Professional Documents
Culture Documents
CONCRETE
NOMINAL MIXES
A nominal mix concrete is a prescribed concrete
It means the proportions of the ingredients are specified by the
engineer usually without testing the materials
A 1:2:4 mix concrete means a concrete consisting of 1 part
cement. 2 parts fine aggregate and 4 parts coarse aggregate by
volume
The water cement ratio may or may not be specified
There is no guarantee that a nominal mix will give a desired
strength
STANDARD MIXES
The nominal mixes of fixed cement-aggregate ratio (by volume)
vary widely in strength and may result in under- or over-rich mixes.
For this reason, the minimum compressive strength has been
included in many specifications. These mixes are termed standard
mixes.
M10, M15, M20, M25, M30, M35 and M40. In this designation the
letter M refers to the mix and the number to the specified 28 day
cube strength of mix in N/mm2. The mixes of grades M10, M15,
M20 and M25 correspond approximately to the mix proportions
(1:3:6), (1:2:4), (1:1.5:3) and (1:1:2) respectively.
VARIABLES IN
PROPORTIONING
Water-Cement ratio
Cement content or cement-aggregate
Gradation of the aggregates
consistency
ratio
PROBABILISTIC CONCEPT IN
MIX DESIGN APPROACH :
It will be very costly to have very rigid criteria to reject the
structure on the basis of a single or a few standard samples. The
basis of acceptance of a sample is that a reasonable control of
concrete work can be provided, by ensuring that the probability of
test result falling below the design strength is not more than a
specified tolerance level.
If a number of cube test results are plotted on histogram, the
results are found so follow a bell shaped curve known as "Normal
Distribution Curve".
Go back
DOE( DEPARTMENT OF
ENVIRONMENT) OR BRITISH MIX
DESIGN METHOD
Go back
EXAMPLE
For the 5 % defectives k = 1.64, and hence formula becomes
= + 1.64s
figure1
relates to a concrete having a specified characteristic
strength of 30 N /m m 2
and a standard deviation o f 6.1 N /m m 2. Hence:
Target mean strength = 30 + (1.64 x 6.1)
= 30 + 10
= 40 N /m m 2 as shown
Go back
Go back
CONTINUE
> Using this table1 find out the 28 days strength for the
approximate type of cement and types of C.A.(course aggregate )
> Mark a point on the Y axis in figure 2 equal to the
compressive strength read form table 1 which is at a water cement
ratio of 0.50.
> Through this intersection point, draw a parallel dotted curve
nearest to the intersection point. Using this curve we read the
water cement ratio as against target mean strength.
Go back
FI
G
U
R
E
2
Go back
EXAMPLE
As an example, referring to Table 1 for sulphate resisting cement,
crushed aggregate, approximate compressive strength, with a free
W/C ratio of 0.5 at 28 days is 49 MPa. In figure2 intersection point
of 49 MPa and W/C ratio of 0.50 is marked. A parallel dotted curve
is drawn to the neighboring curve. Water/Cement ratio is read off
on this new dotted curve for any target mean strength.
This Water/Cement ratio must be compared to the maximum W/C
requirement for durability (refer Table D1 or Table D2, depending
upon whether it is RCC or plain concrete).
And lower of the two is taken
Go back
STEP 3
Go back
Cement content =
The cement content so calculated should be compared with the
minimum cement content specified from the durability
consideration (Table D1 )and higher of the two should be adopted.
Sometime maximum cement content is also specified. The
calculated cement content must be less than the specified
maximum cement content
Go back
Go back
FIGURE 3
Go back
Go back
Figure 4
Go back
Figure 4 continued
Go back
Figure 4 continued
Go back
Go back
Go back
EXAMPLE
ExampleDOE Method
Design a concrete mix for a reinforced concrete work which will be
exposed to the moderate condition. The concrete is to be designed
for a mean compressive strength of 30MPa at the age of 28 days. A
requirement off 25 mm cover is prescribed. Maximum size of
aggregate is 20 mm uncrushed aggregate will be used. Sieve
analysis shows that 50% passes through 600 Sieve. The bulk
specific gravity of aggregate is found to be 2.65(by DOE or British
method)
Go back
Example 1
Go back
Example 1
Go back
Example 1
STEP 3
Decide the water content for slump of 75 mm (assumed) 20 mm
uncrushed aggregate from Table 3.
The water content is 195 kg/m3
Go back
Example 1
STEP4
With W/C of 0.5 and water content of 195 kg/m3, the cement
content is
= 390 kg/m3
(Check this cement content with that of durability requirements
given in TableD1) Minimum cement content from durability point
of view is 350 kg/m3.
Adopt greater of the two
Therefore adopt cement content = 390 kg/m3
Go back
Example 1
STEP5
Find out the density of fresh concrete from Fig.3. for water content
of 195 kg/m3
20 mm uncrushed aggregate ofsp.gr. 2.65 The wet density = 2400
kg/m3
Go back
Example 1
STEP6
find the weight of total aggregate 2400 - (195 +390) = 1815
kg/m3
Next, find the percentage of fine aggregate from Fig.4.
For 20 mm aggregate size, W/C ratio of 0.50,
Slump of 75 mm, for 50% fines passing through 600 sieve,
the percentage of FA. = 40 percent
Go back
Example 1
CONT
Weight of F A. = 1815 x40/100 = 726 kg/m3
.. Weight of C.A.= 1815-726 = 1089 kg/m3
Estimated quantities in kg/m3 :
Cement = 390
FA. = 726
C.A. = 1089
Water = 195
Wet density = 2400
The above quantities are required to be adjusted for the field moisture content
and absorption characteristics of aggregates
Lastly trial mixes are made to arrive at the correct quality of concrete.
Go back
The following data are required for mix proportioning of a particular grade of concrete:
Grade designation;
Type of cement;
Maximum nominal size of aggregate;
Minimum cement content;
Maximum water-cement ratio;
Workability;
Exposure conditions as per Table 4 and Table5 of IS 456;
Maximum temperature of concrete at the time of placing;
Method of transporting and placing;
Early age strength requirements, if required;
Type of aggregate;
Go back
Design
steps
Go back
TABLE 1 : STANDARD
DEVIATION
Go
back
STEP2 : SELECTION OF
WATER CEMENT RATIO
Water cement ratio may be
fixed by experience or that of
used in the neighboring project.
We can use the generalized
relationship established and
given in text books, one such
graph is shown
The water cement ratio
selected by whatever method
should be checked against the
limiting water
Gocement
backratio for
durability as per table D1.
TABLE 2
Go back
Go back
STEP 5 :
Approximate values for this
aggregate volume are given in
Table 3 for a water-cement ratio
of 0.5, which may be suitably
adjusted for other watercement ratios.
For every decrease of w\c ratio
by 0.05 the coarse aggregate
volume may be increased by 1.0
percent to reduce the sand
content and for every increase
of w\c ratio by 0.05 the coarseGo
aggregate volume may be
back
STEP 6
With the completion of step 5, all the ingredients have been
estimated except the coarse and fine aggregate content. As a next
step, find out the absolute volume of all the so far known
ingredients. Deduct the sum of all the known absolute volume from
unit volume (1m3), the result will be the absolute volume of coarse
and fine aggregates put together.
We know the volume of coarse aggregate and hence volume of fine
aggregate can be calculated.
Go back
l)
Example 2
= + 1.65S
From Table 1, standard deviation, s= 5 N/mm2.
Therefore, target strength = 45 + 1.65 x 5 = 53.25 N/mm2.
Go back
Example 2
Go back
3. SELECTION OF WATER
CONTENT
Example 2
From
Table 2, maximum water content =186 liter (for 25 to 50 mm
slump range) for 20 mm aggregate
Estimated water content for 120 mm slump = 186 + x 186* =203
liter (or simply increase 3% for every 25 mm slump over above
50mm slump .i.e. = 186+186*3%+186*3%+186*3%=203 liter)
Superplasticizer is assumed to reduce water content of 25 percent
. Hence, the arrived water content = 203*75% = 152 liter
Go back
STEP 4 : CALCULATION OF
CEMENT CONTENT
Example 2
Go back
Example 2
From
Table 3, volume of coarse aggregate corresponding to 20 mm size
aggregate and fine aggregate (Zone II) for water-cement ratio of 0.50 =
0.62
In the present case water-cement ratio is 0.42. As the water-cement
ratio is lower by 0.08, the proportion of volume of coarse aggregate is
increased by 0.016 (at the rate of 0.01 for every decrease in water
cement ratio of 0.05: increase in proportion =). Therefore, corrected
proportion of volume of coarse aggregate = 0.62+0.016=0.636
Since it is angular aggregate and the concrete is Pumpable , these
values should be reduced by 10 percent.
Therefore, volume of coarse aggregate = 0.636 x 0.9 = 0.572 say 0.57.
Volume of fine aggregate content = 1 - 0.57 = 0.43
Go back
STEP 6 : CALCULATION OF
MIX PROPORTIONS
Example 2
Specific
gravity =
Density of cement = ?
(mass of cement)/(specific gravity of cement)*1/1000
Volume of cement =
0.115
Volume of water = 152 liter = 0.152
Volume of chemical admixture
=(1.2*362)/(100*1.1)*1/1000
=0.004
Go back
Example 2
FINALLY
Mix proportions are:
Cement
362 kg /
Water
152 kg/
FA
846 kg/
CA
1163 kg/
0.42
Go back