CABLE LOCATION
=
=
=
=
=
1.600
0.600
0.000
1.70
1.00
0.000
CONDUCTOR
DAILY LOAD
DUCT
FACTOR
NUMBER
YL
TEMPERATURE
(M)
(M)
(DEG C)
---
---
-------
------
-0.65
-0.50
-0.35
0.35
0.50
0.65
1.87
1.61
1.87
1.87
1.61
1.87
90.00
90.00
90.00
90.00
90.00
90.00
1.00
1.00
1.00
1.00
1.00
1.00
CABLE DESCRIPTION
*****************
,XB
,YB
,AXB
,ALB
,RHOB
XL
25.0
1.50
-----1
2
3
4
5
6
===========
ELEMENT
MATERIAL
DESCRIPTION THICKNESS
(m)
----------- ---------
-------
--------
CONDUCTOR
COPPER
SCREEN
CUSTOM
INSULATION
XLPE-UNF
RHI=3.5
JACKET
POLYETHYLENE
EXTERNAL DIAMETER
(m)
-----------------
6 SEGMENTS
TAND=0.0010
EPS=2.5
0.04400
0.00150
0.04700
0.02650
0.10000
0.00756
0.12400
0.10888
0.62000
0.37000
0.19200
0.20000
m
m
BONDING ARRANGEMENT
------------------*
*
*
*
*
1
SOLUTION CONVERGED AFTER
GEOMETRIC FACTOR:
4 ITERATIONS
2.06
ENEL
60KV - 1200 MM2 - 2T
CABLE
CONDUCTOR
DC
AC/DC
PHASE
NO
-1
2
3
4
5
6
CABLE
NO
-----
886.
886.
886.
886.
886.
886.
0.1912E-04
0.1911E-04
0.1925E-04
0.1925E-04
0.1911E-04
0.1912E-04
YCS
YCP
RATIO
YS
YA
ID
---
---
-----
--
--
-----
0.113
0.113
0.112
0.112
0.113
0.113
0.003
0.003
0.003
0.003
0.003
0.003
1.117
1.117
1.115
1.115
1.117
1.117
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
A
B
C
A
B
C
1
2
3
4
5
6
0.2129E-04
0.2128E-04
0.2141E-04
0.2141E-04
0.2128E-04
0.2129E-04
CABLE
NO
-1
2
3
4
5
6
0.2135E-04
0.2134E-04
0.2147E-04
0.2147E-04
0.2134E-04
0.2135E-04
1
CABLE RESISTANCES IN THE THERMAL CIRCUIT((C/W)/M)
T1 = INSULATION THERMAL RESISTANCE
T2 = JACKET THERMAL RESISTANCE
INCLUDING ARMOUR BEDDING THERMAL RESISTANCE
OR THERMAL RESISTANCE OF PIPE FILLING MEDIUM
IN PIPE TYPE CABLES
OR THERMAL RESISTANCE OF FILLERS AND ARMOUR BEDDING
IN TYPE SL CABLES
T3 = ARMOUR SERVING THERMAL RESISTANCE
OR PIPE COATING THERMAL RESISTANCE
IN PIPE TYPE CABLES
T4 = EXTERNAL THERMAL RESISTANCE
AT UNITY DAILY LOAD FACTOR
T4P= EXTERNAL THERMAL RESISTANCE
AT SPECIFIED DAILY LOAD FACTOR
FOR CABLES IN AIR, T4P = T4
FOR CABLES IN DUCTS, T4 AND T4P INCLUDE
THE THERMAL RESISTANCES OF THE DUCT WALL
T1
--
T2
--
T3
--
T4
--
1
2
3
4
5
6
0.484
0.484
0.484
0.484
0.484
0.484
0.072
0.072
0.072
0.072
0.072
0.072
0.000
0.000
0.000
0.000
0.000
0.000
3.154
3.142
3.285
3.285
3.142
3.154
T4P
--3.154
3.142
3.285
3.285
3.142
3.154
1
CABLE CALCULATED TEMPERATURES (DEG C)
NO
CONDUCTOR SHEATH/ ARMOUR/
EXTERIOR/
SHIELD
PIPE OR JACKET
DUCT
---------- ----------------- -------1
2
3
4
5
6
87.8
87.6
90.0
90.0
87.6
87.8
79.6
79.4
81.8
81.8
79.4
79.6
78.4
78.2
80.6
80.6
78.2
78.4
74.5
74.3
76.7
76.7
74.3
74.5