Professional Documents
Culture Documents
Generator & Exciter Basics: Whitby Hydro Energy Services Corporation: Engineering & Construction Services
Generator & Exciter Basics: Whitby Hydro Energy Services Corporation: Engineering & Construction Services
Exciter Basics
Whitby Hydro Energy Services Corporation: Engineering & Construction Services
The relationship between magnetism and electrical the rate at which the conductor crosses the magnetic
current was discovered and documented by Oerstad in field. The induced voltage has a polarity that will
1819. He found that if an electric current was caused to oppose the change causing the induction – Lenz’s law.
flow through a conductor that a magnetic field was
This natural phenomenon is known as Generator
produced around that conductor.
Action and is described today by Faraday’s Law of
In 1831, Michael Faraday discovered that if a conductor Electro Magnetic Induction: (Vind = ∆Ø/∆t), where
is moved through a magnetic field, an electrical voltage Vind = induced voltage, Ư = change in flux density,
is induced in the conductor. ∆t = change in time
The magnitude of this generated voltage is directly All rotary generators built today use the basic principles
proportional to the strength of the magnetic field and of Generator Action.
GENERATOR ACTIONS
At the instant the loop is in the vertical position, the Three phase voltage is developed using the same
loop sides are moving parallel to the field and do not cut principles as the development of single phase voltage.
magnetic lines of force.
Three (3) coils are required positioned 120 electrical
In this instant, there is degrees apart.
no voltage induced in
A rotating magnetic
the loop. As the loop
field induces voltage
rotates, sides will cut
in the coils which
the magnetic lines of
when aggregated
force inducing voltage
produce the familiar three
in the loop.
phase voltage pattern.
When the loop is in the
horizontal position,
maximum voltage is
induced. The rotation of
the coil through 360
degrees results in an ac
sine wave output
TYPES OF GENERATORS
INDUCTION GENERATORS
The induction generator is nothing more than an The induction generator requires one additional item
induction motor driven above its synchronous speed by before it can produce power – it requires a source of
an amount not exceeding the full load slip the unit leading VAR’s for excitation. The VAR’s may be supplied
would have as a motor. by capacitors (this requires complex control) or from
the utility grid.
Assuming a full load slip of 3%, a motor with a
synchronous speed of 1200 rpm would have a full load Induction generators are inexpensive and simple
speed of 1164 rpm. This unit could also be driven by an machines, however, they offer little control over their
external prime mover at 1236 rpm for use as an output. The induction generator requires no separate
induction generator. DC excitation, regulator controls, frequency control
or governor.
ASP MODEL COMPONENTS
SYNCHRONOUS GENERATORS
Synchronous generators are used because they offer The magnitude of the AC voltage generated is controlled
precise control of voltage, frequency, VARs and WATTs. by the amount of DC exciting current supplied to the field.
This control is achieved through the use of voltage
If “FIXED” excitation were applied, the voltage
regulators and governors.
magnitude would be controlled by the speed of the
A synchronous machine consists of a stationary rotor (E=4.44fnBA), however, this would necessitate a
armature winding (stator) with many wires connected in changing frequency!
series or parallel to obtain the desired terminal voltage.
Since the frequency component of the power system is
The armature winding is placed into a slotted laminated
to be held constant, solid state voltage regulators or
steel core. A synchronous machine also consists of a
static exciters are commonly used to control the field
revolving DC field - the rotor.
current and thereby accurately control generator
A mutual flux developed across the air gap between the terminal voltage.
rotor and stator causes the interaction necessary to
The frequency of the voltage developed by the
produce an EMF. As the magnetic flux developed by the DC
generator depends on the speed of the rotor and the
field poles crosses the air gap of the stator windings, a
number of field poles. For a 60 Hz system, Frequency =
sinusoidal voltage is developed at the generator output
speed(rpm)*pole pairs/60.
terminals. This process is called electromagnetic induction.
Generator Frame: Provides the structural strength and Stator Coil End Turns: Formed when coils leave one slot
rigidity for the generator and serves as a housing to in a stator core and are returned to a different slot
guide cooling air flow Terminal Leads: Serve to conduct the three phase
Inner End Shield: Is a baffle used to form a path for voltage and current flow from the generator stator to
cooled air the external system
Generator Fan: Provides continuous circulation of
cooling air STATOR DESIGN
Rotating Field: A magnetic field which induces AC
The stator frame is fabricated from mild steel plate,
voltage in the stator windings
forming a rigid structure. The core is built up from
Collector Rings: Provide a connection and path for DC segmental laminations of grain oriented silicon steel for
power into the rotating field windings low loss and high permeability. Radial ventilating ducts
Main Coupling: Is the connection to the drive shaft are formed at intervals along the core by steel spacers.
Generator Coolers: Remove heat from the generator The core is hydraulically pressed during the assembly
cooling air operation to ensure uniform compaction. When finished,
it is clamped between heavy steel end plates. The stator
Stator Core: Houses the stationary windings and forms
winding is usually a two layer conventional lap-wound
a magnetic path necessary for induced voltages
design. The insulation is class F (155C)
Air Gap: Is the radial clearance between the rotating
field and the stator core
SALIENT VS CYLINDRICAL ROTOR
There are two (2) basic rotor structures used, depending Salient pole rotors are too weak mechanically and
on speed. develop too much wind resistance and noise to be used
in large, high speed machines.
For low speed machines, such as hydraulic turbines, a
relatively large number of poles are required to produce Cylindrical rotor machines have a relatively uniform air
rated frequency, hence a rotor with salient poles is well gap, therefore, it can be assumed that a cylindrical rotor
suited to this application. Such rotors often have field will produce a uniform air-gap flux regardless of
damper windings (amortisseurs) in the form of copper angular direction.
or brass rods embedded in the pole face, they are
This cannot be said of a salient -pole machine as the air-
intended to dampen out speed oscillations.
gap is much larger between the poles (i.e. along the
For high speed machines, such as steam and gas quadrature axis) than it is at the centres of the poles
turbines, a relatively small number of poles ( 2 to 4 ) are (i.e. on the direct axis).
required to produce rated frequency, hence a cylindrical
rotor is well suited to this application.
GENERATOR COOLING
Depending upon rating and design, the generator stator AIR COOLED GENERATORS
core and windings may be cooled by air, oil, hydrogen or
water. For direct cooled generators, the coolant is in Air cooled generators are produced in two (2) basic
direct contact with the heat producing members such as configurations: open ventilated (OV) & totally enclosed
the stator winding. For indirect cooled generators, the water -to-air-cooled (TEWAC)
coolant cools the generator by relying on heat transfer In the OV design, air is drawn from outside the unit
through the insulation. through filters, passes through the generator and is
For any generator, a failure of the cooling system can discharged outside the generator.
result in rapid deterioration of the stator core In the TEWAC design, air is circulated within the
lamination insulation and/or stator winding conductors generator passing through frame mounted air-to-water
and insulation. heat exchangers.
Problem: Objects can come from external sources or Problem: Primarily a design related problem that
failure of internal components, they can pick up energy affects large (>300Mw) generators which have
from the spinning rotor and do extensive damage insufficient end winding bracing to limit the
movement of end turns.
Prevention: Inspect on a regular basis all internal parts
that are prone to failure or can be dislodged. Prevention: Proper bracing of the end winding is
Inspection tests can be a combination of visual required to limit motion caused by steady state and
inspection along with ultrasonic or magnetic particle transient electromagnetic forces.
tests on rotating components
ROTOR WINDING DISTORTION CONTAMINATION
Problem: Rotor winding distortion caused by poor end Problem: For air cooled machines, dirt and dust cause
turn blocking support design or by foreshortening of tracking which can lead to electrical ground faults.
the rotor coils. Foreshortening is caused by thermal
Prevention: Inspect air filterson a regular basis , the
forces which compress rotor coils.
filters must be checked and cleaned regularly.
Prevention: Proper design of rotor coils and bracing to Polarization index (PI) tests give a good indication of
support the coils under axial load is essential. overall cleanliness of the rotor winding.
Rotors should be tested for turn to turn shorts at
operating speed.
ROTOR VIBRATION
STATOR WINDING VIBRATION Problem: There are many causes, turn-to-turn shorts,
rotor coil foreshortening, electrical grounds,
Problem: Primarily a design related problem that mechanical imbalances, overheating, etc.
affects large (>300Mw) generators which have
Prevention: Comprehensive vibration measuring is effective
insufficient end winding bracing to limit the
combined with a regular maintenance program.
movement of end turns.
Prevention: Proper bracing of the end winding is
STATOR WEDGE LOOSENESS
required to limit motion caused by steady state and
transient electromagnetic forces. Problem: When stator wedges become loose, coils can
vibrate causing insulation wear leading to ground
OVERHEATING faults or turn-to-turn shorts.
Prevention: Inspect on a regular basis tightness of
Problem: Overheating of the rotor or stator can lead to
wedge blocks.
insulation failure, shorting of turns and ground
faults. Overheating can result from blocked
ventilation passages caused by shifting insulation STATOR CORE DAMAGE
components or slot wedges.
Problem: Stator core looseness can occur over time as
Prevention: Inspect on a regular basis to ensure all rotor pre-tensioned through bolts relax. A loose core
wedges are "locked" in place preventing migration results in insulation wear to coils and laminations
and thus blocking of cooling passages. resulting in hot spots and core-to-coil failures.
Prevention: Inspect bolt tightness on a regular basis.
GENERATOR MAINTENANCE
The following tests which should be carried out annually B) INSPECTION ON STATIC EXCITER
in addition to vendor recommended maintenance. • Remove exciter end cover
• Examine condition of diode carrier
A) INITIAL GENERATOR TEST • Examine exciter armature/stator for contamination
• Examine exciter armature/stator for winding wear
• “Megger” rotor winding
• Check pmg magnets for contamination
• “Megger” exciter armature winding
• “Megger” exciter field winding
• Complete polarization index (pi) on main stator
• Check bearing insulation
C) ELECTRICAL CONTROL/PROTECTION PANEL E) ROTOR EARTH FAULT PROTECTOR
• Visually inspect external surfaces of panel • Carry out static checks to confirm operation of
• Complete insulation resistance checks of panel wiring detector
• Check function of all relays • Carry out functional check to confirm operation of
• Check all fuses detector
• Check all lamps
• Check operation of all switches F) SLIP-RINGS AND BRUSH-GEAR (IF FITTED)
• Check operation of panel heaters
• Check all brushes for grade and length
• Run generator; recalibrate avr
• Check condition of brush holders/mountings
• Secondary inject all protective relays
• Check that spring tensions are correct
• Check conditions of slip-rings
D) LINESIDE CUBICLE/NEUTRAL CUBICLE • Check mechanical run-out of slip-rings
• Check condition of main generator terminal bushings • Check cooler and leakage alarms
• Check all busbar/cable connections
• Check ct/vt connections
• Check condition of neutral earthing transformer
• Check condition of neutral earthing resistor
• Check operation of cubicle heaters
• Clean all post insulators and examine for damage
• Carry out insulation check
EXCITOR BASICS
STATIC EXCITERS
EXCITERS
When a generator is used to supply power, it can be When a machine operates in parallel with a power
operated in the following modes: system, the voltage and frequency will be fixed by
• isolated (sometimes referred to as island) mode or the system.
• parallel with a system or other machines. The voltage regulator no longer controls the generator
In both cases, the power (WATTs) supplied at the output voltage.
generator terminals is a function of the fuel supplied to The fuel supply to the prime mover which is controlled
the prime mover, which is controlled by the governor. by the governor determines the power which is supplied
by the generator .