60KV - 1200 MM2 - 2T

GENERAL INPUT DATA


SELF CONTAINED CABLES IN DUCT BANK
NUMBER OF CABLES
NUMBER OF DIFFERENT CABLE TYPES.......
REFERENCE CABLE FOR CALCULATING AMPACITY
OF UNEQUALLY LOADED CABLES

6
1
1

FUNDAMENTAL OPERATING FREQUENCY .....


(HERTZ)
CONDUCTOR RESISTANCES CALCULATED PER IEC-228
AMBIENT TEMPERATURE...................
NATIVE SOIL THERMAL RESISTIVITY.......

60.0

(DEG C)
(C.M/W),

BACKFILL/DUCT BANK DATA


BACKFILL/DUCTBANK WIDTH.............. (M)
BACKFILL/DUCTBANK HEIGTH............. (M)
X LOCATION OF CENTRE OF BACKFILL/DUCTBANK, (M)
DEPTH OF CENTRE OF BACKFILL/DUCT BANK, (M)
BACKFILL/DUCTBANK THERMAL RESISTIVITY, (C.M/W)
FRACTION OF THE RETURN CURRENT IN THE
CONCENTRIC NEUTRAL OF A SINGLE PHASE CABLE

CABLE CCT PHASE CABLE


LOAD
NO
NO
ID TYPE
CURVE
INDEX
INDEX
---- ---------1
2
3
4
5
6

1
1
1
2
2
2

A
B
C
A
B
C

1
1
1
1
1
1

CABLE LOCATION

=
=
=
=
=

1.600
0.600
0.000
1.70
1.00
0.000

CONDUCTOR

DAILY LOAD

DUCT

FACTOR

NUMBER

YL

TEMPERATURE

(M)

(M)

(DEG C)

---

---

-------

------

-0.65
-0.50
-0.35
0.35
0.50
0.65

1.87
1.61
1.87
1.87
1.61
1.87

90.00
90.00
90.00
90.00
90.00
90.00

1.00
1.00
1.00
1.00
1.00
1.00

CABLE DESCRIPTION
*****************

SINGLE CORE SELF CONTAINED CABLE


COMPOSITION

,XB
,YB
,AXB
,ALB
,RHOB

XL

CABLE TYPE No. :


==============

25.0
1.50

-----1
2
3
4
5
6

===========
ELEMENT

MATERIAL

DESCRIPTION THICKNESS
(m)
----------- ---------

-------

--------

CONDUCTOR

COPPER

SCREEN

CUSTOM

INSULATION

XLPE-UNF
RHI=3.5

JACKET

POLYETHYLENE

EXTERNAL DIAMETER
(m)
-----------------

6 SEGMENTS

TAND=0.0010
EPS=2.5

0.04400
0.00150

0.04700

0.02650

0.10000

0.00756

0.12400

SKID WIRE/CONCENTRIC NEUTRAL ASSEMBLY (COPPER)


82 WIRES,
L= 0.0100
0.00194
SKIN EFFECT FACTOR AKS................. :
PROXIMITY EFFECT FACTOR AKP............ :

0.10888

0.62000
0.37000

CABLES IN DUCTBANK(DIRECTLY BURIED DUCTS)


---------------------------------CABLES IN DUCTBANK(DIRECTLY BURIED DUCTS)
CABLES IN DUCTBANK(DIRECTLY BURIED DUCTS)
POLYETHYLENE DUCT IN CONCRETE.
DUCT INTERNAL DIAMETER................. :
DUCT EXTERNAL DIAMETER................. :

0.19200
0.20000

m
m

BONDING ARRANGEMENT
------------------*
*
*
*
*

SINGLE CONDUCTOR CABLES


SHEATH CROSS BONDED
TRIANGULAR CONFIGURATION
CROSS BONDED CABLE SYSTEM
EQUAL SECTION LENGTHS

1
SOLUTION CONVERGED AFTER
GEOMETRIC FACTOR:

4 ITERATIONS
2.06

ENEL
60KV - 1200 MM2 - 2T

CABLE

CONDUCTOR

DC

AC/DC

PHASE

NO
-1
2
3
4
5
6

TEMPERATURE AMPACITY RESISTANCE


(DEG C)
(A)
(OHMS/M)
----------------87.8
87.6
90.0
90.0
87.6
87.8

CABLE
NO
-----

886.
886.
886.
886.
886.
886.

0.1912E-04
0.1911E-04
0.1925E-04
0.1925E-04
0.1911E-04
0.1912E-04

YCS

YCP

RATIO

YS

YA

ID

---

---

-----

--

--

-----

0.113
0.113
0.112
0.112
0.113
0.113

0.003
0.003
0.003
0.003
0.003
0.003

1.117
1.117
1.115
1.115
1.117
1.117

0.000
0.000
0.000
0.000
0.000
0.000

0.000
0.000
0.000
0.000
0.000
0.000

A
B
C
A
B
C

CONDUCTOR AC RESISTANCE (OHMS/M) AT ATTAINED TEMPERATURE


SKIN EFFECT ONLY
TOTAL AC RESISTANCE
-----------------------------------

1
2
3
4
5
6

0.2129E-04
0.2128E-04
0.2141E-04
0.2141E-04
0.2128E-04
0.2129E-04
CABLE
NO
-1
2
3
4
5
6

0.2135E-04
0.2134E-04
0.2147E-04
0.2147E-04
0.2134E-04
0.2135E-04

CURRENT DEPENDENT LOSSES(W/M) DIELECTRIC TOTAL LOSSES


CONDUCTOR SHEATH/ ARMOUR/
LOSS
IN CABLE
SHIELD
PIPE
(W/M)
(W/M)
--------- ------------16.84
0.00
0.00
0.08
16.92
16.84
0.00
0.00
0.08
16.92
16.84
0.00
0.00
0.08
16.92
16.84
0.00
0.00
0.08
16.92
16.84
0.00
0.00
0.08
16.92
16.84
0.00
0.00
0.08
16.92

1
CABLE RESISTANCES IN THE THERMAL CIRCUIT((C/W)/M)
T1 = INSULATION THERMAL RESISTANCE
T2 = JACKET THERMAL RESISTANCE
INCLUDING ARMOUR BEDDING THERMAL RESISTANCE
OR THERMAL RESISTANCE OF PIPE FILLING MEDIUM
IN PIPE TYPE CABLES
OR THERMAL RESISTANCE OF FILLERS AND ARMOUR BEDDING
IN TYPE SL CABLES
T3 = ARMOUR SERVING THERMAL RESISTANCE
OR PIPE COATING THERMAL RESISTANCE
IN PIPE TYPE CABLES
T4 = EXTERNAL THERMAL RESISTANCE
AT UNITY DAILY LOAD FACTOR
T4P= EXTERNAL THERMAL RESISTANCE
AT SPECIFIED DAILY LOAD FACTOR
FOR CABLES IN AIR, T4P = T4
FOR CABLES IN DUCTS, T4 AND T4P INCLUDE
THE THERMAL RESISTANCES OF THE DUCT WALL

AND THE DUCT FILLING MEDIUM


CABLE
NO
--

T1
--

T2
--

T3
--

T4
--

1
2
3
4
5
6

0.484
0.484
0.484
0.484
0.484
0.484

0.072
0.072
0.072
0.072
0.072
0.072

0.000
0.000
0.000
0.000
0.000
0.000

3.154
3.142
3.285
3.285
3.142
3.154

T4P
--3.154
3.142
3.285
3.285
3.142
3.154

1
CABLE CALCULATED TEMPERATURES (DEG C)
NO
CONDUCTOR SHEATH/ ARMOUR/
EXTERIOR/
SHIELD
PIPE OR JACKET
DUCT
---------- ----------------- -------1
2
3
4
5
6

87.8
87.6
90.0
90.0
87.6
87.8

79.6
79.4
81.8
81.8
79.4
79.6

78.4
78.2
80.6
80.6
78.2
78.4

74.5
74.3
76.7
76.7
74.3
74.5