Code of Practice On Sanitary Plumbing and Drainage System
Code of Practice On Sanitary Plumbing and Drainage System
ON
SANITARY PLUMBING AND DRAINAGE SYSTEM
CONTENTS
INTRODUCTION
PART VI : APPENDICES
a. STANDARD DRAWINGS ON SANITARY PLUMBING AND DRAINAGE
SYSTEM
CODE OF PRACTICE
ON
SANITARY PLUMBING AND DRAINAGE SYSTEM
(3rd Edition -Feb 90 and 4th Reprint - May 97)
ADDENDUM NO. 1
(Sep 1997)
This addendum shall be read in conjunction with the Code of Practice on Sanitary Plumbing and Drainage
System (3rd Edition- Feb 90 and 4th Reprint - May 97) and shall form part of the Code of Practice.
*
S/No.
Part /Page No
Part I /page 1
Clause /
Appendix
Drawing
No
Part I/ page 4
Part I/page 4
Clause
6.9
Clause
6.3
Amendments /corrections
Part I /page 7
Clause
11.2
S/No.
Part /Page
No
Part I/ page
8
Clause /
Appendix
Drawing
No
Amendments /corrections
Part II /
page 10
Clause
1.3
Part II /
page 11
Clause
2.3.1
Part II/
page 11
Clause
2.3.5
Part II/
page 13
10
Part II/
page 13
Clause
3.3.5
S/No.
Part /Page No
Clause /
Appendix
Drawing
No
Amendments /corrections
11
Part II /
page 14
Clause
3.5.3
12
Part III/
page 17
13
Part III /
page 18
Clause
3.4.2
-Every wall hung water closet pans for use in public toilets
shall be of a design suitable for use with 6-litre flush valves
and shall conform to the functional requirements and tests in
the relevant Singapore Standards.
14
Part III /
page 19
Clause
4.1.7
15
Part III /
page 19
Clause
4.1.8
Part III /
page 19
Clause
4.1.12
Part III/
Clause
5.1.1
page 20
18
Part III /
page 20
Clause
5.1.3
19
Part III /
page 20
Clause
5.3.1
20
Part III/
page 21
Clause
6.2.3
16
17
S/No
.
Part /Page No
21
Part III/
page 22
Clause /
Appendix
Drawing
No
Amendments /corrections
Clause
6.2.12
- Each sensor unit shall only operate one flushing device for a
sanitary appliance. The sensor unit when installed shall not
be affected by the operation of adjacent sensor unit.
-The sensor unit shall be firmly installed on the wall fronting
the appliance. It should not be supported by the water pipe.
Clause
6.2.13
Clause
6.2.14
22
23
Part III /
page25
Clause
10.12
Part III /
page 25
Clause
11.2
CODE OF PRACTICE
ON
SANITARY PLUMBING AND DRAINAGE SYSTEM
INTRODUCTION
The Code of Practice on Sanitary Plumbing and Drainage System, issued under regulation 3 of The
Sanitary Plumbing and Drainage System Regulations, 1976 shall be complied with by Professional
Engineers, Registered Architects and Registered Plumbers for the design, installation and execution of all
sanitary plumbing and drainage works.
The requirements under this Code are supplemental to The Sanitary Plumbing and Drainage System
Regulations, 1976. They do not exhaustively cover all aspects of the design and construction of sanitary
plumbing and drainage works but only set out the minimum requirements.
This edition incorporates changes in design and construction based on recent experiences and practices.
This Code of Practice may be amended and revised from time to time.
Sewerage Department
Ministry of the Environment
Singapore
CODE OF PRACTICE
ON
SANITARY PLUMBING AND DRAINAGE SYSTEM
INTRODUCTION
The Code of Practice on Sanitary Plumbing and Drainage System, issued under regulation 3 of The
Sanitary Plumbing and Drainage System Regulations, 1976 shall be complied with by Professional
Engineers, Registered Architects and Registered Plumbers for the design, installation and execution of all
sanitary plumbing and drainage works.
The requirements under this Code are supplemental to The Sanitary Plumbing and Drainage System
Regulations, 1976. They do not exhaustively cover all aspects of the design and construction of sanitary
plumbing and drainage works but only set out the minimum requirements.
This edition incorporates changes in design and construction based on recent experiences and practices.
This Code of Practice may be amended and revised from time to time.
Sewerage Department
Ministry of the Environment
Singapore
CODE OF PRACTICE
ON
SANITARY PLUMBING AND DRAINAGE SYSTEM
PART I : SANITARY DRAINAGE SYSTEM
1.
2.
The design and layout of the sanitary drainage system shall be as simple and direct as
practicable for the proper conveyance of sewage within the premises for discharge to the
sewerage system
2.3
The distance from the inlet of the branch drain-line to the inspection chamber shall not
exceed 10 metres where practicable. If the distance is required to be extended, the
maximum distance shall not exceed 20 metres provided the size of the branch drain-line
is at least 150 mm diameter.
Every branch drain-line shall be connected obliquely in the same direction of flow as the
main drain-line within the inspection chamber by means of curved vitrified clay channel
bedded in concrete and finished with a benching sloping 1 in 6 to 1 in 10 upwards to
meet the wall of the inspection chamber.
Every branch drain-line shall be laid in a straight run with a constant gradient and shall
be water-tight.
Every branch drain-line shall have flexible pipe joint.
Every branch drain-line shall be laid using the same material throughout its entire
length.
The invert of the branch drain-line entering the inspection chamber shall be connected
above the horizontal diameter of the main channel.
The gradient of branch drain-lines shall be as follows except where otherwise required.
2.4
2.5
2.6
2.7
2.8.
2.9
Diameter of branch
Maximum Gradient
Allowable Gradient
drain line
Upstream of Backdrop/
in other Cases
Tumbling Bay
3.
100mm
1 in 2o to
1 in 60
150mm
1 in 70
1 in 30 to
1 in 90
225mm
1 in 90
1 in 40 to
1 in 150
3.6
3.7
3.8
3.9
Diameter of branch
Maximum Gradient
Allowable Gradient
drain line
Upstream of Backdrop/
in other Cases
Tumbling Bay
4.
150mm
1 in 70
1 in 30 to
1 in 90
225mm
1 in 90
1 in 40 to
1 in 150
No drain-line shall pass under any building except where an alternative route is
4.2
4.3
4.4
5.
5.2
6.
Every drain-line under drive-way or car-park shall be laid in heavy duty cast iron pipe
or ductile iron pipe and shall be bedded and encased in concrete of at least 100 mm
thickness
Where the depth from the top of the drain-line to the ground level exceeds 1.4 metres
other pipes except uPVC pipe may be used and shall be completely embedded in
concrete to a thickness of at least 100 mm all round.
Inlet to Drain-line(6)
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
7.
impracticable.
Where a drain-line passes under a building, it shall be laid in a straight run for the
whole distance and shall be surrounded in concrete at least 100 mm thickness
Where a drain-line is to be encased within the basement floor slab, it shall be of heavy
duty cast iron pipe or ductile
Where a drain-line passes through the basement wall, it shall be of heavy duty cast iron
pipe or ductile iron pipe. The joint through the wall shall be designed to ensure water
tightness and accommodate any differential movement.
Every inlet to the drain-line shall be properly trapped and capable of maintaining a
water seal of not less than 50 mm
Proper means of access shall be provided for the purpose of maintenance.
Every gully trap and inspection chamber shall be located outside the building proper
but under cover wherever practicable.
Every gully trap shall be embedded in concrete to a thickness of at least 100 mm all
round.
Every gully trap shall be fixed as near the floor level as practicable and the depth
from the floor level to the bottom of the trap, including the depth of any riser if
required, shall not exceed 600 mm. Where the depth exceeds 600 mm, it shall be
housed within a sump of at least 900 mm x 700 mm. The gully sump shall be covered
with removable precast concrete slabs or chequered plates. However, the maximum
depth of gully trap from the bottom of sump shall be maintained at 600 mm.
Every waste discharge pipe shall be connected to a gully trap at the riser below the
grating and above the water seal of the trap
Where a riser is provided to a gully trap, it, shall be made of uPVC or other approved
piping material to provide a smooth and even finish.
Where a gully trap is sited in a location where it is likely to receive rain-water or on
unpaved ground, it shall be fixed with a gully frame and an unperforated cover flap at
least 20 mm above the ground or floor level to prevent ingress of rain-water. The floor
surrounding the raised gully trap shall be sloped away from the trap.
Where the gully trap is intended to receive sullage water, it shall be fixed with a gully
frame and grating at least 5mm below the paved floor. The floor surrounding such
gully trap shall be sloped towards the trap.
Excavation
7.1
7.2
7.3
7.4
7.5
8.
8.2
8.3
8.4
8.5
8.6
9.
Every trench excavation shall be properly timbered to support the walls thereof from
collapsing and shall comply with the provisions in The Building Operations and
Works of Engineering Construction Regulations.
Where the trench excavation is contiguous to a public tboroughfare or where it would
constitute a danger or hazard to the safety of the public or to any adjoining property,
every precaution shall be taken against accidents occurring.
Adequate appropriate warning signs shall be displayed conspicuously.
Adequate flashing warning lights shall be displayed at night.
Where pipejacking is required, details of such work shall be submitted by a
Professional Engineer prior to commencement of work.
Where the cover depth is between 0.6 metres and 2.0 metres and on firm ground, every
drainline of cast iron or ductile iron pipe shall be laid on granular bedding (Type '1'
bedding). However, every drain-line of uPVC, vitrified clay or reinforced concrete pipe
shall be bedded in concrete at least 100 mm thick and properly haunched in concrete to
at least 100 mm on either side of the pipe (Type '2' bedding).
Where the cover depth is less than 0.6 metres or more than 2.0 metres and on firm
ground, every drain-line of uPVC, vitrified clay or reinforced concrete pipe shall be
encased in concrete of minimum thickness 100 mm (Type '3' bedding). However, every
drain-line of cast iron or ductile iron pipe shall be bedded in concrete at least 100 mm
thick and properly haunched in concrete to at least 100 mm on either side of the pipe
(Type '2' bedding).
On soft or yielding ground, every drain-line shall be provided with the same bedding
as for firm ground except bat the bedding shall be founded on 'bakau' piles.
Granular material for bedding of flexible jointed pipes shall be of such size ranging
from 3 mm to 12 mm or a free running coarse sand.
Selected fill material, free from lumps exceeding 75 mm in size and from stones, shall
be placed over the pipes and compacted in layers not exceeding 150 mm in depth to a
height of 300 mm above the top of the pipes. The rest of the trench shall then be
backfilled to the surrounding level with ordinary fill material properly compacted.
Break joint for concrete bedding and haunching shall be provided along every drainline at intervals not exceeding 6 metres.
9.3
Every inspection chamber of the sanitary drainage system shall have a minimum
depth of 750 mm from surface level wherever practicable
The first inspection chamber shall be provided with a ventilating stack or not less
than 100 mm in diameter. The ventilating stack shall have an untrapped opening in
the inspection chamber and no bend or angle, except where unavoidable, shall be
formed in any such stack. However, ventilating stack for the first inspection chamber
need not be provided for guard house and bin centre.
A discharge stack at the first inspection chamber shall constitute a suf6cient opening
9.4
9.5
9.6
9.7
9.8
9.9
9.10
9.11
9.12
9.13
9.14
9.15
9.16
10.
Testing
10.1
10.2
10.3
11.
Every drain-line laid shall be water - tight and subjected to a water test under a static
head of not less than 1 metre of water at the upstream end of the line.
The said water test shall be applied after laying and before placing concrete for
haunching or encasing. Any leakage in the drain-line shall be rectified
Every inspection chamber shall be water-tight and subjected to a water test.
Wash Area(9)
11.1
Every wash area where provided shall be roofed over. Rain-water run-off from the
11.2
11.3
12.
12.4
13.
Every eating establishment, food centre and other like places shall be provided with
grease trap.
Every grease trap shall not be sited within areas where food is prepared, cooked
stored or served
On the first storey level, sufficient cast iron floor traps shall be provided and
connected to a screen chamber and a grease trap before connection to the inspection
chamber (see Appendix 10).
On the upper storey level, a separate cast iron discharge pipe and stack of at least
100 mm diameter shall be provided. Sufficient cast iron floor traps shall be provided
and connected to the cast iron discharge pipe and stack. The discharge stack shall be
extended to serve as ventilating stack but may be reduced to 75 mm diameter and
either extended to the roof or connected into nearby ventilating stack. The discharge
stack shall be connected to a screen chamber and grease trap prior to connection to
the inspection chamber.
13.2
13.3
Common corridors, common verandahs, covered play areas, covered car parks,
refuse chutes, bin centres, markets and other like places of any building where
sullage water flows, shall be recessed below the surrounding or adjacent floors or
curbed up. Such areas shall be laid in falls to floor trap/gully trap so that the run is
not more than 5 metres to each floor trap/gully trap. Where additional drainage
outlets are required, floor waste may be provided. In such case, the floor waste shall
be connected to a floor trap before connection to the sanitary plumbing and drainage
system
On the first storey level, sufficient floor traps and a cast iron gully trap with an
aluminum alloy strainer bucket (Standard Drawing ENV/SEW/76/113 & 83) housed
within a sump shall be provided before connection to an inspection chamber (See
Appendix 12).
On the upper storey level, the floor traps shall be connected to a separate sullage
water discharge stack of at least 100 mm diameter. The sullage water discharge stack
shall be connected to a cast iron gully trap with an aluminum alloy strainer bucket
housed within a sump at first storey level before connection to an inspection
chamber. Similarly where there are several sullage water discharge stacks, sumps are
to be provided at every change in direction to collect and direct the sullage water to
an inspection chamber. However, the last sump prior to connection to the inspection
chamber shall be provided with a gully trap with strainer as stipulated above (See
Appendix 11).
14.
14.3
15.
Provision of Silt Trap for Shower/Bathroom Compartment at Beach Site/Construction Site (13)
15.1
16.
Sewer Connection
16.1
16.2
17.
Every sump for sullage water drainage system shall have a minimum depth of 450
mm from surface level to invert level where practicable
Every sump shall have a minimum internal dimensions of 600 mm in length and
600 mm in width. However, where a sump is required to accommodate a gully trap,
it shall be at least 900 mm x 700 mm. Sump shall be provided with main channel to
collect and convey sullage water from branch waste pipes. The sump shall be
provided with a slope of not less than 1 in 6 towards the main channel
Every sump of 600 mm x 600 mm shall be provided with cast iron frame and cover.
However, removable precast concrete slabs or chequered plates shall be provided for
sump of 900 mm x 700 mm to facilitate maintenance.
No uPVC pipe shall be used for sewer connection between the last inspection chamber
and the sewer/manhole.
Every sewer connection shall be construed in accordance with the Sewerage
Department's Standard Drawing ENV/SEW/76/11
General
17.1.
1
Subject to the foregoing and the requirements in Part IV, the following
materials are acceptable for use in sanitary drainage system viz
a)
b)
c)
d)
e)
17.1.
uPVC
Heavy duty cast iron
Ductile iron
Vitrified clay
Reinforced concrete
17.2
Pipe Joints
17.2.1
17.2.2
17.2.3
Every joint in a sanitary drainage system shall be made air-tight and watertight and shall remain so during use.
No jointing material shall protrude inside the bore of the pipe.
Pipes for sanitary drainage system shall be flexibly jointed by means of
rubber rings suitably designed to accommodate rubber ring seals such that
when the spigot is introduced the joint ring will be compressed to render
the joint air-tight and water-tight. Alternatively a coupling with rubber
rings suitably designed to ensure air and water tightness may be used.
**** Note : Numerals in parenthesis refer to the corresponding Appendices in Part VI ***
CODE OF PRACTICE
ON
SANITARY PLUMBING AND DRAINAGE SYSTEM
PART II: SANITARY PLUMBING SYSTEM
1.2
1.3
2.
The Sanitary plumbing system for any premises shall be designed to carry away sewage
and waste water from the building quickly so as not to create any nuisance or risk of
injury to health.
No sanitary plumbing system shall be used to convey rain-water.
The one pipe "fully ventilated system is recommended in the design of the sanitary
plumbing system. However, in the case or residential buildings where the sanitary
appliances are closely grouped around a discharge stack, the "single stack system" may
be adopted for buildings up to six storeys high and the "ventilated stack system" for
buildings up to twenty five storeys high.
2.1.5
The fully ventilated system is used where there are large number of sanitary
appliances in range or where they have to be widely dispersed
Every discharge stack shall have a uniform diameter of not less than 100mm
throughout its entire length.
Where more than one trap is connected to a discharge stack, each trap shall
be provided with a branch ventilating pipe of not less than 50mm in diameter.
Every ventilating pipe shall be constructed upwards individually and be
connected to a main ventilating stack. Such connection shall be above the
spill over level of the soil sanitary appliance or floor trap served by such
ventilating pipe.
The top end of every main ventilating pipe or main ventilating stack shall
either terminate as high as the discharge stack or connect into the discharge
stack at a point not less than 150mm above the spill over level of the topmost
soil sanitary appliance or floor trap
2.1.6
2.1.7
2.2
2.2.2
2.2.3
2.2.4
2.3
The single stack system may be adopted where there are single appliances
connected to a discharge stack or where the sanitary appliances/fittings are
closely grouped round a discharge stack which is large enough to limit
pressure fluctuations without the need for a ventilating stack.
The single stack system may be adopted for residential buildings up to six
storeys high.
The main discharge stack shall have a uniform diameter of not less than
150mm without offset throughout its entire length.
The length of the discharge pipe connecting to the discharge stack shall not
be more than 2.5m and there shall be not more than two numbers of
connections made to the discharge pipe.
2.3.2
2.3.3
2.3.4
2.3.5
3.
The ventilated stack system may be adopted in situations where there are
close grouping of sanitary appliances around the discharge stack in residential
buildings up to fourteen storeys high.
The main discharge stack shall have a uniform diameter of not less than
150mm throughout its entire length.
The length of a discharge pipe connecting to the discharge stack shall not be
more than 2.5m and there shall be not more than two numbers of connections
made to the discharge pipe.
A separate discharge stack of diameter not less than 100mm shall be provided
to serve the second and third storeys. This secondary discharge stack shall be
extended to serve as ventilating stack but may be reduced to 75mm diameter.
The ventilating stack shall either terminate as high as the discharge stack or
connect into the main discharge stack at a point not less than 150mm above
the spill over level of the topmost soil sanitary appliance or floor trap.
Cross venting between the ventilating stack and the discharge stack shall be
provided at third, ninth and twelfth storeys.
General
3.1
Trap
3.1.1
Every inlet to the discharged stack shall be properly trapped to prevent the
3.1.2
3.1.3
3.1.4
3.2
3.2.6
3.2.7
3.2.8
3.2.9
3.2.10
3.2.11
3.2.12
3.3
entry of foul air from the drainage system into the building.
Every trap for soil sanitary appliance and floor trap shall have a water seal of
not less than 50mm.
Every trap with an outlet of less than 75 mm in diameter shall have a water
seal of not less than 75 mm.
Every trap shall be provided with access cover so as to facilitate cleaning.
Every discharge stack shall have a uniform diameter and be made of the
same material throughout its entire length.
Every discharge pipe conveying soil shall have a diameter of not less than
100 mm.
Every discharge pipe shall not be reduced in diameter in the direction of
flow.
Every discharge stack shall be extended through the roof to the atmosphere.
Every discharge pipe and discharge stack shall be fined with access covers,
bends, branches, junctions and other fittings for connections from the
sanitary appliances and floor traps.
In the case of the "fully ventilated system" and "ventilated stack system",
the discharge stack shall, as far as practicable, not form any offset
throughout its entire length. Where offset is to be made, large radius bends
of at least 200 mm radius shall be used and cross venting between the
ventilating stack and the discharge stack is required above and below the
offset.
Swept branch connections from discharge pipe to discharge stack are
recommended. Opposed discharge pipes without swept entries shall be at
least 200 mm apart so that the discharge from one branch into the other is
avoided
In the case of 'P' floor trap and water closet pan connected in series to the
same discharge pipe, a double 45 bend shall be incorporated between the
~' floor trap and the water closet pan to prevent backflow. Alternatively, a
'S' floor trap may be used without the double 45 bend.
Every access cover Shall be so fixed in a manner for easy access to facilitate
maintenance and also away from hidden comers. Access cover on the invert
of pipe shall be avoided. Access for rodding and testing shall be provided al
or near the foot of the discharge stack.
Every discharge pipe and discharge stack shall be securely supported or
fixed to the wall of a building. The pipe supports or fixing shall be properly
aligned and the distance between them shall not exceed 2.0 metres
vertically and 1.5 metres horizontally.
Where discharge pipe or stack passes through wall or floor, the joint
through the wall or floor shall be water-tight.
Every discharge pipe shall not be located above any potable water storage
tank and electrical transformer/switchgear.
3.3.1
3.3.2
3.3.3
3.3.4
3.4
3.4.2
3.4.3
3.4.4
3.5
Every ventilating pipe shall be fixed as close to the crown of the trap as
practicable.
Every ventilating pipe shall be constructed upwards individually or be
connected to a main ventilating stack. Such connection shall be above the
spill over level of the soil sanitary appliance or floor trap served by such
ventilating pipe.
Where cross venting is to be provided, the cross connection shall be sloped
upwards from the discharge slack to prevent the entry of discharge water into
the ventilation system. This connection shall be of the same diameter as the
ventilating stack.
The lowest cross venting between the ventilating stack and the discharge
stack shall be fixed at a point not less than 225 mm below the lowest
discharge pipe connection.
The top end of every discharge stack shall be provided with a guard (i.e. wire
ball for cast iron ventilating stack and uPVC cowl for uPVC ventilating stack)
and extended not less than IS0 mm above the highest sloping roof or IS0 mm
above a flat roof without parapet, or in the case of a flat roof with a parapet to
the height of the parapet above the roof.
If a flat roof is used for any purpose other than as a covering to the building,
the discharge stack or the ventilating stack shall be extended at least 2.5
metres above roof level.
The top end of the discharge stack or ventilating stack above the roof shall be
at least 3 metres away from any window or opening of an adjoining building
in the horizontal direction so as to give efficient ventilation and prevent any
likelihood of contamination or nuisance to an adjoining building.
Where a stack passes through a roof the area surrounding the stack shall be
water-tight.
3.5.2
3.5.3
4.
5.
5.2
6.
The sanitary plumbing system shall be tested either by means of an air test, smoke test
or water test for soundness of the installation.
Painting
7.1
8.
No pipe other than the ventilating pipe or ventilating stack and waste pipe shall be
encased in columns, beams, walls or floor slabs. Where the pipework is required to be
concealed, it shall be accommodated in an enclosure.
Pipework enclosures such as ducts or casings shall be of a suitable size and provided
with ready access for maintenance, painting, testing and cleaning.
Testing
6.1
7.
For wastes collected from canteen, cooked food centre and restaurant located below
surrounding ground level, sewage divertor shall be provided.
For domestic wastes collected below surrounding ground level, sewage ejector shall be
provided.
For waste water from covered car park below ground level, sewage ejector or any other
approved system of pumping shall be provided.
Where a sewage divertor or sewage ejector is required a room of minimum size 3.0
metres be 3.0 metres shall be provided.
The tank for the sewage divertor or sewage ejector shall be constructed from noncorrodible material.
After testing, the pipework of the sanitary plumbing system may be painted to any
suitable colour.
General
8.1.1
Subject to the foregoing and the requirements in Part IV, the following
materials are acceptable for use in a sanitary plumbing system viz
a)
b)
c)
8.1.2
8.2
uPVC
Cast iron
Ductile iron
Pipe Joint
8.2.1
Every joint in the sanitary plumbing system shall be made air-tight and watertight and shall remain so during use.
No jointing material shall protrude inside the bore of the pipe.
Joint for cast iron pipe shall be made as follows:
8.2.2
8.2.3
a)
b)
c)
8.2.4
8.2.5
spigot and socket cast iron pipe joint shall be packed firmly with spun
yarn and then tightly caulked to not less than two-thirds of the depth of
the socket with molten lead or fibrous lead yarn.
rubber ring joint.
rubber sleeve joint
CODE OF PRACTICE
ON
SANITARY PLUMBING AND DRAINAGE SYSTEM
PART III : SANITARY APPLIANCE FITTING
Sanitary Appliance
1.1
1.2
2.
3.
Every sanitary appliance installed in any premises shall be connected to the sanitary
plumbing and drainage system.
No direct connection from any water service pipe shall be made to any part of a soil
sanitary appliance other than a connection through the flushing cistern or flush valve as
detailed under Clause 6 of this Part.
The discharge from a soil sanitary appliance shall pass through at least one trap having
a water seal of not less than 50 mm before connecting to a branch drain-line on first
storey level or to a discharge pipe on upper storey level.
General
3.1.1
3.1.2
3.1.3
Every water closet pan shall conform to the functional requirements and tests
in Singapore Standard 205.
Every water closet pan shall connect directly to an individual branch drainline to an inspection chamber on first storey level or to a discharge pipe on
upper storey level.
Every water closet pan shall be firmly bedded in cement mortar or by other
3.1.4
3.1.5
3.2
3.3
Every oriental water closet pan installed in a combined bath and water closet
compartment shall be fixed at least 75 mm above floor level.
Every oriental water closet pan shall be installed within a specially designed recessed
reinforced concrete floor slab such that no part of the pan shall protrude into the floor
slab or the floor below. The pan shall then be bedded in sand and concreted over to
provide an impervious surround. The floor surrounding the pan shall also be graded to
drain off any water into the pan.
Pedestal Water Closet Pan
3.3.1
3.4
Every pedestal water closet pan shall be secured to the floor using stainless
steel or non-ferrous fixing screws. Provision shall be made in the floor to
receive the fixing screws
4.
Wall hung water closet pan shall be fixed with stainless steel bolts and nuts
or other approve means to an independent support frame such that no strain
is transmitted to the water closet pan connector or any other part of the
plumbing system. The support frame, depending on the design, shall be
either fully or partially fixed within the structure of the building.
Urinal (23)
4.1
General
4.1.1
4.1.2
4.1.3
4.1.4
4.1.5
4.1.6
Number of
Urinals Connected
Minimum Internal
Diameter of Common
Diameter of Loop
Venting Pipe
is Series
in mm
50
50
75
4.1.7
Every urinal shall be spaced at least 750 mm apart from centre to centre.
Where urinals are provided, the maximum height of urinals shall be as
follows:For adults - 550mm
For Children - 380mm
4.1.8
4.1.9
4.1.10
4.1.11
5.
Every urinal shall be operated by flush valve which must be adjusted to give
a flush of not less than 2.5 litres and not more than 4.5 Litres. The flush
valve shall preferably be concealed Heavy duty type flushing cistern may be
allowed only where the use of flush concealed Heavy duty type flushing
cistern may be allowed only where the use of flush valve is not technically
feasible. At least one 9-litre flushing cistern shall be fixed for every 4
urinals in series.
For flush valve operated urinals, the minimum internal diameter of the flush
pipe shall be 13mm.
Every flush pipe for flush valve shall be made of either stainless steel or
chrome-plated copper alloy and shall preferably be concealed.
For urinals coupled with flushing cistern, the minimum internal diameter of
the flush pipe shall be 25mm.
Flushing Cistern
5.1
General
5.1.1
5.1.2
5.1.3
5.1.4
5.1.5
5.2
5.2.2
5.2.3
5.3
5.3.2
The low level flushing cistern shall be Fixed to a pedestal water closet pan
with a pipe of vertical arm not less than 3SO mm from the base of the cistern
shell to the centre line of the flush inlet socket of the water closet pan. The
installation shall be of such a configuration that an assembly of the flushing
cistern with a pedestal water closet pan shall enable a seat and cover to
remain in the raised position.
The minimum internal diameter of the flush pipe shall be 35mm.
6.
The high level flushing cistern shall be fixed to an oriental water closet pan
with a flush pipe of height not less than 1.5 metres between the bottom of the
cistem and the top of the water closet pan.
The flush pipe connecting a flushing cistem to the water closet pan shall be
fixed as straight as possible and shall not be less than 32 mm in diameter.
Every flush pipe from the cistern shall be securely filched to the wall.
5.4
means.
Every flushing cistern shall be installed abutting the wall.
Where brackets or other approved means are used, they shall not protrude
beyond the bottom width of the cistern and shall not have any sharp edges.
The connection of the flush pipe of the flushing cistern to the water closet pan
and the urinal shall be made using a purpose made connector or bush to
ensure a robust and water-tight joint.
The flushing cistern for close-coupled water closet suite is designed for use
only as a complete unit with a particular water closet pan. The suite shall be
installed in accordance with recommended practice.
General
6.1.1
6.1.2
6.1.3
6.1.4
6.2
Installation
6.2.1
6.2.2
6.2.3
6.2.4
6.2.5
6.2.6
6.2.7
6.2.8
6.2.9
6.2.10
Bidet
7.1
General
7.1.1
7.1.2
7.1.3
7.2
Every flush valve for water closet pan shall incorporate approved check
valve and vacuum breaker. 241tematively, flush valve for water closet pan
shall derive water from a separate storage tank which is not connected in
any way with all other fittings supplying basin, sink, heater, etc in the
building.
Every flush valve shall be controlled by an approved stop-valve.
Every flush valve must be so adjusted to give a flush of not less than 2.5
Litres and not more than 4.5 litres of water for each urinal or not less than 8
litres and more than 9.5 litres of water for each water closet pan.
Vacuum breaker of the flush valve shall be installed at least I metre above
the rim for oriental water closet pan and at least 300 mm above the rim level
for other types of water closet pan.
Every flush valve shall be Fixed to a urinal with a flush pipe of height not
less than 150mm.
Every flush pipe shall be made of either stainless steel or chrome-plated
copper alloy and preferably be concealed.
The connection of the flush pipe of the flush valve to the water closet pan
and urinal shall be made using a purpose made connector to ensure a robust
and water-tight joint.
The minimum internal diameter of the flush pipe for water closet pan shall
be 25 mm
The minimum internal diameter of the flush pipe for urinal shall be 13 mm
For auto-sensing/electronic sensor flush valve, the installation of the
sensor/electronic sensor unit shall be carried out by a PUB licensed
electrician who shall ensure compliance with the relevant regulations and
Code of Practice.
Every bidet shall be provided with a spray nozzle fixed above the spill over
level of the bidet pan
Every bidet shall be provided with a fitting trap of at least 40 mm in
diameter. The connection by means of a bidet trap of at least 75 mm in
diameter shall be made directly to an individual branch drain-line to an
inspection chamber on first storey level or to a discharge pipe on upper
storey level.
Water for the flushing of the bidet shall not be supplied directly f from the
water main unless through an approved vacuum breaker and check valve or
other approved means for reverting backflow or back siphonage and
controlled by an approved stop-valve.
Installation
7.2.1
The bidet pan shall be installed in accordance with the pedestal water closet pan or the
wall hung water closet pan as specified in clauses 3.3.1 or 3.4.1 of this Part
respectively.
8.
9.
Approval of the Director shall be obtained for the use of any special soil sanitary
appliance not covered under this Part.
9.2
9.2.4
Every waste sanitary appliance shall be provided with a waste fitting trap
for connection to the waste pipe.
The waste pipe shall connect to the floor trap above the water seal of the
trap.
The waste pipe for waste sanitary appliance fixed on firs storey level
outside the building may connect directly to a gully trap above the water
seal of the trap.
Where a group of 3 or more wash basins are connected in series, loop
venting is required. However, the loop venting shall be terminated
separately to the atmosphere. The minimum diameter of loop venting pipe
shall be 25 mm. The minimum internal diameter of waste pipe for each
type of waste sanitary appliance and the maximum number of waste
sanitary appliances allowed on common waste pipe for waste sanitary
appliances connected in series shall be as follows:a)
b)
Type of Appliance
Wash basin
Sink (Single or double bowl)
Laboratory sink
Longbath/Shower tray
Foot bath
Wash tub
Wash trough/Custom-made sink
Drinking fountain
32
40
40
40
40
50
50
32
Maximum Number of Waste
Sanitary Appliances Allowed
on Common Waste Pipe
75
10
6
2
12
2
2
6
40
6
6
Floor Trap
10.1
10.2
10.3
10.4
10.5
10.6
10.7
10.8
Every floor trap at First storey level shall be connected to a gully trap above the
water seal of the trap and the length of the waste pipe bet between the floor trap
and gully trap shall be as short as practicable.
Every floor trap at upper storey level shall be connected to a discharge pipe.
Every floor trap shall be located inside the building wherever practicable
The minimum internal diameter of the outlet of the floor trap shall be 75 mm.
The riser to every floor trap shall be of the same diameter as the opening of the
trap.
The height of a riser to every floor trap shall not be more than 600 mm from the
top of the grating to the bottom of the trap.
Where a riser is provided to a floor trap, it shall be made of uPVC or other
approved piping material to provide a smooth and even finish.
Every waste pipe connection shall be flushed with the internal surface of the riser.
10.9
10.10
10.11
11.
11.2
11.3
Floor waste where provided Shall be connected to a floor trap above the water seal
of the trap and the length of the waste pipe between the floor waste and floor trap
shall be as short as possible.
The minimum internal diameter of the floor waste shall be 75 mm. ,Only one
sanitary waste appliance may be connected to the floor waste.
The floor waste shall be covered with a grating.
Grating and Cover for Gully Trap, Floor Trap and Floor Waste
12.1
12.2
12.3
13
Floor Waste
11.1
12.
Every floor trap frame and grating shall be fixed at least 5 mm below the lowest
point of a graded floor where it is intended to receive sullage water.
Floor trap shall be provided for bathroom or shower compartment. The floor shall
be graded towards a floor trap to receive sullage water.
The grating and cover shall be constructed of durable plastic, stainless steel or
other suitable approved material.
The grating and cover shall be of an approved design so as to enable them to be
bolted down to the frame or otherwise secured to deter the unwarranted opening of
the grating or cover and hence the discharge of garbage or other solid waste into
the sewerage system.
Subject to the sub-clauses 6.8 & 6.9 of Part I the grating or cover shall be installed
and located such that they blend in with the surrounding ground levels and do not
pose a hazard in causing trip, etc
CODE OF PRACTICE
ON
SANITARY PLUMBING AND DRAINAGE SYSTEM
1.
1.3
2.
The term "sanitary appliance and material" shall refer to sanitary appliance/fitting, pipe
and fitting, and manhole/inspection chamber frame and cover.
Every sanitary appliance and material used in the construction of a sanitary plumbing
and drainage system described in this Code shall be of a type, size, brand, quality and
workmanship approved by the Director.
Every sanitary appliance and material shall be clearly embossed or permanently marked
with be brand name/trade mask and the country of origin at a conspicuous position such
that they can be clearly identified after installation.
2.3
Every application for approval for sanitary appliance and material shall be made by
the applicant to the Director in writing.
The applicant shall deliver to the Director such samples of the sanitary appliance and
material and give such other information in connection therewith as the Director may
require
If so required by the Director, the applicant shall deliver one or more samples of the
sanitary appliance and material to the Singapore Institute of Standards and Industrial
2.4
2.5
2.6
2.7
Research (SISIR) for examination and testing. The applicant shall pay such fees as
SISIR may determine for such examination and testing or any other fees associated
with the application for approval.
The applicant will be notified in writing of the approval/disapproval based on the test
report/s received directly from the SISIR.
The Director may require the applicant to dispose of all unapproved sanitary
appliances and materials and to submit proof of such disposal.
Notwithstanding the approval given for the use of the sanitary appliance and material,
further samples may be required and selected at any time for periodical testing.
The approval given by the Director for the use of any sanitary appliance and material
may be rescinded at any time if
(a)
(b)
(c)
the sanitary appliance and material is found to be unsafe or unsuitable for use;
the design, material or construction of the sanitary appliance and material is
changed or modified without the approval of the Director; and
the applicant has contravened or failed to comply with any of the requirements
as may be stipulated by the Director
CODE OF PRACTICE
ON
SANITARY PLUMBING AND DRAINAGE SYSTEM
1.
General
1.1
1.2
2.
A11 sanitary works shown on the approved Sketch Plan/Building Plan Shall be carried
out in accordance with The Sanitary Plumbing and Drainage System Regulations, 1976
and The Code of Practice on Sanitary Plumbing and Drainage System.
Application for sanitary permit is required before the commencement of any sanitary
work
Application
2.1.1
The Registered Sanitary Plumber Shall ensure that the following accompany
the application:
(a)
(b)
(c)
(i)
(ii)
(iii)
(iv)
(v)
(vi)
*(d)
*(e)
*(f)
2.2
Commencement of Work
2.2.1
2.2.2
2.2.3
(b)
has given all notices and obtained all consents that may be required by
any law to be obtained from all relevant authority or persons in respect
of the sanitary works; and
has taken appropriate insurance coverage against any damage or
injury which may be caused to persons or property or against any other
2.3
Supervision
2.3.1
2.3.2
2.4
3.
Certificate of Supervision
2.4.1
2.5
The Registered Sanitary Plumber shall ensure that Form B (See Appendix
28), Form C -'Certificate of Supervision' (See Appendix 29) and Form E (See
Appendix 31) in duplicate are duly completed and submitted before
arrangement for an inspection of the completed work can be made.
3.1
Application
3.1.1
The Registered Sanitary Plumber Shall ensure that the following accompany
the application:
(a)
(b)
3.2
Commencement of Work
3.2.1
3.2.2
3.2.3
(b)
3.3
Supervision
has given all notices and obtained all consents that may be required
by any law to be obtained from all relevant authority or persons in
respect of the sanitary works; and
has taken appropriate insurance coverage against any damage or
injury which may be caused to has given all notices and obtained all
consents that may be required by any law to be obtained persons or
property or against any other liability which may be incurred under
written law by reason of the execution of the sanitary works and
sewer connection. Such insurance coverage should be kept in force
for the entire duration of the works
3.3.1
3.3.2
3.4
Certificate of Supervision
3.4.1
3.5
4.
The Registered Sanitary Plumber shall ensure that Form B (See Appendix
28) and Form E (See Appendix 31) duly completed and Form C-'Certificate
of Supervision' by the 1Architect/Professional Engineer are submitted in
duplicate before arrangement for an inspection of the completed work can be
made.
CODE OF PRACTICE
ON
SANITARY PLUMBING AND DRAINAGE SYSTEM
PART VI : APPENDICES
(A) STANDARD DRAWINGS ON SANITARY PLUMBIGN AND DRAINAGE SYSTEM
Appendix 1 : ENV/SEW/SAN/1
Appendix 2 : ENV/SEW/SAN/2
Appendix 3 : ENV/SEW/SAN/3
Appendix 4 : ENV/SEW/SAN/4
Appendix 5 : ENV/SEW/SAN/5
Appendix 6 : ENV/SEW/SAN/6
Appendix 7 : ENV/SEW/SAN/7
Appendix 8 : ENV/SEW/SAN/8
Appendix 9 : ENV/SEW/SAN/9
Appendix 10 : ENV/SEW/SAN/10
Appendix 11 : ENV/SEW/SAN/11
Appendix 12 : ENV/SEW/SAN/12
Appendix 13 : ENV/SEW/SAN/13
Appendix 14 : ENV/SEW/SAN/14
Appendix 15 : ENV/SEW/SAN/15
Appendix 16 : ENV/SEW/SAN/16
Appendix 17 : ENV/SEW/SAN/17
Appendix 18 : ENV/SEW/SAN/18
Appendix 19 : ENV/SEW/SAN/19
Appendix 20 : ENV/SEW/SAN/20
Appendix 21 : ENV/SEW/SAN/21
Appendix 22 : ENV/SEW/SAN/22
Appendix 23 : ENV/SEW/SAN/23
Appendix 24 : ENV/SEW/SAN/24
Piping Arrangement for Floor Trap (P-Type) and Water Closet Pan
Connected in Series
Below Ground Details (Connection Between Discharge Stacks and
Inspection Chamber)
Offset and Cross Venting
Jointing of Outlet of Pedestal Water Closet Pan to Branch Drainline or Discharge Pipe
Flush Valve Installation for Water Closet Pan and Wall Hung
Urinal
Loop Venting Requirement for Wall Hung Urinals Connected in
Series
Loop Venting Requirements for Wash Basins Connected in Series
CODE OF PRACTICE
ON
SANITARY PLUMBING AND DRAINAGE SYSTEM
Appendix 25 : ENV/SEW/SAN/25
Appendix 26 : ENV/SEW/SAN/26
Appendix 27 : ENV/SEW/SAN/27
Appendix 28 : ENV/SEW/SAN/28
Appendix 29 : ENV/SEW/SAN/29
Appendix 30 : ENV/SEW/SAN/30
Appendix 31 : ENV/SEW/SAN/31
CODE OF PRACTICE
ON
SANITARY PLUMBING AND DRAINAGE SYSTEM
PART VI : APPENDICES
( C ) LIST OF STANDARD METRIC DRAWINGS AVAILABLE FOR SALE
Serial
No.
1.
2.
3.
4.
5.
6.
7.
8.
9.
Drawing Number
Description
ENV/SEW/76/2B
ENV/SEW/76/3B
ENV/SEW/76/4D
ENV/SEW/76/11
ENV/SEW/76/91A
ENV/SEW/76/92A
ENV/SEW/76/93
ENV/SEW/76/39
ENV/SEW/76/80B
10.
11.
12.
ENV/SEW/76/113
ENV/SEW/76/83
ENV/SEW/76/82-4
13.
ENV/SEW/76/114
14.
ENV/SEW/76/97