F0107

2012 Tyco Safety Products, All Rights Reserved.

How to Upgrade a 4100ES


Panel and Related .BIN Files
4100ES

(Adobe Reader 9 or later is required to correctly view


this document Click here to download the free viewer )

Follow these steps and click the corresponding movie to view the
procedure for upgrading a 4100ES Panel and its related .BIN files.
1. From the ES Programmer, click Transfer, Network, and then Local Panel.
File Transfer software opens.
2. Click the CFIG and all Execs radio button and then the Download button.
3. If necessary, use the Browse button to set the .BIN file path.
4. Verify and, if necessary, select the appropriate Load check boxes for the files to be downloaded.
5. Click the Download button and the files are downloaded to the Master Controllers Compact Flash Memory.
The files are then automatically transferred to the appropriate Slave Cards.
6. When the transfer process is complete, click the Close button and then Close again to exit File Transfer.

See the suite of 4100ES Tutorials


F0071 through F0106.

To give us feedback, click here.

International Trade Controls and Restrictions


This material may contain information or technology the export or re-export of which is restricted by U.S. laws and regulations. By viewing this material, the recipient agrees to the following: (i) the recipient's use of the
contents of this material shall comply with all applicable laws, rules and regulations, including, without limitation, U.S. international trade laws and regulations, and (ii) the recipient may not transfer or otherwise export or
re-export any information or technology contained in this material except in full compliance with the export controls administered by the U.S. and other countries and any applicable import and use restrictions.

You might also like