April 22, 2015

MR. JEONY BIGAY:

We hereby inform you about the incident that happened last April 12, 2015.
During my sign on, eight modules of the transmitter has been damaged. As I tried
to troubleshoot the problem, I managed to discover that the CENECO (Central
Negros Electric Cooperative) was supplying high single phase voltage instead of the
required three-phase voltage.
The day after the incident, CENECO conducted an online site testing and
found out that the transformer was defective due to the fact that it has been almost
20 years. It was also discovered that the connectors are corroded and the insulating
oil of the transformer has dried up. These cause the inefficient performance of the
transformer thus, supplying unstable voltage to the transmitter.
This list consist of the following items to be bought given by the CENECO:
Retightening and replacement of transformer accessories
-

20m
20m
3pcs
6pcs
3 set
3 set
3pcs

4/0 Copper Wire


#6 Stranded Copper Wire
Hot Wire Clamp
350HYD Connector
Disconnecting Cut Out
Lightning Arrester
300HYD Connector

Labor: P10, 000.00

RANEL
BAGONOC
TEHCNICAL
DIRECTOR