You are on page 1of 2

Tel.

X Battery rack systems


Standard rack

Safts rack systems, together with Tel.X high energy density batteries, provide a robust, lighter and
reliable battery back-up solution for multiple types of telecom applications.
The modular and scalable solution systems
are available in two voltage ranges: 24 V
and 48 V systems. Available in standard
19 and 23 rack, the systems are custom
fit for the overall Tel.X battery range. The
systems are capable to host up to 5 each
48 V battery strings per rack. This
combination allows for accrued flexibility
of both foot print and back-up capacity
range most suitable for deployment in
demanding indoor environments.
With these systems, Saft is able to provide
a turnkey solution which significantly
reduces the floor loading compared to
VRLA.
Safts rack systems are delivered preassembled and pre-wired.

Applications

For wireline and wireless applications


such as:
CEV, hut and shelter
BTS (base stations)
Central Office
Customer premises

Tel.X battery
Safts Tel.X battery is a proven solution
designed specifically for telecom
applications.
Long life
High reliability
Maintenance-free
High energy density
NEBS certified

Cable harnesses and bus bar

System features
Based on standard frame width: 19 or
23
Available in 2 versions: 24 V or 48 V
Integrated bus bar(s) with polycarbonate
cover(s)
Pre-wired with: Direct Connect or SB 50
Anderson quick connect
Modular and scalable: up to 5 each 48 V
battery strings per system (or 10 each
24 V battery strings)
Scalable back-up power: from 3.6 kWh
up to 41 kWh
All levels are liquid tight
Painted grey using durable epoxy
powder-coat
Template for anchoring pattern provided

System benefits
ompact, optimized and integrated
C
solution
Significant reduction in floor loading
compared to VRLA (15 % to 40 %)
Pre-assembled and pre-wired for rapid
installation
Flexible in voltage, capacity, dimensions
and connections to answer individual
customers needs
Increased operational reliability

Battery capacities and floor loading for the standard rack systems
19" rack system without batteries
Battery model
TLX 8O
TLX 100
TLX 150
TLX 180

Rack weight without batteries


48 V [kg] 48 V [lbs] 24 V [kg] 24 V [lbs]
104
230
122
270
113
250
132
290
127
280
145
320
132
290
150
330

W [cm]
52
52
52
52

W [in]
20.5
20.5
20.5
20.5

D [cm]
42
52
71
85

D [in]
16.5
20.5
28.0
33.5

Number of strings

C8 Ah/
string

Max Wh/
string

Rack dimensions
H [cm]
H [in]
213
84
213
84
213
84
213
84

19" rack system with batteries


Battery model

TLX 8O
TLX 100
TLX 150
TLX 180

Rack weight with batteries


48 V [kg] 48 V [lbs]
506
1115
581
1280
814
1795
934
2060

24 V [kg] 24 V [lbs]
524
1155
599
1320
832
1835
953
2100

48 V
5
5
5
5

24 V
10
10
10
10

75
97
140
172

18000
23280
33600
41280

W [cm]
62
62
62
62

W [in]
24.5
24.5
24.5
24.5

D [cm]
38
42
57
68

D [in]
15.0
16.5
22.5
26.7

Number of strings

C8 Ah/
string

Max Wh/
string

75
97
140
172

18000
23280
33600
41280

Floor
loading
[kg/m2]
2400
2208
2248
2150

Floor
loading
[lbs/ft2]
492
452
460
440

The floor loading data is calculated based on the full system load.

23" rack system without batteries


Battery model
TLX 8O
TLX 100
TLX 150
TLX 180

Rack weight without batteries


48 V [kg] 48 V [lbs] 24 V [kg] 24 V [lbs]
109
240
127
280
118
260
136
300
132
290
150
330
136
300
154
340

Rack dimensions
H [cm]
H [in]
213
84
213
84
213
84
213
84

23" rack system with batteries


Battery model

TLX 8O
TLX 100
TLX 150
TLX 180

Rack weight with batteries


48 V [kg] 48 V [lbs]
517
1140
624
1375
821
1810
930
2050

24 V [kg] 24 V [lbs]
535
1180
642
1415
839
1850
948
2090

48 V
5
5
5
5

24 V
10
10
10
10

Floor
loading
[kg/m2]
2258
2460
2360
2246

Floor
loading
[lbs/ft2]
462
504
483
460

The floor loading data is calculated based on the full system load.

Notes
1. Use provided information to insure proper floor loadings are respected. Review building codes and respect proper engineering practices
before installing the battery rack systems. Always consider fully loaded battery rack systems when evaluating floor loadings.
2 Anchoring mechanism and grounding straps are not provided with the rack systems. Anchoring and grounding shall be done in
accordance with all applicable and required company as well as local, state and federal codes.
3. Saft is not liable or responsible for the improper installation of the rack systems.

Saft

Industrial Battery Group


12, rue Sadi Carnot
93170 Bagnolet - France
Tel. : +33 1 49 93 19 18
Fax : +33 1 49 93 19 64
www.saftbatteries.com

Doc. No 21808-2-0811
Information in this document is subject to change without notice
and becomes contractual only after written confirmation by Saft.
Published by the Communications Department.
Photo credit: Saft
Socit par Actions Simplifie au capital de 31 944 000
RCS Bobigny B 383 703 873
Produced in the UK by Arthur Associates Limited

You might also like