You are on page 1of 4

  TMSw    TMSd 

w :=
i  0.14⋅  if i ≥ Ifault  D :=
i 0.14⋅  if 11462 > i > Ipickup2
   Ifault 
0.02
    i 
0.02 
  I  − 1   I  − 1
   pickup      pickup2  
   TMSd 
  TMSw 
0.14⋅  if Ipickup ≤ i ≤ Ifault 0.14⋅  if i > 11462
  0.02     11462 
0.02

  i    I  − 1
 I  − 1
   pickup      pickup2  
 0.05 if i ≥ 1600  0 otherwise
 
 0 otherwise 
 TMSg   TMSg 
GG :=
i
0.14⋅  if 11462 > i > Ipickup2 DD :=
i
0.14⋅  if 20462 > i > Ipickup3
  i 
0.02
   i 
0.02

 I  − 1  I  − 1
  pickup2     pickup3  
 TMSg   TMSg 
0.14⋅  if i > 11462 0.14⋅  if i > 20462
  11462 
0.02
   20462 
0.02

 I  − 1  I  − 1
  pickup2     pickup3  
0 otherwise 0 otherwise

 TMSf 
DF := 13.5⋅  if 1210 > i > Ipickup5
i   i  − 1
 I  
  pickup5  
 TMSf 
13.5⋅  if 1575 ≥ i > 1210
  1210  − 1
 I  
  pickup5  
0.08 if i ≥ 1575
0 otherwise
10000

1000

100
Time of Optn.

10

0.1

0.01
100 1000 10000 100000

Current
11KV O/G FEEDER
11KV BUS SECTION
11KV PBB
66kV BUS SECTION
ET 1&2
i := 401 .. 40000
TMSw := 0.4 TMSd := 0.3 CTRw := 400
TMSg := 0.25
Ipickup := 400 Ifault := CTRw⋅ 20
Ipickup3 := 3200
Ipickup2 := 4000 Ifault2 := 11462
Ifault3 := 20926

TMSe := 0.50 Ipickup4 := 525 Ifault4 := 11462


TMSf := 0.80 Ipickup5 := 125 Ifault5 := 1210

 TMSd 
D :=
i 0.14⋅  if 11462 > i > Ipickup2
  i 
0.02

 I  − 1
  pickup2  
0 otherwise

13.5⋅ 
TMSe
DE := if 11462 > i > Ipickup4
i
  i  − 1
 I  
  pickup4  
13.5⋅ 
TMSe
if 17720 ≥ i > 11462
  11462  − 1
 I  
  pickup4  
0.1 if i > 17720
0 otherwise
4
2953⋅ 6 = 1.772 × 10