Deluge Valve (Assembled Trim - supplied loose)

1. A. Deluge Valve
Type

Inbal make (Assembled trim - supplied loose)

Design Particulars
Model No.
Inlet End
Outlet End
Size
Pressure rating
Temperature (water)

:
:
:
:
:
:

799D
Wafer
Wafer
4 in.
21 bar (max) & 1.5 bar (min)
65 deg. C

Material of Construction
Valve Housing
Valve Ends
Sleeve

:
:
:

Coating
Union (1/2)
Plug (1/4)

:
:
:

Carbon steel
Ductile Iron
SMR5 Elastomer reinforced with Polyester
and Kevlar
Powder Epoxy coated (0.1 mm)
St.St.304
St.St.304

B. Deluge Pilot Valve


Model No.
Ends
Pressure rating
Temperature (water)
Material
Flow Factor (Kv)
Nipple 2

:
:
:
:
:
:
:

296-08
4 ports (1/2 in.)
21 bar (max)
80 deg. C
Brass, Ni-Cr plated
1.9
St.St.304

:
:
:

393-02
163mm x 140mm x 62mm
21 bar (max)

:
:
:

1/2 in. NPT, female


1/2 in. NPT, male
1/2 in. NPT, female

:
:
:

Brass, Ni-Cr plated


Stainless steel 304
1mm stainless steel, red polyester coated

C. Emergency Release Station


Model No.
Enclosure Dimension
Pressure rating
Ends
Pressure
Vent
Common
Material
Emergency Release valve
Pipe Nipple
Enclosure

D. Water supply Unit (ball valve + strainer+ check valve)


Model No.

351-08-02 + 31-08-01 + 371-08-01

Strainer
Pressure rating
Temperature (water)
Flow Factor (Kv)

:
:
:
:

30 mesh, Stainless steel screen


21 bar (max)
80 deg. C
0.86

Ends
Inlet Port
Outlet Port

:
:

1/2 in. NPT, female


1/2 in. NPT, male

2. Deluge Release Cabinet (Supplied Preassembled)


A. Deluge Release Cabinet
Model No.

B. Pressure Gauge
Range

C394-Q3436

Make
General

:
0-16 Kg/cm2. And 0-10 kg/cm2 (air Pressure
gauges)
:
WIKA
:
PG to be provided into the cabinet

C. Solenoid Valve
Rating
Make
Minimum Area Classification Required
Approvals

:
:
:
:

24 V DC (2-8 kg/cm2)
ASCO
Zone 2, IIB, T3
ATEX, Ex ia IIC T6 (IP65)

D. Pressure Switch
Make
:
Minimum Area Classification Required :
Approvals
:

UE
Zone 2, IIB, T3
UL, CE, EX, Ex ia IIC T6 (IP66)

E. Air Pressure Regulator


Range
Make
Body Size
Construction

0.5-8.7 Kg/cm2
Norgren
1/2"
Relief type

3. Painting
Finish (except deluge pilot valve)

:
:
:
:

Two coats of epoxy primer followed by Fire red


paint. (For Deluge pilot valve - Natural
polished & Chromium plated)

4. Markings/Stamping

Name of Manufacturer
Year of Manufacture
Equipment Model no. & Serial no.
Size
FM mark

5. Inspection
Visual Inspection

100%

6. Approvals

FM Approved

7. Documents to be submitted
Test Pressure

Internal Test pressure

Material certificate
Drawing
Catalogue

:
:
:

Lab certificate
Detailed drawing
Complete catalogue containing
maintenance and operation manual.

8. Testing & Acceptance


Performance Test

Hydraulic Test: 21 kg/cm2