You are on page 1of 11

-------------------------------------------------------------------------------

Date and Time : Wed Aug 25 13:42:24 2010


File Name & Path : D:\MiPower\load\SCS\1short0S.out0
-------------------------------------------------------------------------------
SHORT CIRCUIT STUDIES
CASE NO : 1 CONTINGENCY : 0 SCHEDULE NO : 0
CONTINGENCY NAME : Base Case
-------------------------------------------------------------------------------
LARGEST BUS NUMBER USED : 7 ACTUAL NUMBER OF BUSES : 6
NUMBER OF 2 WIND. TRANSFORMERS : 2 NUMBER OF 3 WIND. TRANSFORMERS : 0
NUMBER OF TRANSMISSION LINES : 5
NUMBER OF SERIES REACTORS : 0 NUMBER OF SERIES CAPACITORS : 0
NUMBER OF BUS COUPLERS : 0
NUMBER OF SHUNT REACTORS : 0 NUMBER OF SHUNT CAPACITORS : 0
NUMBER OF SHUNT IMPEDANCES : 0 NUMBER OF GENERATORS : 2
NUMBER OF MOTORS : 0
NUMBER OF LOADS : 0
NUMBER OF FILTERS : 0
NUMBER OF HVDC CONVERTORS : 0
-------------------------------------------------------------------------------
NUMBER OF ZONES : 1
PRINT OPTION : 3 (BOTH DATA AND RESULTS PRINT)
PLOT OPTION : 7 (PLOT FILE - PHASE A, MVA)
BASE MVA : 100.000
NOMINAL SYSTEM FREQUENCY: 50.000
PREFAULT VOLTAGE OPTION : 0 (VOLTAGE OF 1.0 PU IS ASSUMED)
FAULT OPTION : 0 (FAULT CONSIDERED AT ALL BUSES, ONE AT A TIME)
FLOW OPTION : 3 (FAULT CONTRIBUTION COMPUTED FROM ALL LINES)
FAULT TYPE : 1 (3 PHASE TO GROUND FAULT)
POST FAULT VOLT OPTION : 1 (COMPUTED AT ALL BUSES)
-------------------------------------------------------------------------------
-------------------------------------------------------------------------------
FAULT RESISTANCE - PHASE - 0.000000 (PU)
FAULT REACTANCE - PHASE - 0.000000 (PU)
FAULT RESISTANCE - GROUND - 0.000000 (PU)
FAULT REACTANCE - GROUND - 0.000000 (PU)
-------------------------------------------------------------------------------
CIRCUIT BREAKER RESISTANCE (PU) : 0.000000
CIRCUIT BREAKER REACTANCE (PU) : 0.000100
TRANSFORMER R/X RATIO : 0.050000
TRANSFORMER ZERO SEQUENCE IMPEDANCE MULT FACTOR : 0.900000
NUMBER OF TRANSMISSION VOLTAGE LEVELS : 3
TRANSMISSION LINE VOLTAGE - KV : 110.000000
TRANSMISSION LINE ZERO SEQUENCE RES. MULT. FACTOR : 2.500000
TRANSMISSION LINE ZERO SEQUENCE REA. MULT. FACTOR : 2.500000
TRANSMISSION LINE ZERO SEQUENCE ADM. MULT. FACTOR : 0.800000
TRANSMISSION LINE VOLTAGE - KV : 11.000000
TRANSMISSION LINE ZERO SEQUENCE RES. MULT. FACTOR : 2.500000
TRANSMISSION LINE ZERO SEQUENCE REA. MULT. FACTOR : 2.500000
TRANSMISSION LINE ZERO SEQUENCE ADM. MULT. FACTOR : 0.025000
TRANSMISSION LINE VOLTAGE - KV : 0.230000
TRANSMISSION LINE ZERO SEQUENCE RES. MULT. FACTOR : 2.500000
TRANSMISSION LINE ZERO SEQUENCE REA. MULT. FACTOR : 2.500000
TRANSMISSION LINE ZERO SEQUENCE ADM. MULT. FACTOR : 2.500000
GENERATOR NEGATIVE SEQUENCE RESISTANCE MULT. FACTOR : 0.175000
GENERATOR NEGATIVE SEQUENCE REACTANCE MULT. FACTOR : 0.175000
GENERATOR ZERO SEQUENCE RESISTANCE MULT. FACTOR : 0.037500
GENERATOR ZERO SEQUENCE REACTANCE MULT. FACTOR : 0.037500
LOAD NEGATIVE SEQUENCE IMPEDANCE MULT. FACTOR : 0.810000
LOAD ZERO SEQUENCE IMPEDANCE MULT. FACTOR : 1.600000
SERIES REACTOR ZERO SEQUENCE IMPEDANCE MULT. FACTOR : 1.000000
SHUNT REACTOR ZERO SEQUENCE IMPEDANCE MULT. FACTOR : 0.625000
-------------------------------------------------------------------------------
FAULT CONSIDERED FROM SENDING END OF LINE NUMBER 0 AT 0.00%
-------------------------------------------------------------------------------
BUS DATA
NODE STAT ZONE BUS-KV NAME VMAG-PU VANG-DEG PGEN-MW QGEN-MR
PLOAD-MW QLOAD-MR QCOMP-MR
---- ---- ---- -------- -------- -------- -------- -------- --------
1 1 1 110.000 Bus1 1.0000 0.000 0.000 0.000
0.000 0.000 0.000
2 1 1 110.000 Bus2 1.0000 0.000 0.000 0.000
0.000 0.000 0.000
4 1 1 110.000 Bus4 1.0000 0.000 0.000 0.000
0.000 0.000 0.000
5 1 1 110.000 Bus5 1.0000 0.000 0.000 0.000
0.000 0.000 0.000
6 1 1 11.000 Bus6 1.0000 0.000 0.000 0.000
0.000 0.000 0.000
7 1 1 11.000 Bus7 1.0000 0.000 0.000 0.000
0.000 0.000 0.000
-------------------------------------------------------------------------------
TRANSFORMER DATA
STAT CKTS FROM FROM TO TO POSITIVE ZERO
NODE NAME NODE NAME R(P.U) X(P.U.) R(P.U.) X(P.U.)
TAP PHASE FB-MVA TB-MVA
---- ---- ---- -------- ---- -------- -------- -------- -------- -------- - -
3 1 6 Bus6 1 Bus1 0.00250 0.04994 0.00250 0.04994
1.00000 0.000 350 5000 D G
3 1 7 Bus7 5 Bus5 0.00250 0.04994 0.00250 0.04994
1.00000 0.000 350 5000 D G
-------------------------------------------------------------------------------
TRANSMISSION LINE DATA
STAT CKTS FROM FROM TO TO
NODE NAME NODE NAME RP(P.U) XP(P.U) BP/2(PU)
RZ(P.U) XZ(P.U) BZ/2(PU) FB-MVA TB-MVA
---- ---- ---- -------- ---- -------- -------- -------- -------- ------ ------
3 1 1 Bus1 4 Bus4 0.00000 0.10000 0.00000
0.00000 0.10000 0.00000 5000 5000
3 1 2 Bus2 5 Bus5 0.00000 0.10000 0.00000
0.00000 0.10000 0.00000 5000 5000
3 1 1 Bus1 2 Bus2 0.00000 0.15000 0.00000
0.00000 0.15000 0.00000 5000 5000
3 1 4 Bus4 5 Bus5 0.00000 0.15000 0.00000
0.00000 0.15000 0.00000 5000 5000
3 1 1 Bus1 5 Bus5 0.00000 0.20000 0.00000
0.00000 0.20000 0.00000 5000 5000
-------------------------------------------------------------------------------
GENERATOR/MOTOR DATA
Classification Code :
0 : Generator
1 : Large Motor >1000 hp for <= 1800 rpm, >250 hp for 3600 rpm
2 : Medium Motor >= 50 hp
3 : Small Motor < 50 hp
FROM FROM POSITIVE NEGATIVE ZERO
CLASS
NODE NAME R(P.U) X(P.U.) R(P.U.) X(P.U.) R(P.U.) X(P.U.) CB-MVA STAT
CODE
---- -------- -------- -------- -------- -------- -------- -------- ------ ----
-----
6 Bus6 0.00000 0.10000 0.00000 0.00000 0.00000 0.00000 350 3
0
7 Bus7 0.00000 0.10000 0.00000 0.00000 0.00000 0.00000 350 3
0
-------------------------------------------------------------------------------
-------------------------------------------------------------------------------
FAULT AT BUS NUMBER 1 : NAME Bus1
CURRENT (AMPS/DEGREE) FAULT MVA
SEQUENCE (1,2,0) PHASE (A,B,C) SEQUENCE (1,2,0) PHASE (A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE MAGNITUDE
--------- ------- --------- ------- --------- ---------
5813 -89.17 5813 -89.17 1108 1108
0 -90.00 5813 150.83 0 1108
0 -90.00 5813 30.83 0 1108
R/X RATIO OF THE SHORT CIRCUIT PATH : 0.0144
PEAK ASYMMETRICAL SHORT-CIRCUIT CURRENT : 16187 AMPS
PASCC = k x sqrt(2) x If , k = 1.9689
-------------------------------------------------------------------------------
POST FAULT BUS VOLTAGES
NUMBER NAME SEQUENCE (1,2,0) PHASE (A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE
------ -------- --------- ------- --------- -------
1 Bus1 0.000 90.00 0.000 90.00
0.000 -90.00 0.000 -30.00
0.000 -90.00 0.000 -150.00
2 Bus2 0.203 0.63 0.203 0.63
0.000 -90.00 0.203 -119.37
0.000 -90.00 0.203 120.63
4 Bus4 0.136 0.63 0.136 0.63
0.000 -90.00 0.136 -119.37
0.000 -90.00 0.136 120.63
5 Bus5 0.339 0.63 0.339 0.63
0.000 -90.00 0.339 -119.37
0.000 -90.00 0.339 120.63
6 Bus6 0.333 -1.91 0.333 -1.91
0.000 -90.00 0.333 -121.91
0.000 -90.00 0.333 118.09
7 Bus7 0.559 -0.50 0.559 -0.50
0.000 -90.00 0.559 -120.50
0.000 -90.00 0.559 119.50
-------------------------------------------------------------------------------
FAULT CONTRIBUTION
FROM FROM TO TO CURRENT (AMPS/DEGREE) MVA
NODE NAME NODE NAME SEQUENCE (1,2,0) PHASE (A,B,C) PHASE(A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE
---- -------- ---- -------- --------- ------- --------- ------- ---------
1 Bus1 6 Bus6 3500 90.95 3500 90.95 667
0 -90.00 3500 -29.05 667
0 -90.00 3500 -149.05 667
7 Bus7 5 Bus5 23135 -89.37 23135 -89.37 441
0 -90.00 23135 150.63 441
0 -90.00 23135 30.63 441
1 Bus1 4 Bus4 712 90.63 712 90.63 136
0 -90.00 712 -29.37 136
0 -90.00 712 -149.37 136
2 Bus2 5 Bus5 712 90.63 712 90.63 136
0 -90.00 712 -29.37 136
0 -90.00 712 -149.37 136
1 Bus1 2 Bus2 712 90.63 712 90.63 136
0 -90.00 712 -29.37 136
0 -90.00 712 -149.37 136
4 Bus4 5 Bus5 712 90.63 712 90.63 136
0 -90.00 712 -29.37 136
0 -90.00 712 -149.37 136
1 Bus1 5 Bus5 890 90.63 890 90.63 170
0 -90.00 890 -29.37 170
0 -90.00 890 -149.37 170
-------------------------------------------------------------------------------
FAULT CONTRIBUTION FROM SHUNT CONNECTION
FROM FROM CURRENT (AMPS/DEGREE) MVA
NODE NAME SEQUENCE (1,2,0) PHASE (A,B,C) PHASE(A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE
---- -------- --------- ------- --------- ------- ---------
6 Bus6 35001 90.95 35001 90.95 667
0 -90.00 35001 -29.05 667
0 -90.00 35001 -149.05 667
7 Bus7 23135 90.63 23135 90.63 441
0 -90.00 23135 -29.37 441
0 -90.00 23135 -149.37 441
-------------------------------------------------------------------------------
FAULT AT BUS NUMBER 2 : NAME Bus2
CURRENT (AMPS/DEGREE) FAULT MVA
SEQUENCE (1,2,0) PHASE (A,B,C) SEQUENCE (1,2,0) PHASE (A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE MAGNITUDE
--------- ------- --------- ------- --------- ---------
3871 -89.47 3871 -89.47 738 738
0 -90.00 3871 150.53 0 738
0 -90.00 3871 30.53 0 738
R/X RATIO OF THE SHORT CIRCUIT PATH : 0.0092
PEAK ASYMMETRICAL SHORT-CIRCUIT CURRENT : 10840 AMPS
PASCC = k x sqrt(2) x If , k = 1.9801
-------------------------------------------------------------------------------
POST FAULT BUS VOLTAGES
NUMBER NAME SEQUENCE (1,2,0) PHASE (A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE
------ -------- --------- ------- --------- -------
1 Bus1 0.470 0.52 0.470 0.52
0.000 -90.00 0.470 -119.48
0.000 -90.00 0.470 120.52
2 Bus2 0.000 90.00 0.000 90.00
0.000 -90.00 0.000 -30.00
0.000 -90.00 0.000 -150.00
4 Bus4 0.452 0.52 0.452 0.52
0.000 -90.00 0.452 -119.48
0.000 -90.00 0.452 120.52
5 Bus5 0.424 0.54 0.424 0.54
0.000 -90.00 0.424 -119.46
0.000 -90.00 0.424 120.54
6 Bus6 0.646 -0.27 0.646 -0.27
0.000 -90.00 0.646 -120.27
0.000 -90.00 0.646 119.73
7 Bus7 0.616 -0.35 0.616 -0.35
0.000 -90.00 0.616 -120.35
0.000 -90.00 0.616 119.65
-------------------------------------------------------------------------------
FAULT CONTRIBUTION
FROM FROM TO TO CURRENT (AMPS/DEGREE) MVA
NODE NAME NODE NAME SEQUENCE (1,2,0) PHASE (A,B,C) PHASE(A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE
---- -------- ---- -------- --------- ------- --------- ------- ---------
6 Bus6 1 Bus1 18565 -89.50 18565 -89.50 354
0 -90.00 18565 150.50 354
0 -90.00 18565 30.50 354
7 Bus7 5 Bus5 20145 -89.44 20145 -89.44 384
0 -90.00 20145 150.56 384
0 -90.00 20145 30.56 384
1 Bus1 4 Bus4 95 -89.67 95 -89.67 18
0 -90.00 95 150.33 18
0 -90.00 95 30.33 18
2 Bus2 5 Bus5 2228 90.54 2228 90.54 424
0 -90.00 2228 -29.46 424
0 -90.00 2228 -149.46 424
2 Bus2 1 Bus1 1643 90.52 1643 90.52 313
0 -90.00 1643 -29.48 313
0 -90.00 1643 -149.48 313
4 Bus4 5 Bus5 95 -89.67 95 -89.67 18
0 -90.00 95 150.33 18
0 -90.00 95 30.33 18
1 Bus1 5 Bus5 118 -89.67 118 -89.67 23
0 -90.00 118 150.33 23
0 -90.00 118 30.33 23
-------------------------------------------------------------------------------
FAULT CONTRIBUTION FROM SHUNT CONNECTION
FROM FROM CURRENT (AMPS/DEGREE) MVA
NODE NAME SEQUENCE (1,2,0) PHASE (A,B,C) PHASE(A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE
---- -------- --------- ------- --------- ------- ---------
6 Bus6 18565 90.50 18565 90.50 354
0 -90.00 18565 -29.50 354
0 -90.00 18565 -149.50 354
7 Bus7 20145 90.56 20145 90.56 384
0 -90.00 20145 -29.44 384
0 -90.00 20145 -149.44 384
-------------------------------------------------------------------------------
FAULT AT BUS NUMBER 4 : NAME Bus4
CURRENT (AMPS/DEGREE) FAULT MVA
SEQUENCE (1,2,0) PHASE (A,B,C) SEQUENCE (1,2,0) PHASE (A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE MAGNITUDE
--------- ------- --------- ------- --------- ---------
3871 -89.47 3871 -89.47 738 738
0 -90.00 3871 150.53 0 738
0 -90.00 3871 30.53 0 738
R/X RATIO OF THE SHORT CIRCUIT PATH : 0.0092
PEAK ASYMMETRICAL SHORT-CIRCUIT CURRENT : 10840 AMPS
PASCC = k x sqrt(2) x If , k = 1.9801
-------------------------------------------------------------------------------
POST FAULT BUS VOLTAGES
NUMBER NAME SEQUENCE (1,2,0) PHASE (A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE
------ -------- --------- ------- --------- -------
1 Bus1 0.424 0.54 0.424 0.54
0.000 -90.00 0.424 -119.46
0.000 -90.00 0.424 120.54
2 Bus2 0.452 0.52 0.452 0.52
0.000 -90.00 0.452 -119.48
0.000 -90.00 0.452 120.52
4 Bus4 0.000 180.00 0.000 180.00
0.000 -90.00 0.000 60.00
0.000 -90.00 0.000 -60.00
5 Bus5 0.470 0.52 0.470 0.52
0.000 -90.00 0.470 -119.48
0.000 -90.00 0.470 120.52
6 Bus6 0.616 -0.35 0.616 -0.35
0.000 -90.00 0.616 -120.35
0.000 -90.00 0.616 119.65
7 Bus7 0.646 -0.27 0.646 -0.27
0.000 -90.00 0.646 -120.27
0.000 -90.00 0.646 119.73
-------------------------------------------------------------------------------
FAULT CONTRIBUTION
FROM FROM TO TO CURRENT (AMPS/DEGREE) MVA
NODE NAME NODE NAME SEQUENCE (1,2,0) PHASE (A,B,C) PHASE(A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE
---- -------- ---- -------- --------- ------- --------- ------- ---------
6 Bus6 1 Bus1 20145 -89.44 20145 -89.44 384
0 -90.00 20145 150.56 384
0 -90.00 20145 30.56 384
7 Bus7 5 Bus5 18565 -89.50 18565 -89.50 354
0 -90.00 18565 150.50 354
0 -90.00 18565 30.50 354
4 Bus4 1 Bus1 2228 90.54 2228 90.54 424
0 -90.00 2228 -29.46 424
0 -90.00 2228 -149.46 424
2 Bus2 5 Bus5 95 90.33 95 90.33 18
0 -90.00 95 -29.67 18
0 -90.00 95 -149.67 18
1 Bus1 2 Bus2 95 90.33 95 90.33 18
0 -90.00 95 -29.67 18
0 -90.00 95 -149.67 18
4 Bus4 5 Bus5 1643 90.52 1643 90.52 313
0 -90.00 1643 -29.48 313
0 -90.00 1643 -149.48 313
1 Bus1 5 Bus5 118 90.33 118 90.33 23
0 -90.00 118 -29.67 23
0 -90.00 118 -149.67 23
-------------------------------------------------------------------------------
FAULT CONTRIBUTION FROM SHUNT CONNECTION
FROM FROM CURRENT (AMPS/DEGREE) MVA
NODE NAME SEQUENCE (1,2,0) PHASE (A,B,C) PHASE(A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE
---- -------- --------- ------- --------- ------- ---------
6 Bus6 20145 90.56 20145 90.56 384
0 -90.00 20145 -29.44 384
0 -90.00 20145 -149.44 384
7 Bus7 18565 90.50 18565 90.50 354
0 -90.00 18565 -29.50 354
0 -90.00 18565 -149.50 354
-------------------------------------------------------------------------------
FAULT AT BUS NUMBER 5 : NAME Bus5
CURRENT (AMPS/DEGREE) FAULT MVA
SEQUENCE (1,2,0) PHASE (A,B,C) SEQUENCE (1,2,0) PHASE (A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE MAGNITUDE
--------- ------- --------- ------- --------- ---------
5813 -89.17 5813 -89.17 1108 1108
0 -90.00 5813 150.83 0 1108
0 -90.00 5813 30.83 0 1108
R/X RATIO OF THE SHORT CIRCUIT PATH : 0.0144
PEAK ASYMMETRICAL SHORT-CIRCUIT CURRENT : 16187 AMPS
PASCC = k x sqrt(2) x If , k = 1.9689
-------------------------------------------------------------------------------
POST FAULT BUS VOLTAGES
NUMBER NAME SEQUENCE (1,2,0) PHASE (A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE
------ -------- --------- ------- --------- -------
1 Bus1 0.339 0.63 0.339 0.63
0.000 -90.00 0.339 -119.37
0.000 -90.00 0.339 120.63
2 Bus2 0.136 0.63 0.136 0.63
0.000 -90.00 0.136 -119.37
0.000 -90.00 0.136 120.63
4 Bus4 0.203 0.63 0.203 0.63
0.000 -90.00 0.203 -119.37
0.000 -90.00 0.203 120.63
5 Bus5 0.000 0.00 0.000 0.00
0.000 -90.00 0.000 -120.00
0.000 -90.00 0.000 120.00
6 Bus6 0.559 -0.50 0.559 -0.50
0.000 -90.00 0.559 -120.50
0.000 -90.00 0.559 119.50
7 Bus7 0.333 -1.91 0.333 -1.91
0.000 -90.00 0.333 -121.91
0.000 -90.00 0.333 118.09
-------------------------------------------------------------------------------
FAULT CONTRIBUTION
FROM FROM TO TO CURRENT (AMPS/DEGREE) MVA
NODE NAME NODE NAME SEQUENCE (1,2,0) PHASE (A,B,C) PHASE(A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE
---- -------- ---- -------- --------- ------- --------- ------- ---------
6 Bus6 1 Bus1 23135 -89.37 23135 -89.37 441
0 -90.00 23135 150.63 441
0 -90.00 23135 30.63 441
5 Bus5 7 Bus7 3500 90.95 3500 90.95 667
0 -90.00 3500 -29.05 667
0 -90.00 3500 -149.05 667
1 Bus1 4 Bus4 712 -89.37 712 -89.37 136
0 -90.00 712 150.63 136
0 -90.00 712 30.63 136
5 Bus5 2 Bus2 712 90.63 712 90.63 136
0 -90.00 712 -29.37 136
0 -90.00 712 -149.37 136
1 Bus1 2 Bus2 712 -89.37 712 -89.37 136
0 -90.00 712 150.63 136
0 -90.00 712 30.63 136
5 Bus5 4 Bus4 712 90.63 712 90.63 136
0 -90.00 712 -29.37 136
0 -90.00 712 -149.37 136
5 Bus5 1 Bus1 890 90.63 890 90.63 170
0 -90.00 890 -29.37 170
0 -90.00 890 -149.37 170
-------------------------------------------------------------------------------
FAULT CONTRIBUTION FROM SHUNT CONNECTION
FROM FROM CURRENT (AMPS/DEGREE) MVA
NODE NAME SEQUENCE (1,2,0) PHASE (A,B,C) PHASE(A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE
---- -------- --------- ------- --------- ------- ---------
6 Bus6 23135 90.63 23135 90.63 441
0 -90.00 23135 -29.37 441
0 -90.00 23135 -149.37 441
7 Bus7 35001 90.95 35001 90.95 667
0 -90.00 35001 -29.05 667
0 -90.00 35001 -149.05 667
-------------------------------------------------------------------------------
FAULT AT BUS NUMBER 6 : NAME Bus6
CURRENT (AMPS/DEGREE) FAULT MVA
SEQUENCE (1,2,0) PHASE (A,B,C) SEQUENCE (1,2,0) PHASE (A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE MAGNITUDE
--------- ------- --------- ------- --------- ---------
71443 -89.73 71443 -89.73 1361 1361
0 -90.00 71443 150.27 0 1361
0 -90.00 71443 30.27 0 1361
R/X RATIO OF THE SHORT CIRCUIT PATH : 0.0048
PEAK ASYMMETRICAL SHORT-CIRCUIT CURRENT : 201026 AMPS
PASCC = k x sqrt(2) x If , k = 1.9897
-------------------------------------------------------------------------------
POST FAULT BUS VOLTAGES
NUMBER NAME SEQUENCE (1,2,0) PHASE (A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE
------ -------- --------- ------- --------- -------
1 Bus1 0.181 -1.83 0.181 -1.83
0.000 -90.00 0.181 -121.83
0.000 -90.00 0.181 118.17
2 Bus2 0.347 -0.45 0.347 -0.45
0.000 -90.00 0.347 -120.45
0.000 -90.00 0.347 119.55
4 Bus4 0.292 -0.74 0.292 -0.74
0.000 -90.00 0.292 -120.74
0.000 -90.00 0.292 119.26
5 Bus5 0.458 -0.09 0.458 -0.09
0.000 -90.00 0.458 -120.09
0.000 -90.00 0.458 119.91
6 Bus6 0.000 -27.70 0.000 -27.70
0.000 -90.00 0.000 -147.70
0.000 -90.00 0.000 92.30
7 Bus7 0.639 -0.58 0.639 -0.58
0.000 -90.00 0.639 -120.58
0.000 -90.00 0.639 119.42
-------------------------------------------------------------------------------
FAULT CONTRIBUTION
FROM FROM TO TO CURRENT (AMPS/DEGREE) MVA
NODE NAME NODE NAME SEQUENCE (1,2,0) PHASE (A,B,C) PHASE(A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE
---- -------- ---- -------- --------- ------- --------- ------- ---------
6 Bus6 1 Bus1 18959 91.03 18959 91.03 361
0 -90.00 18959 -28.97 361
0 -90.00 18959 -148.97 361
7 Bus7 5 Bus5 18959 -88.97 18959 -88.97 361
0 -90.00 18959 151.03 361
0 -90.00 18959 31.03 361
1 Bus1 4 Bus4 583 91.03 583 91.03 111
0 -90.00 583 -28.97 111
0 -90.00 583 -148.97 111
2 Bus2 5 Bus5 583 91.03 583 91.03 111
0 -90.00 583 -28.97 111
0 -90.00 583 -148.97 111
1 Bus1 2 Bus2 583 91.03 583 91.03 111
0 -90.00 583 -28.97 111
0 -90.00 583 -148.97 111
4 Bus4 5 Bus5 583 91.03 583 91.03 111
0 -90.00 583 -28.97 111
0 -90.00 583 -148.97 111
1 Bus1 5 Bus5 729 91.03 729 91.03 139
0 -90.00 729 -28.97 139
0 -90.00 729 -148.97 139
-------------------------------------------------------------------------------
FAULT CONTRIBUTION FROM SHUNT CONNECTION
FROM FROM CURRENT (AMPS/DEGREE) MVA
NODE NAME SEQUENCE (1,2,0) PHASE (A,B,C) PHASE(A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE
---- -------- --------- ------- --------- ------- ---------
6 Bus6 52486 90.00 52486 90.00 1000
0 -90.00 52486 -30.00 1000
0 -90.00 52486 -150.00 1000
7 Bus7 18959 91.03 18959 91.03 361
0 -90.00 18959 -28.97 361
0 -90.00 18959 -148.97 361
-------------------------------------------------------------------------------
FAULT AT BUS NUMBER 7 : NAME Bus7
CURRENT (AMPS/DEGREE) FAULT MVA
SEQUENCE (1,2,0) PHASE (A,B,C) SEQUENCE (1,2,0) PHASE (A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE MAGNITUDE
--------- ------- --------- ------- --------- ---------
71443 -89.73 71443 -89.73 1361 1361
0 -90.00 71443 150.27 0 1361
0 -90.00 71443 30.27 0 1361
R/X RATIO OF THE SHORT CIRCUIT PATH : 0.0048
PEAK ASYMMETRICAL SHORT-CIRCUIT CURRENT : 201026 AMPS
PASCC = k x sqrt(2) x If , k = 1.9897
-------------------------------------------------------------------------------
POST FAULT BUS VOLTAGES
NUMBER NAME SEQUENCE (1,2,0) PHASE (A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE
------ -------- --------- ------- --------- -------
1 Bus1 0.458 -0.09 0.458 -0.09
0.000 -90.00 0.458 -120.09
0.000 -90.00 0.458 119.91
2 Bus2 0.292 -0.74 0.292 -0.74
0.000 -90.00 0.292 -120.74
0.000 -90.00 0.292 119.26
4 Bus4 0.347 -0.45 0.347 -0.45
0.000 -90.00 0.347 -120.45
0.000 -90.00 0.347 119.55
5 Bus5 0.181 -1.83 0.181 -1.83
0.000 -90.00 0.181 -121.83
0.000 -90.00 0.181 118.17
6 Bus6 0.639 -0.58 0.639 -0.58
0.000 -90.00 0.639 -120.58
0.000 -90.00 0.639 119.42
7 Bus7 0.000 -90.00 0.000 -90.00
0.000 -90.00 0.000 -90.00
0.000 -90.00 0.000 -90.00
-------------------------------------------------------------------------------
FAULT CONTRIBUTION
FROM FROM TO TO CURRENT (AMPS/DEGREE) MVA
NODE NAME NODE NAME SEQUENCE (1,2,0) PHASE (A,B,C) PHASE(A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE
---- -------- ---- -------- --------- ------- --------- ------- ---------
6 Bus6 1 Bus1 18959 -88.97 18959 -88.97 361
0 -90.00 18959 151.03 361
0 -90.00 18959 31.03 361
7 Bus7 5 Bus5 18959 91.03 18959 91.03 361
0 -90.00 18959 -28.97 361
0 -90.00 18959 -148.97 361
1 Bus1 4 Bus4 583 -88.97 583 -88.97 111
0 -90.00 583 151.03 111
0 -90.00 583 31.03 111
2 Bus2 5 Bus5 583 -88.97 583 -88.97 111
0 -90.00 583 151.03 111
0 -90.00 583 31.03 111
1 Bus1 2 Bus2 583 -88.97 583 -88.97 111
0 -90.00 583 151.03 111
0 -90.00 583 31.03 111
4 Bus4 5 Bus5 583 -88.97 583 -88.97 111
0 -90.00 583 151.03 111
0 -90.00 583 31.03 111
1 Bus1 5 Bus5 729 -88.97 729 -88.97 139
0 -90.00 729 151.03 139
0 -90.00 729 31.03 139
-------------------------------------------------------------------------------
FAULT CONTRIBUTION FROM SHUNT CONNECTION
FROM FROM CURRENT (AMPS/DEGREE) MVA
NODE NAME SEQUENCE (1,2,0) PHASE (A,B,C) PHASE(A,B,C)
MAGNITUDE ANGLE MAGNITUDE ANGLE MAGNITUDE
---- -------- --------- ------- --------- ------- ---------
6 Bus6 18959 91.03 18959 91.03 361
0 -90.00 18959 -28.97 361
0 -90.00 18959 -148.97 361
7 Bus7 52486 90.00 52486 90.00 1000
0 -90.00 52486 -30.00 1000
0 -90.00 52486 -150.00 1000
-------------------------------------------------------------------------------
3 phase fault level
Bus No. Name BUS kV 3PH-fMVA Fault I
NOMINAL kA
------- -------- -------- -------- --------
1 Bus1 110.000 1107.6 5.814
2 Bus2 110.000 737.5 3.871
4 Bus4 110.000 737.5 3.871
5 Bus5 110.000 1107.6 5.814
6 Bus6 11.000 1361.2 71.445
7 Bus7 11.000 1361.2 71.445
-------------------------------------------------------------------------------
-------------------------------------------------------------------------------
From From From Bus-f Line-f To To To Bus-f Line-f
Node Name Rating MVA MVA Node Name Rating MVA MVA
---- -------- ------ ------ ------ ---- -------- ------ ------ ------
6 Bus6 350 1361 361 1 Bus1 5000 1108 667 @#
7 Bus7 350 1361 361 5 Bus5 5000 1108 667 @#
1 Bus1 5000 1108 136 4 Bus4 5000 738 424
2 Bus2 5000 738 424 5 Bus5 5000 1108 136
1 Bus1 5000 1108 136 2 Bus2 5000 738 313
4 Bus4 5000 738 313 5 Bus5 5000 1108 136
1 Bus1 5000 1108 170 5 Bus5 5000 1108 170
Number of instants bus fault level exceeding FROM breaker rating (@ mark) : 2
Number of instants net fault flow exceeding FROM breaker rating (# mark) : 2
-------------------------------------------------------------------------------