You are on page 1of 1

EXTRACT FAN SCHEDULE (NDT AREA)

AIRFLOW
L/SEC

STATIC
PRESSURE
PASCAL

PHASE / Hz

NEW

555

160

1 / 60

230

0.09

CONSTANT

DIRECT DRIVE- DOWN BLAST INTERLOCK WITH AHU - 01,

LABORATORY AREA

EXISTING

1355

350

3 / 60

380

1.119

CONSTANT

BELT DRIVEN - DOWN BLAST

LABORATORY AREA

EXISTING

1355

350

3 / 60

380

1.119

CONSTANT

BELT DRIVEN - DOWN BLAST INTERLOCK WITH AHU - 01,

EQUIPMENT LABORATORY

EXISTING

1355

350

3 / 60

380

1.119

CONSTANT

BELT DRIVEN - DOWN BLAST INTERLOCK WITH AHU - 01,

NEW

1355

168

1/ 60

230

0.62

CONSTANT

EXTRACT FAN
NUMBER

LOCATION
OF UNIT

MAKE

MODEL
NUMBER

AREA
SERVED

EF - NDT - 01

ROOF

GREEN HECK

G-103-A

PT ROOM

EF - NDT - 02

ROOF

GREEN HECK

GB-180-15

EF - NDT - 03

ROOF

GREEN HECK

GB-180-15

EF - NDT - 04

ROOF

GREEN HECK

GB-180-15

NEW OR
EXISTING

POWER (KW) CONSTANT OR VFD

FAN TYPE

COMMENTS

INTERLOCK WITH AHU - 01,

EF - NDT - 05

ROOF

GREEN HECK

SWB-218-20

TUBE FURNACE,
WELDING MACHINES
STORAGE

EF - NDT - 06

ROOF

GREEN HECK

GB-180-15

EQUIPMENT LABORATORY

EXISTING

1355

350

3 / 60

380

1.119

VFD

BELT DRIVEN - DOWN BLAST INTERLOCK WITH AHU - 01,

EF - NDT - 07

ROOF

GREEN HECK

G-095-D

OFFICE TOILETS

NEW

230

110

1/ 60

230

0.06

CONSTANT

DIRECT DRIVE- DOWN BLAST INTERLOCK WITH AHU - 01,

EF - NDT - 08

ROOF

GREEN HECK

G-090-D

CHEMICAL LAB

NEW

160

100

1/ 60

230

0.03

CONSTANT

DIRECT DRIVE- DOWN BLAST INTERLOCK WITH AHU - 01,

BACKWARD INCLINED
CENTRIFUGAL UTILITY FAN

INTERLOCK WITH AHU - 01,

You might also like