Given the coordination below.

The CT used is 15VA, 5P10. Evaluate the suitability of the relay and the type
of CT used.
Amps X 1000 @ 0.48 kV
.5

10

30

50

100

300

500

1K

3K

5K

1K

500 MVAsc

10K
1K

U1
500

500

FLA
300

2000 kVA (Secondary) 5 %Z


Delta-Wye Solid Grd

13.8 kV

100

100

Relay1
Mitsubishi
CO-D
CT Ratio 100:5
CO-11-D
Pickup = 7 (4 - 12 Sec - 5A)
Time Dial = 2
3x = 1.19 s, 5x = 0.439 s, 8x = 0.228 s
Inst = 45 (20 - 80 Sec - 5A)

50

30

10

100/5

CB2

.5
.3

Relay1

10

T1
2000 kVA
13.8/0.48 kV
5 %Z

LT Pickup = 1.0 (2500 Amps)


LT Band = Curve A
ST Pickup = 4 (10000 Amps)
ST Band = Curve A I2t = OUT
Inst. Pickup = 1.5 (3750 Amps)

.5
.3

CB2
.1

44.55kA @ 0.48kV

.05

Relay1 - 3P
20.918kA @ 13.8kV
(Sym)

.03

.5

10

30

50

100

300

500

1K

Amps X 1000 @ 0.48 kV


Star1
Project:
Location:
Contract:
Engineer:
Filename: C:\ET AP 556\ST UDYCASE5\ST UDYCASE5.OTI

Date:
SN:
Rev:
Fault:

Inrush

13-02-2008
JGCPHILSIN
Base
Phase

3K

Bus2

.03

0.48 kV

.01
5K

.01
10K

2500 A
42 kA

.1

CB2 - 3P
.05

16 kA

30

CB1

50

ABB SACE PR111


Sensor = 2500

1200 A

Seconds

Seconds

Bus1

300

T1