Professional Documents
Culture Documents
Diqagrama de Mollier
Diqagrama de Mollier
Heating of Air
Humidifying ,
Adding Steam or Water (liquid)
Psychrometric Chart
The psychrometric chart is a variant of the Mollier diagram used in
some parts of the world.
The process transforming a Mollier diagram to a psychrometric
chart is shown below. First it has to be reflected in a vertical mirror,
then rotated 90 degrees.
evap
evap
A hc
( xs x )
cp
Condenser
Evaporator
Water liquid
Problem dryer
Heating coil
Outdoor air
A
T=+14 C
=60% RH
B
+
Wood dryer
Capacity: 500 kg/h
D
T=+40 C
=90% RH
Volume flow of moist air: 20100 m
3/h
TA 14 C , A 60 % RH
pws 1599 Pa,
959.4
0.00595 kg / kg
101325 959.4
hA 1.0114 0.00595(2502 1.84 14) 29.17 kJ / kg
x A 0.622
TD 40 C , D 90 % RH
pws 7375 Pa,
6637.5
0.04360 kg / kg
101325 6637.5
hD 1.01 40 0.04360(2502 1.84 40) 152.70 kJ / kg
xD 0.622
8314.51
Ru
(273.15 40)
T 0.04360
18.02
M
V
0.94914 m3
p
6637.5
m 1.0 0.04360
1.09952 kg / m3
V
0.94914
m
m dry air
m moist air
22100.3
21177.0 kg / h
1.0 x 1.0 0.04360
xC xD
m water in dryer
0.04360
m dry air
hC hD 152.70 kJ / kg
500
0.01999 kg / kg
21177.0
xB xD 0.01999 0.04360
0.627
x A xD 0.00595 0.04360
21177.0
(152.70 75.23) 455.7 456 kW
3600
Problem dryer
with heat pump
Cooling coil
Outdoor air
A
T=+14 C
=60% RH
C
Condenser
Wood dryer
Capacity: 500 kg/h
F
Evaporator
T=+28C
T=+40 C
=90% RH
3/h
TA 14 C , A 60 % RH
pws 1599 Pa,
959.4
0.00595 kg / kg
101325 959.4
hA 1.0114 0.00595(2502 1.84 14) 29.17 kJ / kg
x A 0.622
TE 40 C , E 90 % RH
pws 7375 Pa,
6637.5
0.04360 kg / kg
101325 6637.5
hE 1.01 40 0.04360(2502 1.84 40) 152.70 kJ / kg
xE 0.622
TF 28 C , F 100 % RH (assumed )
pws 3780 Pa,
3780
0.02410 kg / kg
101325 3780
hF 1.01 28 0.02410(2502 1.84 28) 89.82 kJ / kg
xF 0.622
8314.51
Ru
(273.15 40)
T 0.04360
18.02
V M
0.94914 m3
p
6637.5
m 1.0 0.04360
1.09952 kg / m3
V
0.94914
m
m dry air
m moist air
22100.3
21177.0 kg / h
1.0 x 1.0 0.04360
xD xE
m water in dryer
0.04360
m dry air
hD hE 152.70 kJ / kg
500
0.01999 kg / kg
21177.0
21177.0
Q L m dry air (hE hF )
(152.70 89.82) 369.89 kW
3600
Condenser xB xC 0.01999 kg / kg
0.226
x A xF 0.00595 0.02410
mix
QL
369.89
0.4804 kg / s
(h1 h4 ) (1780 1010)
Q L m R 717 (h1 h4 )
m R 717
QH
523.61
76.11 165.12 kJ / kg
21177.0
m dry air
3600
Adiabatic conditions in dryer hD hE 152.70 kJ / kg
hC
hB
21177.0
(165.12 152.70) 73.07 73 kW
3600
Wood dryer using only outdoor air consumes about 456 kW of heat
Wood dryer with a mechanical heat pump consumes
electricity 154 kW and deliviers 75 kW of heat
ps: no efficiency have been included.