You are on page 1of 1

TRA PROJECT

INSULATION THICKNESS
COLD INSULATION

TEMP. PIPE SIZE

(0C) 15 20 25 40 50 65 80 100 150 200 250 300 400 500

-104 ~ -91 100 110 120 130 140 150 160 170 N/A

-91 ~ -81 90 100 110 120 130 140 150 160 N/A

-81 ~ -71 80 90 100 110 120 130 140 150 N/A

-71 ~ -61 80 90 100 110 120 130 N/A

-61 ~ -51 70 80 90 100 120 N/A

-51 ~ -41 60 70 80 90 100 110 110

-41 ~ -31 60 70 80 90 100

-31 ~ -21 50 60 70 80

-21 ~ -11 40 50 60 70

-11 ~ -01 40 50

-01 ~ 10 40 