I. INTRODUCTION
VII. REFERENCES
[1]
[2]
V. IMPLEMENTATION ISSUES
The omission of the required anti-aliasing filter defined in
the standard is one of the most often observed reasons why
harmonic / interharmonic measurements (especially current
measurements near power electronic devices) fail to compare
with a known good reference instrument. The mains
synchronization mechanism is another common source of
measurement error when not properly implemented (or
omitted).