Table 1

MAIN PARAMETERS OF THE SIMULATED SYSTEM


Source Vs=110V, fs= 50Hz
Source impedance R=0.1Ω, L=0.5 mH
Active filter C=30 µF; R=1Ω
L=2.5 mH, C1=C2=3.0 Mf
Vref=Vdc=600v

Load 1 One 6-pulse current source converter bridge:

Firing angle=300 ;

Commutation inductance=3mH

Load 2 One three phase diode bridge:


LDC=300mh; Rdc=20 Ω
Commutation inductance=3mH
Load 3 One three phase diode bridge:
R=50 Ω; C=1000uF
TABLE 2
SHUNT APF SYSTEM & THD DETAILS
Sr. System Details Conventional With Neural With Neural With Neural N/W
No. Techniques N/W Current N/W Voltage Current & Voltage
Controller Controller Controller
THD-I THD-V THD-I THD-V THD-I THD-V THD-I THD-V
(%) (%) (%) (%) (%) (%) (%) (%)
1. Uncompensated System - 25.63 4.1 - - - - - -
(with all three loads
connected at different
time interval)
2. With Load-1 45.29 27.75 - - - - - -
3. With Load-2 34.1 31.63 - - - - - -
4. With Load-3 46.44 27.77 - - - - - -
5. Sin Source Current 1.6 2.93 1.6 2.93 1.62 2.93 1.62 2.93
Strategy-(with all three
loads connected at
different time interval)
6. With Load-1 1.4 4.18 1.27 2.68 1.27 2.68 1.27 2.68
7. With Load-2 1.23 2.51 1.18 1.97 1.18 1.97 1.18 1.97
8. With Load-3 0.88 1.6 0.85 1.3 0.85 1.3 0.85 1.32
9. Const source inst Power 1.5 3.3 1.5 3.3 1.5 3.3 1.5 3.3
Strategy(with all three
loads connected at
different time interval)
10. With Load-1 1.22 2.91 1.22 2.9 1.22 2.91 1.22 2.91
11. With Load-2 1.13 2.35 1.13 2.35 1.13 2.35 1.13 2.35
12. With Load-3 0.81 1.6 0.81 1.6 0.81 1.6 0.81 1.6
13. SRF strategy(with all 1.72 4.11 1.7 4.09 1.76 4.11 1.71 4.09
three loads connected at
different time interval)
14. With Load-1 1.4 4.19 1.41 4.19 1.42 4.21 1.41 4.19
15. With Load-2 1.2 2.5 1.23 2.5 1.37 2.53 1.24 2.53
16. With Load-3 0.88 1.6 0.88 1.6 0.91 1.6 0.89 1.63
17. Sin Source Current – 1.7 4.09 1.7 4.09 1.71 4.09 1.70 4.09
SVM Strategy-(with all
three loads connected at
different time interval)
18. With Load-1 1.4 4.18 1.4 4.18 1.41 4.18 1.41 4.18
19. With Load-2 1.24 2.5 1.24 2.5 1.24 2.5 1.24 2.5
20. With Load-3 0.89 1.6 0.88 1.6 0.89 1.6 0.89 1.61
21. Const source inst Power 1.71 4.09 1.71 4.09 1.71 4.09 1.7 4.09
–SVM Strategy(with all
three loads connected at
different time interval)
22. With Load-1 1.41 4.188 1.4 4.18 1.41 4.18 1.4 4.18
23. With Load-2 1.25 2.52 1.23 2.50 1.24 2.5 1.24 2.5
24. With Load-3 0.89 1.61 0.88 1.6 0.88 1.62 0.88 1.6
Table 3
MAIN PARAMETERS OF THE AIRCRAFT POWER UTILITY
SIMULATED SYSTEM
Source Vs=115V, fs= 400Hz
Source impedance R=0.1Ω, L=0.01 mH
Active filter L=0.25 mH, C1=C2=4.7 µf
Vref=Vdc=400 v

Load 1 One three phase diode bridge: R1=12 Ω

Load 2  One three phase diode bridge: R1=12 Ω


 inductive load of 6KVA(CosѰ= 0.75)
R=5 Ω ; L=1.75mh

Load 3  One three phase diode bridge(1.5KVA) R1=48 Ω


 inductive load of 7.5 KVA(CosѰ= 0.75)
R=5.2 Ω ; L=0.42 mh
 Unbalanced load of 2.5 KVA in resistance R2 of
5.3 Ω.
TABLE 4
SHUNT APF SYSTEM USED WITH ACFT POWER UTILITY SYSTEM &
THD DETAILS
Sr. No. System Details Conventional With Neural N/W
Techniques Current Controller
THD-I THD-V THD-I THD-V
(%) (%) (%) (%)
1. Uncompensated System -(with 9.3 1.53 - -
all three loads connected at
different time interval)
2. With Load-1 4.03 30 - -
3. With Load-2 2.07 20.93 - -
4. With Load-3 0.9 5.14 - -
5. Sin Source Current Strategy- 2.8 1.69 2.74 1.70
(with all three loads connected
at different time interval)
6. With Load-1 2.4 1.66 2.46 1.57
7. With Load-2 2.18 1.66 2.34 1.5
8. With Load-3 0.86 0.96 0.10 0.94
9. Const source inst Power 2.92 1.77 2.89 1.87
Strategy-(with all three loads
connected at different time
interval)
10. With Load-1 2.52 1.49 2.72 4.22
11. With Load-2 2.3 1.47 2.5 5
12. With Load-3 0.64 0.72 0.75 1.03
13. SRF –SVM strategy-(with all 2.68 1.69 2.69 1.52
three loads connected at
different time interval)
14. With Load-1 2.49 1.57 2.5 1.5
15. With Load-2 2.3 1.53 2.3 1.49
16. With Load-3 0.69 0.82 0.69 0.78
TABLE 3
SERIES & HYBRID APF SYSTEM & THD DETAILS

System Details THD-I (%) THD-V (%)


Uncompensated system with 45.29 27.75
Load1
Uncompensated system with 34.1 31.63
Load2
Uncompensated system with 46.44 27.77
Load3
With series APF(load1) 32.47 3.18
(sin fryze voltage strategy)
With series APF(load2) 20.98 2.34
(sin fryze voltage strategy)
With series APF(load3) 36.56 1.54
(sin fryze voltage strategy)
With hybrid-APF-
series – passive(load1) 0.05 0.2
(sin fryze voltage strategy)
With hybrid-APF-
series – passive(load2) 0.13 0.16
(sin fryze voltage strategy)
With hybrid-APF- 0.59 0.60
series – passive(load3)
(sin fryze voltage strategy)