Terminology
1. Cable
A single standard conductor with insulation and protective covering or two or more such
conductors laid-up together.
2.1.2 Core
A single conductor with its insulation but not including protective covering. (Core
is called conductor in USA).
A cable may be:
- Single core or single conductor type.
- Double core or two conductor type.
- Multi core or Multi-conductor type.
2.1.3 Screened cable or shielded cable
A cable in which each conductor is separately enclosed in a conducting films in
order to ensure even distribution radial electric field surrounding the conductor. It
also limits electromagnetic field beyond the shield to low value, minimise surface
voltage stress on conductor surface & reduces shock hazards when shields are
properly grounded. These conducting films have electrical connection with each
other and with the metallic sheath/armour of the cable which is usually earthed.
The cable does not have metallic shield or screen over insulation.
Metallic sheath immediately under the lead sheath and connected to it.
Lead Sheath
A protective lead cover over the insulation for excluding moisture from conductor
and insulation. Sheath is made of commercially available pure lead or lead with
small amount of hardening alloy. Sheath should be of non-magnetic material. It
serves as a return path to fault current.
A sheathing over insulation of a cable to form outer protective cover of tough rubber
mixed with hardening substance and suitably vulcanised to make it water proof and
resistant to decay, mechanical abrasion, acids, alkalis and other corrosive material.
1. Armour
Metallic wrapping (usually tape or wires) over the sheath for the purpose of mechanical
protection. In single core cable, armour should be of non-magnetic material.
In three-core cable, common armour is provided for all the three cores and the
material of armour may be Galvanised steel.
1. Belt
1. Belted cable
A Multi-cored cable in which part of the insulation is on each conductor individually and
remainder is in the form of overall belt.
A layer of fibrous material (permeated with water proof compound) on external surface
along with layers of water proof compound serving is the outermost non metallic water
proof covering over the armour. Serving may be water-proof, corrosion proof,
mechanical abrasion proof etc.
1. Braiding of a cable
1. Filler
An insulating material such as treated hemp, synthetic rubber, thermo plastic material
etc., which is used for filling up the space inside the sheaths / shield to fill-up the gaps.
1. Jacket/Sheath/Covering
It is provided over the insulation for mechanical protection, to avoid moisture entry, &
provides a return path of fault current in cables with metallic sheath.
Metallic Sheath : Lead or Aluminium.
Non-metallic Sheath : Rubber or Plastic.
1. Insulation
Part of the cable which provides insulation over individual conductor and or over a group
of insulated conductors.
The cable filled with oil (in the central duct) and does not need any external pressure
system.
Jointing
6.1 GENERAL
- The conductivity of the joined conductor is not less than that of an equivalent
length of enjoined conductor, and the conductivity of the enclosing metallic
sheath and armouring is maintained unimpaired.
- The insulation of cable is maintained and at the joint is not less effective than
that of the cable cores.
- The joint will withstand the mechanical stresses imposed by a short-circuit and
the thermal effects of normal or fault currents.
Physical inspection of the joints where the possible helps us to ascertain the
healthiness of the Joints. Physical indications like crack, leakage of oil bitumen
compound of noise of partial discharge give unhealthy symptoms of the joints. In
such cases, Joint may fail in near future and hence preventive action is invited.
This is normally used for jointing a service cable to the main distribution cable in
city distribution network.
The basic types of cable jointing accessories available in the country, at present
are :
a) Joint sleeves with insulating and bitumen based filling compound suitable for
jointing cables of voltages up to and including 33 kV.
b) Cast resin based cable accessories suitable for jointing cables of voltages up
to and including 11 kV.
Note:- Other accessories; such as heat shrinkable tubes, taped joints and slip on
(pre-moulded) joints are also in use.
c) Plumbing metallic sleeve or wiping gland to the lead sheath of the cable to
prevent moisture from entering the joint,
e) Fixing a cast iron or any other protective shell around the joint filling the same
once again with molten bitumen compound.
It comprises:
b) Wiping dry - The core insulation should be wiped dry and all parts, which are
to be embedded in casting resin should be roughened and cleared with relevant /
degreasing agents,
c) Fixing two halves of mould around the cable joints or ends and sticking them
together and sealing to form a leak proof cast mould,
f) Removing plastics mould. In case of buried joint, the plastics mould may be left
intact.
6.3 GENERAL INSTALLATION GUIDELINES
Joint Position
During the preliminary stages of laying the cable, consideration should be given
to proper location of the joint position so that when the cable is actually laid the
joints are made in the most suitable places. There should be sufficient overlap of
cables to allow for the removal of cable ends which may have been damaged.
This point is extremely important as otherwise it may result in a short piece of the
cable having to be included. The joint should be near pipe end or at the bend.
Joint Pits
When two or more cables are laid together, the joints are arranged to be
staggered so as to reduce the excess width of trench and also be isolate the
joints from each other and reduce the possibility of one joint failure affecting the
other joints.
Sump Holes
Tents
As far as possible a tent should be used where jointing work is being carried out
in the open.
When a cable which is in service is cut for making a joint, normally it is first
isolated, discharged, tested and earthed, before proceeding further, although
work on live conductors is permissible under certain conditions. The test lamp is
one of the apparatus used to determine whether the cable is 'alive' or 'dead'. The
jointer should wear rubber boots or gloves or stand on a rubber mat. When
rubber mats are used in wet holes, pieces of board should be placed under the
mat and water should not be allowed to creep over the edges of the mat.
Before cutting the cable prior to making a straight joint, the most convenient core
to be cut (the neutral should always be cut last) should be selected, and
separated from the others by means of a wooden wedge. A small piece of rubber
insertion should then be placed between the core to be cut and the remaining
cores and cut through the selected core. The cut ends should be separated and
tested to ascertain if either or both are live or dead. Irrespective of being live or
dead, both ends should be taped as a measure of safety. The same procedure
should be followed with the remaining cores. It is advisable to step the positions
of the cuts, so that it is impossible for the hacksaw, knife or any other tools which
may be in use to cause a short circuit by coming into contact with two or more of
the cut ends simultaneously.
Before making conductor joints, the lead sheath and armour should be wrapped
with insulating material - an old bicycle inner tube is useful for this purpose. The
precaution will prevent a 'short' to earth if a tool slips between the live conductor
and the sheath or armour neutral conductor should be joined first.
In the case of baring of the conductors for 'tee' and 'service' joints where
conductors are not cut, the jointer should be instructed to remove sufficient
armouring and lead sheathing for making a joint in the most suitable position.
The cores of the cable to be tee-jointed should be spread and suitable tapping
positions selected on the main cable. The most convenient core to be teed
should be selected and separated from others by means of a wooden wedge (as
far as possible, the neutral should be selected first). A rubber insulation should
be inserted between this core and the rest and prepare the core for tee-jointing.
The paper insulation of the main cable core should be cut for a suitable length
and the jointing work completed. Rubber insertion between this core and the rest
should not be removed till this exposed core is completely taped. This process
should be repeated for other cores taking care that only one core is handled at a
time.
All jointing accessories and materials such as solders, plumbing metal, lead
sleeves, ferrules and bitumen compound should be in accordance with the
relevant Indian Standards, wherever such standards exists.
These joints are preferably done using cold setting casting resins, primarily
because of thermoplastic nature of insulation and sheath. Cast iron boxes with
bitumen based filing compounds can be used with PVC cables with certain
precautions.
Typical drawings for cast resin and bitumen compound filled straight through
joints are shown in enclosed Figure A.
For 1.1 kV grade, moulds conforming to relevant Indian standard should be used.
For voltages above this neither moulds nor casting resins are standardised.
Hence cable supplier may be consulted for his advice on selection.
While jointing control cables having large number of cores jointing of proper
cores should be ensure. Core identification should be properly studied for this
purpose.
For XLPE cables up to 3.3 kV (un-screened), these joints are done by using cold
setting casting resins in suitable moulds.
A typical drawing of straight through joint for HT (high tension) screened type
XLPE cable is shown in Figure B.
These joints should be restricted to 1.1 KV grade cables. Tee joints on HT cables
up to and including 11 kV may be done only in exceptional cases.
These joints are made either using cast resin kits or C.1. Boxes with cast resin
kits for PVC and XLPE cables.
For PVC cables up to 11 kV cast resin end termination's are recommended both
for indoor and outdoor connections.
Indoor termination's in dry and non-corrosive atmosphere for 1.1 kV grade can
either be done by means of brass glands or by simple dressing.
A typical drawing of 6.6 kV (UE), indoor type cable termination on XLPE cables is
given in Figure C1.
6.7 ALUMINIUM CONDUCTOR CONNECTIONS
Fluxless Friction Solder Method - In this method each strand of the conductor is
carefully cleared and scraped with scraper tongs to remove oxide film. Then all
the strands are tinned by rubbing a special friction solder stick over the heated
strands. This is known as metallising. Aluminium conductor thus prepared may
be soldered on to copper cable lugs, ferrule, terminal studs using 60 percent
solder. No flux is used in any of the operation. This method is not recommended
for jointing conductors in XLPE cables.
The copper ferrule, which is generally of a weak-back type, should be tinned and
fitted on to the conductor and closed firmly but not completely.
The ferrule should then be basted with solder and the gap should be filled in with
the solder. The ferrule then be closed firmly and basted with solder, till the solder
solidifies. The excess solder should be wiped off and the joint allowed to cool.
During jointing operation copious fumes are given off when the flux is heated.
These fumes contain small quantities of fluorine and it is, therefore, advisable to
avoid inhaling them as far as possible. It is also recommended that proper
ventilating be maintained at the place of jointing.
Organic fluxes tend to char and are rendered ineffective when exposed to
temperature in excess of 300 C. Emphasis should, therefore, be laid on the
need to control pot temperature.
Welding Method - Welding method gives the best possible results. Welded
conductor joints have lesser resistance and equal or better mechanical strength
than the conductor itself. Welding, therefore, should be given preference for all
larger cross sections. For smaller cross section welding may not always be
feasible or economical. In this method the end of the stranded conductor are first
welded to the cable lug, terminal stud or to each other, in open or closed mould
using aluminium welding rods or strands taken from conductor. After cooling
welded connections are filed smoothened and cleaned.
The metal sheath, metal screen (if any) and armour of any cable should be
efficiently earthed at both ends.
In case of single-core cables of larger sizes, the armour, lead sheath metal
screen, if any, is bonded at times only at one point. Intention is drawn in this case
to the presence of standing voltages along armour or lead sheath and to the
considerable increase in such voltages when cables carry fault currents. These
voltages must be taken into count when considering safety and outer sheath
insulation requirement.
All metal pipes or conduits in which the cables have been installed would be
efficiently bonded and earthed.
Where cables not having metallic sheath are used, embedding additional earth
electrodes and connecting the same with steel armour cable becomes
necessary.
1. Introduction
Since the late nineteen sixties, the electricity supply industry has installed over five
million heat shrinkable cable termination's and straight through joints throughout the
world for distribution voltage up to 33 kV.
The long-term performance of these numerous installations in some of the most
demanding conditions led to widespread acknowledgement of the reliability and
ease of application of the heat shrinkable cable accessories.
6.9.2 Cable Accessory Requirements
A cable accessory has to perform a number of basic functions. These may be
analysed as follows :
Stress Relief
The design of a termination or joint must provide for the control of the electrical
stresses in the insulation used. This is essential to ensure a long service life and
prevent damaging partial discharges.
Insulation
Joints must re-insulate the cables with high quality dielectric grade insulation and
termination's require protective insulation able to withstand the rigors of sunlight,
humidity, pollution, and surface electrical effects with tracking.
Environmental Seals
The accessory must be capable of fully sealing the cable against the ingress of
moisture. The failure mechanism of plastic insulated cables through water treeing
is now well understood.
Various technologies have attempted to satisfy the above functions using
different approaches as below.
- field engineered designs such as tape wrapped designs, resin filled designs.
- factory engineered designs such as pre-moulded and cold shrink.
The field engineered designs accommodate variations in cable dimensions found
on site but are subject to the variables of assembly in the field and are extremely
sensitive to installer's skills. These accessories have limited shelf life, especially
in tropical climates. Factory engineered designs remove site variables of
assembly, but are different to seal from environment and may require strict
tolerance on cable dimensions which is difficult in cables available in India.
6.9.3 Heat Shrink Technology - A Modern Technology
Heat shrink technology has succeeded in combining the versatility of field
engineered design and the reliability of factory controlled manufacture to meet
the above functions. Heat shrink systems are highly tolerant of variations in cable
dimensions, types and cable stripping dimensions and are manufactured under
closely controlled factory conditions.
A good heat shrinkable cable necessarily requires combination of the following
advanced technologies :
a) Cross-linked Polymers.
Certain plastics, or polymers, acquire enhanced properties when subjected to
high-energy electron-beam radiation's. During this process, their chain-like
molecules bond together "cross-link" at random points. When exposed to high
temperatures, the cross-linked material will become elastic, but will no longer
melt. At low temperatures, it remains flexible, yet resistant to both chemical and
physical abuse. Cross-linked polymers play a central role in many cable
accessories.
b) Elastic Memory
If a plastic is formed into a particular shape before being cross-linked, it will
return to, or "remember" that shape after cross-linking when heated, no matter
how it is expanded or deformed.
c) Adhesives
The adhesives which are incorporated into many heat shrinkable products fall
into two basic categories; hot melt thermoplastics and thermo sets. When
heated, a thermoplastic will melt and flow, providing a durable, watertight seal.
The material can be re-heated, many times without undergoing a chemical
change. A thermo set, however, cures chemically when its two components are
mixed. Once cured, it is infusible and insoluble, and thus well suited to high
temperature environments.
d) High Performance Polymers
A good heat shrinkable cable accessories should include special synthesised
polymers which should offer exceptional mechanical strength as well as
protection against harsh environmental conditions. These rugged materials
should be characterised by their light weight, high heat deflection temperatures
and extraordinary versatility.
6.9.4 Design Basis
It is interesting to look at how heat shrinkable termination's and joints meet the
basic requirements of cable accessories discussed above.
6.9.5 Termination's
Stress control is provided in high voltage cable termination's for one primary
purpose; that is to control the stress which exists at a point where the screen or
shield is terminated. If no form of stress control were applied, discharges could
occur and the life of the termination would be limited depending on the stress at
the end of the screen and the discharge resistance of the primary dielectric but
would typically not exceed one year. Some form of stress control is therefore
required at the termination of all screened power cables which have been
designed to operate at 5kV or higher voltage to eliminate discharge activity
during operation.
To relieve these stresses, a heat shrinkable tubing with correct electrical
characteristics is applied from the end of the screen over the cable dielectric for
an appropriate distance. This layer is coupled capacitively to the conductor. This
reduces the electrical field strength along the end of the cable. In other words,
the voltage drop per centimetre is well below the value of the breakdown in air.
It is essential that in heat shrinkable stress control tubing provided has stable
impedance over the typical operating temperature range of a cable in service.
Further, impedance of the material also should remain constant when aged to
100 Degree. C for more than 10,000 hours.
The outer surface of the termination is protected by a non-tracking and erosion
resistant material. It is formulated and tested to be stable under the extremes of
climate and resistance to the effects of the UV radiation in sunlight.
Condensation, rain or pollution will cause leakage currents to flow on the surface
of the termination's. It is essential that materials used do not track. Tests of
varying degrees of severity are available to demonstrate the effectiveness of an
outdoor material. These include the ASTM-D-2303, Inclined Plan Tracking and
Erosion test and Atlas Weather-O-Meter test.
Pre-coating the moulded sheds and gloves with heat activated adhesive / sealant
ensures positive seals between the cable and the termination.
In short: A cable termination must provide:
(a) A stress relieving function.
(b) An outer non-tracking, erosion and weather resistant surface and
(c) Be fully sealed.
Summary
The following shall be checked / ensured.
a) Identification number tags of the cable for the equipment to which the supply is
fed are provided correctly at both ends of the cable.
b) The tag size is not less than 2 mm thick and 20 mm wide and of enough length
to contain all required details.
c) Cable termination is done with proper crimping lug and use of antioxidant
paste.
d) For cable glands of flameproof design, identification mark on the gland
preferably embossing symbol as per IS should be available, and the required
CMRS certification is verified.
e) The ferruling on all termination's conforms to wiring drawings.
f) Tightness of all termination's. (Confirm the bimetallic washer, if required, is
correctly installed.)
g) Earthing connections and earth continuity are in order.
h) Wherever lugs are used for termination, size of lug matches with cable core
and material of lug is suitable for application.
i) Proper mechanical protection for the cable is available.
j) Pipes, if provided, are sealed at both ends.
k) Bending radius is as per BIS standard.
l) Before back filling cable trench, the straight through joints of High Tension
cables are tested for leakage current.
m) Cable termination's are done as per the manufacturer's instructions.
n) Insulation resistance values between phases and phase to ground (after
termination) are in order.
o) Cable near the termination are supported to relieve the strain on the terminals.
7.0
TESTING OF CABLE INSTALLATION
7.1 TESTING AND ELECTRICAL MEASUREMENTS OF CABLE
INSTALLATIONS (IS 1255 - 1983).
Insulation Resistance Test on Newly Installed Cables Before Jointing -
All new cables should be tested for insulation resistance before jointing. After
satisfactory results are obtained cable jointing and termination work should
commence. The test is meant to reveal gross insulation fault(s). A fairly low
insulation resistance reading compared to the values obtained at factory should
not be a cause of worry since the insulation resistance varies greatly with
parameters such as length and temperature. This is particularly more
pronounced in the case of PVC cables. The voltage rating of the insulation
resistance tester for cables of different voltage grades should be chosen from the
following table :
Voltage Grade of Cable Voltage Rating of IR Tester
1.1 kV 500 V
3.3 kV 1000 V
6.6 kV 1000 V
11 kV 1000 V
22 kV 2.5 kV (see Note)
33 kV 2.5 kV (see Note)
Note - For long feeders, motorised insulation resistance tester should be used.
More accurate insulation resistance values can be measured only by a portable
resistance measuring bridge.
7.2 TEST RESULT OF COMPLETED CABLE-INSTALLATION
The test of completed installation may be measured and entered into record book
for comparison purpose during service life of cable installation and during fault
location.
7.2.1 Insulation Resistance
Insulation resistance is measured by a suitable bridge. In non-screened cables,
the insulation resistance of each core is measured against all the other cores and
armour / metal sheath connected to earth. With screened construction the
insulation resistance of each core is measured against all the other cores and the
metal screen connected to earth.
7.2.2 Conductor Resistance (DC)
The resistance of conductor is measured by a suitable bridge. For this purpose
conductors at other end are looped together with connecting bond of at least
same effective electrical cross-section as conductor. The contact resistance is
kept to a minimum by proper clamped or bolted connections. With properly
installed and jointed cables, values thus measured and corrected to 200 C, are in
general agreement with values given in test certificates.
The measured loop resistance is converted to ohms per km per conductor as:
R
Rt = ------
2L
Where
R = measured loop resistance in ohms at temperature, t0 C;
Rt = measured resistance per conductor at t0 C in ohms; and
L = length of cable (not the loop) in km.
The ambient temperature at the time of measurement to be recorded and the
conductor resistance to be corrected to 200 C by the following formula :
Rt
R20 = ----------------- ohm / km at 200 C
(I + ) (t - 20)
Where
R20 = conductor dc resistance at 200 C
t = ambient temperature during measurement in 0C, and
= temperature coefficient of resistance
(3.93 x 10_ ohms / 0C for aluminium).
7.2.3 Capacitance
For unscreened cables, capacitance is measured for one conductor against
others and metal sheath / armour connected to earth. Case of screened cable it
is measured between conductor and screen. Capacitance bridge is used for this
purpose. This measurement may carried in case of cables above 11 kV;
alternatively values given in the certificate are considered sufficient.
7.2.4 High Voltage Test
Cables after jointing and terminating are subjected to high voltage test. The
recommended values of test voltages are as under. The leakage current shall
also be measured and ordered for future reference.
TABLE 6 DC TEST VOLTAGES AFTER INSTALLATION (BEFORE COMMISSIONING)
RATED VOLTAGE TEST VOLTAGE BETWEEN DURATION
OF CABLE
Any Conductor and Conductor to
Metallic Sheath / Conductor (For
Screen / Armour Un-screened Cables)
Uo / U
kV kV kV Minutes
(1) (2) (3) (4)
0.65 / 1.1 3 3
1.9 / 3.3 5 9
3.3 / 3.3 9 9
1. / 6.6 10.5 18
2. 6.6 / 6.6 18 18 5
6.35 / 11 18 30
11 / 11 30 30
12.7 / 22 37.5 -
19 / 33 60 -
Generally DC test should be preferred as test equipment required is compact,
easily portable and power requirements are low.
The cable cores must be discharged on completion of DC high voltage test and
cable should be kept earthed until it is put into service.
DC test voltage for old cables is 1.5 times rated voltage or depending on the age
of cables, repair work or nature of jointing work carried out, etc. In any case, the
test voltage should not be less than the rated voltage. Test voltage in these
cases should be determined by the engineer-in-charge of the work.
It may be noted that frequent high voltage tests on cable installations should not
be carried out. This test should be carried only when essential. During the high
voltage test, all other electrical equipment related to the cable installation, such
as switches, instrument transformers, bus bars, etc., must be earthed and
adequate clearance should be maintained from the other equipment and
framework to prevent flash over.
In each test, the metallic sheath / screen / armour should be connected, to earth.
7.3 CABLE INSTALLATION PLAN
On completion of laying, terminating and jointing of the cables, a plan should be
prepared, which should contain the following details of the installation.
a) Type of cables, cross-section area, rated voltage. Details of construction,
cable number and drum number;
b) Year and month of laying;
c) Actual length between joint-to-joint or ends;
d) Location of cables and joints in relation to certain fixed reference points, for
example, buildings, hydrant, boundary stones, etc.;
e) Name of the jointer who carried the jointing work;
f) Date of making joint; and
g) Results of original electrical measurements and testing on cable installation.
All subsequent changes in the cable plan should also be entered.
General Construction
3.1 CONDUCTORS
The conductors of power cables are normally made from electrical purity
aluminium, and those of control cables are of annealed high conductivity copper.
However, copper conductor power cable can also be supplied. All conductors
conform to IS:8130-1984.
A point to be noted here is that for conductors for fixed installation (Class 1 and
Class 2), IS:8130 - 1984 specifies only the minimum number of wires and the
maximum d.c. resistance of the conductor at 200 C for a particular cross-section;
the diameter of the wire is not specified.
Normally, aluminium conductors up to size 10 sq. mm. are solid circular in cross
section, and sizes above 10 sq. mm. are stranded. In case of single core and
twin core cables up to 50 sq. mm., they are circular in cross section while for 3
core and 4 core cables, conductors of cross section 25 sq. mm. and above are
normally sector shaped.
11 kV PVC insulated cables are designed with cores having round compacted
stranded conductors.
3.2 INSULATION
The conductors are insulated with the high quality PVC base compound. Cables
with Heat Resisting Insulation are also available for maximum operating
conductor temperature of 850 C for 1.1 kV grade cables.
1. Colour Scheme :
Cores are identified by colour scheme of PVC insulation. The following colour scheme is
normally adopted :
1 core - Red, Black, Yellow, Blue or Natural (non-pigmented)
2 core - Red and Black
3 core - Red, Yellow, and Blue
4 core - Red, Yellow, Blue and Black (also 3-1/2 core) (reduced neutral core is
black)
5 core - Red, Yellow, Blue, Black and Grey
For cables having more than 5 cores :
Two adjacent cores (counting and directional) in each layer are coloured blue
and yellow respectively and the remaining cores are grey.
Alternatively cores with number printing can be offered. For 11 kV PVC/XLPC
cables, cores shall be identified by means of number printing tape.
1. Inner Sheath :
For all cables having two or more cores, a common covering (inner sheath) is applied
over the laid up cores either by extruded sheath of un-vulcanised rubber/PVC compound
or wrapping of plastic or proofed tapes. Single core cables do not have inner sheath.
1. Armouring :
For multi-core cables, armouring is applied over the inner sheath. In case of cables where
fictitious diameter over the inner sheath does not exceed 13 mm., the armour consists of
galvanised round steel wires; above this size, normally the armour is of galvanised
formed steel wires.
Armouring of PVC mining cables consists of galvanised round / formed steel
wires, but wherever necessary, a few tinned copper wires / strips are also
included to meet the resistance requirements of armouring for mining cables as
specified in IS:1554 (Part 1 & 2) 1988.
For single core armoured cables, non magnetic armouring is provided.
1. Outer Sheath :
Outer sheath of PVC is extruded over the armouring. In case of multi-core unarmoured
cables, over the inner sheath, whereas, in case of unarmoured single-core cables, it is
extruded over the insulation. This is always black in colour for best resistance to outdoor
exposure. Any other colour can be available on request.
The manufacturer's name and trademark along with the year / year code of
manufacture are embossed on the outer sheath; additionally in the case of LT
cables, the word 'ELECTRIC' and in the case of HT cables, the voltage grade is
also embossed. In case of LT cables with Heat Resisting Insulation, the word
"HR 85" is also embossed. In the case of mining cables, the word MINING is
added in the embossing script. The embossing script repeats in such a way that
every meter of the cable be are the same script.
3.4 TYPE DESIGNATION
Type designated of PVC Cables is based on the following alphabetical
nomenclature.
A - Aluminium conductors - when first letter of type designation. When type
designation does not contain 'A' in the beginning, then the cable is with copper
conductors.
Y - When at first or second place in type designation, it stands for PVC insulation.
CE - Individual core screening.
W - Round steel wire armouring.
F - Formed steel wire armouring.
Gb - Steel tape counter helix.
Y - When last in type designation, it stands for PVC outer sheath.
WW - Steel double round wire armour.
FF - Steel double formed wire armour.
3.5 CONDUCTOR TYPES
re - Circular solid conductor.
rm - Circular, stranded conductor (non - compacted)
rm/v - Circular, stranded compacted conductor.
sm - Sector shaped, stranded conductor.
Number of cores, conductor cross section, voltage grade are written in the usual
manner.
Example :
AYFY 3 x 400 s. m. 650/1100 V
Aluminium conductor, PVC insulated, formed steel wire armoured, PVC overall
sheathed 3 -core cable, conductor size 400 sq. mm stranded sector shaped
650/1100 V grade.
YY 37 x 1.5 re 650/1100 V
Copper conductor, PVC insulated and PVC sheathed (un-armoured) 37 core
cable, conductor size 1.5 sq. mm. solid round 650/1100 V grade.
3.6 FIELD OF APPLICATION
3.6.1 Control Cables 650/1100V as per IS:1554 (Part-1) - 1988
Type and Construction
Type YY
Un-armoured 1.5 and 2.5 sq. mm. copper conductors up to 61 cores.
Application
These cables are suitable for control purposes or measuring circuits, in
generating stations, sub-stations, industrial installations etc., as well as for
railway signalling. They can be installed indoors or outdoors, in air or in cable
ducts.
Type YWY/YFY
Armoured 1.5 and 2.5 sq. mm. copper conductors up to 61 cores.
Application
These cables are suitable for control purposes or measuring circuits in
generating stations, sub-stations, industrial installations etc., as well as for
railway signalling. On account of armouring, the cables can withstand rough
installations and operation conditions and tensile stresses. These can be laid in
water or buried direct in the ground, even on steep slopes. They can also be
installed indoors or outdoors, in air or in cable ducts.
Power Cables 650/1100V As Per IS:1554 (Part - 1) - 1988
Type AYY
Unarmoured Single-core with Aluminium conductors up to 1000 sq. mm.
Application
Light weight and small permissible bending radii make single core Cables very
easy to install. These cables are therefore particularly useful in power stations
and sub-stations where a comparatively large number of cables in short lengths
are to be used.
3.6.2 Power Cables 650/1100 V As Per IS:1554 (Part - 1) - 1988
Type AYY
Unarmoured Multi-core cables with Aluminium conductors up to 500 sq. mm.
Application
These power cables are suitable for use in generating stations, sub-stations,
house service connections, street lighting, industrial installations, building wiring
etc. They can be installed indoors or outdoors, in air or in cable ducts.
Type AYWY/AYFY
Armoured Multi-core cables with Aluminium conductors up to 500 sq. mm.
Application
These power cables are suitable for use in generating stations, sub-stations,
distribution systems, house service connections, street lighting, industrial
installation etc. On account of the armouring, the cables can withstand rough
installation and operating conditions and tensile stresses, and can be laid in
water or buried direct in the ground, even on steep slopes. They can also be
installed indoors and outdoors, in air or in cable ducts.
3.6.3 Power Cables 1.9/3.3 kV* to 6.35/11 kV. As Per IS:1554 (Part - 2) - 1988
Type AYFY 3.8/6.6 kV (E)
Armoured Multi-core cables with Aluminium conductors up to 500 sq. mm.
Application
These cables can be used both indoors and outdoors, and can be directly laid in
the ground or under water. These are suitable for power stations, switching
stations, industrial plants and as feeders in electricity supply undertakings.
Type AYCEFY 11 kV (E)
Armoured Screened Multi-core cables with Aluminium conductors up to 500 sq.
mm.*
Application
11 kV cables are suitable for all types of industrial applications and particularly
for hydro and thermal power stations and sub-stations. They are ideally suited for
chemical and fertiliser industries on account of their better corrosion resistance or
in heavy industries where severe load fluctuations occur and for systems where
there are frequent over voltages.
Cables of 6.35 / 11 kV grade (Earthed system) can be used on 6.6 / 6.6 kV
(Unearthed system) also.
In a distribution system, if the feeding Transformer neutral is not grounded,
during single phase to ground Fault condition, Transformer neutral will shift and
phase to ground voltages may reach equal to phase to phase voltages. Hence in
unearthed system, insulation level of cables will be higher compared to earthed
system.
3.6.4 Mining Cables 650/1100 V As Per IS: 1554 (Part - 1) - 1988 And 1.9/3.3
kV; 3.8/6.6 kV(E) And 6.35/11 kV As Per IS:1554 (Part - 2) - 1988.
Type YFFGbY
Armoured Multi-core cables, with Copper conductors up to 500 sq. mm.
Application
Mining cables are light in weight, and hence easier to handle and install. It is
provided with an armour consisting of double layer of formed galvanised steel
wire which affords complete protection from falling rocks, wagon tipping or any
other mechanical impact, and makes the cable strong enough to withstand
tensile for many times its own weight especially when used as a shaft cable.
Besides, the incorporation of a counter - helix over the top armour layer prevents
bird caging. In addition, to ensure an adequate path for earth fault currents, the
armour resistance is so designed that it never exceeds that of the main
conductor by more than 33%. All the above features make mining cables ideally
suited for use in all types of mines.(During laying of Power cables, if the cables
are not handled as per the laying practices armour of the cable may buidge. This
building of the armour will look like cage of bird and hence the name of bird
caging"
3.6.5 Flame Retardant Low Smoke PVC Cables (FRLS)
Until recently, flame retardance was never a major consideration when choosing
a cable. However, in the recent past, the growing awareness of hazards due to
fire incidence in power plants, high rise buildings, cable galleries etc., has
resulted in the development of FRLS Cables.
As compared to normal PVC cables, TROPODURE (FRLS) cables offer
improved performance characteristics in respect of the following:
1. Flame Retardance
2. Low Smoke Emission
3. Low Acid Gas Emission
In order to meet the above, special material is used for the outer sheath. The
design, construction and testing of (FRLS) cables is as per IS:1554 Part-1 and 2.
Over and above the standard tests, FRLS cables and its components are
subjected to a series of special tests to fulfill the need of the improved fire
performance characteristics.
1. Physical Testing
2. Smoke Density Measurement Tests as per ASTM D-2843
3. Oxygen Index Tests as per ASTM D-2863
4. HCL Liberation as per IEC-754
1. Smoke Generation Test:
Optical method is most practised to measure the amount of smoke generated
while burning the sample. A fixed dimension sample of material is put to flame of
specified intensity for 4 minutes and the percentage obstruction on an optical
path is measured at 15 seconds interval. A graphical plot of such measurements
evaluates the average smoke density. This area integration method is only the
quantitative indication of smoke generation by the PVC compound.
2. Oxygen & Temperature Index Test:
Oxygen index is the measurement of oxygen content at which the vertically held
sample when ignited ceases to burn off its own within 3 minutes. This is a relative
measure of combustion resistance of materials in the context of atmospheric
oxygen.
Temperature index is the temperature at which the vertically held sample ceases
to burn off on its own within 3 minutes at an Oxygen concentration of 21% i.e.
atmospheric air.
3. HCL Gas Emission Test:
All PVC Compounds when decomposed due to fire emit gaseous fumes which
are basically corrosive in nature. This is entirely due to the ingredients used in
the formulations. These fumes, if containing higher amounts of corrosive gas i.e.
Hydrochloric Acid Gas, may damage various instruments and equipment's in the
vin-city of fire. More and more stress is being given these days to control this
content in reasonable limits. A sample of cable compound is subjected to above
test and the decomposed gases are collected in alkaline solutions. Such alkaline
medium is then analysed to estimate the HCL evolved.
Apart from these tests on materials used on cables, following tests on finished
cables are carried out :
1. Test on electrical cables under the conditions as per IEC 332-1
2. Flammability testing - Chimney test for Class F3 as per Swedish Standards SS
424 1475
3. Flame tests as per IEEE Standard 383, 1974.
Applications
FRLS cables are ideal for use in high rise buildings, data processing centres,
hospitals, theaters, hotels, schools, warehouses, industrial complexes, power
stations, underground railways, oil platforms and areas where safety of personnel
or protection of equipment is necessary.
3.6.6 XLPE Cables (Cross Linked Polyethylene)
3.6.6.1 Properties and Advantages :
The excellent thermal properties of XLPE cables permit maximum continuous
conductor operating temperature of 900 C and short circuit temperature of 2500
C. Moreover, it has very low dielectric loss which does not vary much over the
entire operating temperature range.
These characteristics, along with the low dielectric constant make XLPE cables
particularly suitable for high voltage applications. Given below are additional
outstanding features.
High Continuous Current Rating :
Its ability to withstand higher operating temperature of 90 0 C enables much
higher current ratings than those of PVC or PILC cables.
High Short Circuit Rating :
Maximum allowable conductor temperature during short circuit of 250 0 C is
considerably higher than for PVC or PILC cables resulting in greater short circuit
withstand capacity.
High Emergency Load Capacity :
XLPE cables can be operated even at 1300 C during emergency, therefore in
systems where cables are installed in parallel, failure of one of two cables will not
bring down the system capacity because the remaining cables can carry the
additional load even for longer duration until repairs / replacements are carried
out.
Low Dielectric Losses :
XLPE cables have low dielectric loss angle. The dielectric losses are
quadratically dependent on the voltage. Moreover, these losses occur
continuously in every charged cable whether it carries load or not. Hence use of
XLPE cable at higher voltages would result in considerable saving in costs.
Charging Currents :
The charging currents are considerably lower permitting close setting of
protection relays.
Easy Laying and Installation :
Low weight and small bending radii make laying and installation of cable very
easy. The cable requires less supports due to low weight.
High Safety :
High safety against mechanical damage and vibrations.
3.6.6.2 Applications :
Because of the excellent mechanical and electrical properties XLPE cables are
being used extensively in all power stations and in industrial plants. They are
ideally suited for chemical and fertiliser industries where cables are exposed to
chemical corrosion or in heavy industries where cables are exposed to chemical
corrosion or in heavy industries where severe load fluctuations occur and for
systems where there are frequent over voltages. Cables can also be used at
higher ambient temperature on account of their higher operating temperature.
There excellent installation properties permit the cable to be used even under
most difficult cable routing conditions and also in cramped conditions e.g. City
distribution network. Single core cables due to their excellent installation
properties are used in power stations, sub stations and industrial plants with
advantage.
3.6.6.3 Construction :
XLPE cables are manufactured and tested in accordance with IS : 7098 (Part II) -
1985. Its salient constructional features are as under :
Conductor :
The conductors made from electrical purity aluminium wires, are stranded
together and compacted. All sizes of conductors of single or three core cables
are circular in shape. Conductor construction and testing comply to IS 8130 -
1984.
Cables with copper conductor can also be offered.
Insulation :
High quality XLPE unfilled insulating compound of natural colour is used for
insulation. Insulation is applied by extrusion process and is chemically cross
linked by continuous vulcanisation process.
Shielding :
All XLPE cables rated above 3.3 kV are provided with both conductor shielding
and insulation shielding. Both conductor and insulation shielding consists of
extruded semi conducting compound.
Additionally, insulation is provided with semi-conducting tape and non-magnetic
metallic tape screen over the extruded insulation.
Conductor shielding XLPE insulation and insulation shielding are all extruded in
one operation by a special process. This process ensures perfect bonding of
inner and outer shielding with insulation.
Inner Sheath
(Common Covering) :
In case of multi-core cables, cores are stranded together with suitable non-
hygroscopic fillers in the interstices and provided with common covering of plastic
tape wrapping. As an alternative to wrapped inner sheath, extruded PVC inner
sheath can also be provided.
Armouring :
Armouring is applied over the inner sheath and normally comprises of flat steel
wires (strips) for multi core cables. Alternatively, round steel wire armouring can
also be offered. Single core armoured cables are provided with non-magnetic
armour consisting of hard drawn flat or round aluminium wires.
Outer Sheath :
A tough outer sheath of heat resisting Tropodur (PVC) compound (Type ST2 as
per IS 5831) is extruded over the armouring in case of armoured cables or over
non-magnetic metallic tape covering the insulation or over the non-magnetic
metallic part of insulation screening in case of unarmoured single core cables.
This is always black in colour for best resistance to outdoor exposure. The outer
sheath is embossed with the voltage grade and the year of manufacture. The
embossing repeats every 300/350 mm along the length of the cable.
XLPE cables are manufactured under advanced manufacturing and testing
facilities. The cables are type tested and routine tested in accordance with IS
7098 (Part II) - 1985.
The following tests are carried out as on every length of cable manufactured :
a) Conductor resistance test.
b) Partial discharge test.
c) High voltage test.
d) Insulation resistance.
e) Bending test.
f) Heating cycle test.
g) Dielectric power factor test.
h) Impulse withstand test.
3.6.6.4 Test Voltages :
The following test voltage is applied between conductor and screen / armour (IS
1255 - 1983) :
_________________________________________________________
1. Colour Scheme :
Cores are identified by colour scheme of PVC insulation. The following colour scheme is
normally adopted :
1 core - Red, Black, Yellow, Blue or Natural (non-pigmented)
2 core - Red and Black
3 core - Red, Yellow, and Blue
4 core - Red, Yellow, Blue and Black (also 3-1/2 core) (reduced neutral core is
black)
5 core - Red, Yellow, Blue, Black and Grey
For cables having more than 5 cores :
Two adjacent cores (counting and directional) in each layer are coloured blue
and yellow respectively and the remaining cores are grey.
Alternatively cores with number printing can be offered. For 11 kV PVC/XLPC
cables, cores shall be identified by means of number printing tape.
1. Inner Sheath :
For all cables having two or more cores, a common covering (inner sheath) is applied
over the laid up cores either by extruded sheath of un-vulcanised rubber/PVC compound
or wrapping of plastic or proofed tapes. Single core cables do not have inner sheath.
1. Armouring :
For multi-core cables, armouring is applied over the inner sheath. In case of cables where
fictitious diameter over the inner sheath does not exceed 13 mm., the armour consists of
galvanised round steel wires; above this size, normally the armour is of galvanised
formed steel wires.
Armouring of PVC mining cables consists of galvanised round / formed steel
wires, but wherever necessary, a few tinned copper wires / strips are also
included to meet the resistance requirements of armouring for mining cables as
specified in IS:1554 (Part 1 & 2) 1988.
For single core armoured cables, non magnetic armouring is provided.
1. Outer Sheath :
Outer sheath of PVC is extruded over the armouring. In case of multi-core unarmoured
cables, over the inner sheath, whereas, in case of unarmoured single-core cables, it is
extruded over the insulation. This is always black in colour for best resistance to outdoor
exposure. Any other colour can be available on request.
The manufacturer's name and trademark along with the year / year code of
manufacture are embossed on the outer sheath; additionally in the case of LT
cables, the word 'ELECTRIC' and in the case of HT cables, the voltage grade is
also embossed. In case of LT cables with Heat Resisting Insulation, the word
"HR 85" is also embossed. In the case of mining cables, the word MINING is
added in the embossing script. The embossing script repeats in such a way that
every meter of the cable be are the same script.
3.4 TYPE DESIGNATION
Type designated of PVC Cables is based on the following alphabetical
nomenclature.
A - Aluminium conductors - when first letter of type designation. When type
designation does not contain 'A' in the beginning, then the cable is with copper
conductors.
Y - When at first or second place in type designation, it stands for PVC insulation.
CE - Individual core screening.
W - Round steel wire armouring.
F - Formed steel wire armouring.
Gb - Steel tape counter helix.
Y - When last in type designation, it stands for PVC outer sheath.
WW - Steel double round wire armour.
FF - Steel double formed wire armour.
3.5 CONDUCTOR TYPES
re - Circular solid conductor.
rm - Circular, stranded conductor (non - compacted)
rm/v - Circular, stranded compacted conductor.
sm - Sector shaped, stranded conductor.
Number of cores, conductor cross section, voltage grade are written in the usual
manner.
Example :
AYFY 3 x 400 s. m. 650/1100 V
Aluminium conductor, PVC insulated, formed steel wire armoured, PVC overall
sheathed 3 -core cable, conductor size 400 sq. mm stranded sector shaped
650/1100 V grade.
YY 37 x 1.5 re 650/1100 V
Copper conductor, PVC insulated and PVC sheathed (un-armoured) 37 core
cable, conductor size 1.5 sq. mm. solid round 650/1100 V grade.
3.6 FIELD OF APPLICATION
3.6.1 Control Cables 650/1100V as per IS:1554 (Part-1) - 1988
Type and Construction
Type YY
Un-armoured 1.5 and 2.5 sq. mm. copper conductors up to 61 cores.
Application
These cables are suitable for control purposes or measuring circuits, in
generating stations, sub-stations, industrial installations etc., as well as for
railway signalling. They can be installed indoors or outdoors, in air or in cable
ducts.
Type YWY/YFY
Armoured 1.5 and 2.5 sq. mm. copper conductors up to 61 cores.
Application
These cables are suitable for control purposes or measuring circuits in
generating stations, sub-stations, industrial installations etc., as well as for
railway signalling. On account of armouring, the cables can withstand rough
installations and operation conditions and tensile stresses. These can be laid in
water or buried direct in the ground, even on steep slopes. They can also be
installed indoors or outdoors, in air or in cable ducts.
Power Cables 650/1100V As Per IS:1554 (Part - 1) - 1988
Type AYY
Unarmoured Single-core with Aluminium conductors up to 1000 sq. mm.
Application
Light weight and small permissible bending radii make single core Cables very
easy to install. These cables are therefore particularly useful in power stations
and sub-stations where a comparatively large number of cables in short lengths
are to be used.
3.6.2 Power Cables 650/1100 V As Per IS:1554 (Part - 1) - 1988
Type AYY
Unarmoured Multi-core cables with Aluminium conductors up to 500 sq. mm.
Application
These power cables are suitable for use in generating stations, sub-stations,
house service connections, street lighting, industrial installations, building wiring
etc. They can be installed indoors or outdoors, in air or in cable ducts.
Type AYWY/AYFY
Armoured Multi-core cables with Aluminium conductors up to 500 sq. mm.
Application
These power cables are suitable for use in generating stations, sub-stations,
distribution systems, house service connections, street lighting, industrial
installation etc. On account of the armouring, the cables can withstand rough
installation and operating conditions and tensile stresses, and can be laid in
water or buried direct in the ground, even on steep slopes. They can also be
installed indoors and outdoors, in air or in cable ducts.
3.6.3 Power Cables 1.9/3.3 kV* to 6.35/11 kV. As Per IS:1554 (Part - 2) - 1988
Type AYFY 3.8/6.6 kV (E)
Armoured Multi-core cables with Aluminium conductors up to 500 sq. mm.
Application
These cables can be used both indoors and outdoors, and can be directly laid in
the ground or under water. These are suitable for power stations, switching
stations, industrial plants and as feeders in electricity supply undertakings.
Type AYCEFY 11 kV (E)
Armoured Screened Multi-core cables with Aluminium conductors up to 500 sq.
mm.*
Application
11 kV cables are suitable for all types of industrial applications and particularly
for hydro and thermal power stations and sub-stations. They are ideally suited for
chemical and fertiliser industries on account of their better corrosion resistance or
in heavy industries where severe load fluctuations occur and for systems where
there are frequent over voltages.
Cables of 6.35 / 11 kV grade (Earthed system) can be used on 6.6 / 6.6 kV
(Unearthed system) also.
In a distribution system, if the feeding Transformer neutral is not grounded,
during single phase to ground Fault condition, Transformer neutral will shift and
phase to ground voltages may reach equal to phase to phase voltages. Hence in
unearthed system, insulation level of cables will be higher compared to earthed
system.
3.6.4 Mining Cables 650/1100 V As Per IS: 1554 (Part - 1) - 1988 And 1.9/3.3
kV; 3.8/6.6 kV(E) And 6.35/11 kV As Per IS:1554 (Part - 2) - 1988.
Type YFFGbY
Armoured Multi-core cables, with Copper conductors up to 500 sq. mm.
Application
Mining cables are light in weight, and hence easier to handle and install. It is
provided with an armour consisting of double layer of formed galvanised steel
wire which affords complete protection from falling rocks, wagon tipping or any
other mechanical impact, and makes the cable strong enough to withstand
tensile for many times its own weight especially when used as a shaft cable.
Besides, the incorporation of a counter - helix over the top armour layer prevents
bird caging. In addition, to ensure an adequate path for earth fault currents, the
armour resistance is so designed that it never exceeds that of the main
conductor by more than 33%. All the above features make mining cables ideally
suited for use in all types of mines.(During laying of Power cables, if the cables
are not handled as per the laying practices armour of the cable may buidge. This
building of the armour will look like cage of bird and hence the name of bird
caging"
3.6.5 Flame Retardant Low Smoke PVC Cables (FRLS)
Until recently, flame retardance was never a major consideration when choosing
a cable. However, in the recent past, the growing awareness of hazards due to
fire incidence in power plants, high rise buildings, cable galleries etc., has
resulted in the development of FRLS Cables.
As compared to normal PVC cables, TROPODURE (FRLS) cables offer
improved performance characteristics in respect of the following:
1. Flame Retardance
2. Low Smoke Emission
3. Low Acid Gas Emission
In order to meet the above, special material is used for the outer sheath. The
design, construction and testing of (FRLS) cables is as per IS:1554 Part-1 and 2.
Over and above the standard tests, FRLS cables and its components are
subjected to a series of special tests to fulfill the need of the improved fire
performance characteristics.
1. Physical Testing
2. Smoke Density Measurement Tests as per ASTM D-2843
3. Oxygen Index Tests as per ASTM D-2863
4. HCL Liberation as per IEC-754
1. Smoke Generation Test:
Optical method is most practised to measure the amount of smoke generated
while burning the sample. A fixed dimension sample of material is put to flame of
specified intensity for 4 minutes and the percentage obstruction on an optical
path is measured at 15 seconds interval. A graphical plot of such measurements
evaluates the average smoke density. This area integration method is only the
quantitative indication of smoke generation by the PVC compound.
2. Oxygen & Temperature Index Test:
Oxygen index is the measurement of oxygen content at which the vertically held
sample when ignited ceases to burn off its own within 3 minutes. This is a relative
measure of combustion resistance of materials in the context of atmospheric
oxygen.
Temperature index is the temperature at which the vertically held sample ceases
to burn off on its own within 3 minutes at an Oxygen concentration of 21% i.e.
atmospheric air.
3. HCL Gas Emission Test:
All PVC Compounds when decomposed due to fire emit gaseous fumes which
are basically corrosive in nature. This is entirely due to the ingredients used in
the formulations. These fumes, if containing higher amounts of corrosive gas i.e.
Hydrochloric Acid Gas, may damage various instruments and equipment's in the
vin-city of fire. More and more stress is being given these days to control this
content in reasonable limits. A sample of cable compound is subjected to above
test and the decomposed gases are collected in alkaline solutions. Such alkaline
medium is then analysed to estimate the HCL evolved.
Apart from these tests on materials used on cables, following tests on finished
cables are carried out :
1. Test on electrical cables under the conditions as per IEC 332-1
2. Flammability testing - Chimney test for Class F3 as per Swedish Standards SS
424 1475
3. Flame tests as per IEEE Standard 383, 1974.
Applications
FRLS cables are ideal for use in high rise buildings, data processing centres,
hospitals, theaters, hotels, schools, warehouses, industrial complexes, power
stations, underground railways, oil platforms and areas where safety of personnel
or protection of equipment is necessary.
3.6.6 XLPE Cables (Cross Linked Polyethylene)
3.6.6.1 Properties and Advantages :
The excellent thermal properties of XLPE cables permit maximum continuous
conductor operating temperature of 900 C and short circuit temperature of 2500
C. Moreover, it has very low dielectric loss which does not vary much over the
entire operating temperature range.
These characteristics, along with the low dielectric constant make XLPE cables
particularly suitable for high voltage applications. Given below are additional
outstanding features.
High Continuous Current Rating :
Its ability to withstand higher operating temperature of 90 0 C enables much
higher current ratings than those of PVC or PILC cables.
High Short Circuit Rating :
Maximum allowable conductor temperature during short circuit of 250 0 C is
considerably higher than for PVC or PILC cables resulting in greater short circuit
withstand capacity.
High Emergency Load Capacity :
XLPE cables can be operated even at 1300 C during emergency, therefore in
systems where cables are installed in parallel, failure of one of two cables will not
bring down the system capacity because the remaining cables can carry the
additional load even for longer duration until repairs / replacements are carried
out.
Low Dielectric Losses :
XLPE cables have low dielectric loss angle. The dielectric losses are
quadratically dependent on the voltage. Moreover, these losses occur
continuously in every charged cable whether it carries load or not. Hence use of
XLPE cable at higher voltages would result in considerable saving in costs.
Charging Currents :
The charging currents are considerably lower permitting close setting of
protection relays.
Easy Laying and Installation :
Low weight and small bending radii make laying and installation of cable very
easy. The cable requires less supports due to low weight.
High Safety :
High safety against mechanical damage and vibrations.
3.6.6.2 Applications :
Because of the excellent mechanical and electrical properties XLPE cables are
being used extensively in all power stations and in industrial plants. They are
ideally suited for chemical and fertiliser industries where cables are exposed to
chemical corrosion or in heavy industries where cables are exposed to chemical
corrosion or in heavy industries where severe load fluctuations occur and for
systems where there are frequent over voltages. Cables can also be used at
higher ambient temperature on account of their higher operating temperature.
There excellent installation properties permit the cable to be used even under
most difficult cable routing conditions and also in cramped conditions e.g. City
distribution network. Single core cables due to their excellent installation
properties are used in power stations, sub stations and industrial plants with
advantage.
3.6.6.3 Construction :
XLPE cables are manufactured and tested in accordance with IS : 7098 (Part II) -
1985. Its salient constructional features are as under :
Conductor :
The conductors made from electrical purity aluminium wires, are stranded
together and compacted. All sizes of conductors of single or three core cables
are circular in shape. Conductor construction and testing comply to IS 8130 -
1984.
Cables with copper conductor can also be offered.
Insulation :
High quality XLPE unfilled insulating compound of natural colour is used for
insulation. Insulation is applied by extrusion process and is chemically cross
linked by continuous vulcanisation process.
Shielding :
All XLPE cables rated above 3.3 kV are provided with both conductor shielding
and insulation shielding. Both conductor and insulation shielding consists of
extruded semi conducting compound.
Additionally, insulation is provided with semi-conducting tape and non-magnetic
metallic tape screen over the extruded insulation.
Conductor shielding XLPE insulation and insulation shielding are all extruded in
one operation by a special process. This process ensures perfect bonding of
inner and outer shielding with insulation.
Inner Sheath
(Common Covering) :
In case of multi-core cables, cores are stranded together with suitable non-
hygroscopic fillers in the interstices and provided with common covering of plastic
tape wrapping. As an alternative to wrapped inner sheath, extruded PVC inner
sheath can also be provided.
Armouring :
Armouring is applied over the inner sheath and normally comprises of flat steel
wires (strips) for multi core cables. Alternatively, round steel wire armouring can
also be offered. Single core armoured cables are provided with non-magnetic
armour consisting of hard drawn flat or round aluminium wires.
Outer Sheath :
A tough outer sheath of heat resisting Tropodur (PVC) compound (Type ST2 as
per IS 5831) is extruded over the armouring in case of armoured cables or over
non-magnetic metallic tape covering the insulation or over the non-magnetic
metallic part of insulation screening in case of unarmoured single core cables.
This is always black in colour for best resistance to outdoor exposure. The outer
sheath is embossed with the voltage grade and the year of manufacture. The
embossing repeats every 300/350 mm along the length of the cable.
XLPE cables are manufactured under advanced manufacturing and testing
facilities. The cables are type tested and routine tested in accordance with IS
7098 (Part II) - 1985.
The following tests are carried out as on every length of cable manufactured :
a) Conductor resistance test.
b) Partial discharge test.
c) High voltage test.
d) Insulation resistance.
e) Bending test.
f) Heating cycle test.
g) Dielectric power factor test.
h) Impulse withstand test.
3.6.6.4 Test Voltages :
The following test voltage is applied between conductor and screen / armour (IS
1255 - 1983) :
_________________________________________________________
Failures / Causes
Overloading causes the temperature rise of insulation above normal values. The
dielectric strength of insulation reduces inversely with increased temperature.
The life of insulation reduces rapidly when temperature rises above safe limits.
7. Moisture in insulation.
Summary
3) Over voltage.
4) Faulty laying.
The insulation should not rupture and leakage currents should not increase
above permissible limits.