

.3

.3

.1

.05

.03

K05-RP - G
OC1

K09-RP - G
OC1

11kV O/G
ABB
REF615
CT Ratio 600:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.18
3x = 1.13 s, 5x = 0.77 s, 8x = 0.593 s

11kV AX.T/F
ABB
REF615
CT Ratio 1200:1
IEC - Normal Inverse
Pickup = 42 (1 - 100 xCT Sec)
Time Dial = 0.35
3x = 2.21 s, 5x = 1.5 s, 8x = 1.15 s

.1

.05

.03

.01
.5

10

30

50

100

300

500

1K

3K

Amps X 100 11kV Bus-A (Nom. kV=11, Plot Ref. kV=11)


N7733-ZAKHER
Project:
Location:
Contract:
Engineer:
Filename:

220/33/11kV Zakher Grid


Zakher Area of Al Ain
N7733
JM
C:\ETAP 1250\N7733\N7733.OTI

CASE:3.1 EF
Date:
SN:
Rev:
Fault:
Circuit:

21-01-2016
LARSENTRN2
Base
Ground
20MVASBEF,11kVI/C,BS,OG

5K

.01
10K

ETAP Star 12.5.0C

Seconds

Seconds

10K
1K