Coils
Coils are the main devices for transferring energy
to/from the airstream in an air-handling system.
Heat Transfer Media
Hydronic Fluid (Water)
Steam
Direct Expansion
Important Coil Load Concepts
Apparatus Dew Point
Bypass Factor
Terminology
Sensible Cooling
Latent Cooling
Space Sensible Cooling
Space Sensible Heat Ratio (Factor)
Grand Sensible Heat Ratio (Capacity)
Apparatus Dew Point
Bypass Factor
SHR
Appratus
Dew Point
Coil
Leaving
Air
Coil
Entering
Air
Coil
Entering
Air
Bypass Factor
Some of the air flowing through the coil impinges
on the water tubes or the fins and is cooled to the
ADP. Other air passes through unchanged.
Coil
Entering
Air
Fin
8-Row Coil
80 fpf /2 fps/44 EWT / WTR = 10
Coil Bypass
Coil Selection
Start With Space Conditions
Find the intersection of the SHR
with desired room temperature and
supply air temperature
Room
Supply
Air
SHR
Room Air
Temperature
Coil Selection
Determine Outside Air Requirements Using
ASHRAE Standard 62
Offices
Schools
Bars
Smoking Lounges
Corridors
Entering
Appratus
Leaving
Air
Dew Point
Air
Mixed Air
Room Air
Entering
Appratus
Leaving
Air
Dew Point
Air
Mixed Air
SHR
Room Air
h
Leaving
Air Enthalpy
SHR =
tfan
30,800
1.10 (75 - 55)
30,800
30,800 + 8,500
0.363 x 4
0.7
1400
0.80
1.95F
SHR=0.70
Room Air
75F / 50% RH
10
55F
Mixed Air
SHR=0.80
tfan
Outside Air
85F / 70F WB
Mixed Air
SHR=0.80
11
Outside Air
85F / 70F WB
Mixed Air
SHR=0.80
12
mCpT
qcoil
=
52,290
(500 x T)
(500 x F)
10.5 GPM
13