FLEXALEN PIPE CALCULATION FOR SINGLE OR DOUBLE LINES BETWEEN 2 BUILDINGS

FLEXALEN - PREINSULATED PIPE SYSTEMS


This Calculation is made for standard Domestic Water or Conditioned Water in Central Heating Systems OD (DIMENSION) FLOW SPEED 25 mm 1.64 m/sec 0.54 l/sec 45.0 kW 20 K 20 K 44.6 kW 41 315 Pa 43 831 Pa 85 145 Pa 8.0 bar 9.3 bar 0.9 bar 5.5 bar 10.0 C 800 mm 0.80 W/mK 0.1 C 30 m 18 sec 19.61 l

FLEXALEN 600 FLOW/RETURN SYSTEM


SOURCE DELTA T 20 K PUMP 3.9 bar 1.93 m3/h FLOW 80.0 C RETURN 60.0 C 3.00 bar ADDITIONAL PUMP PRESSURE Temperature Pressure loss Dimension C bar OD 80C 60C 30 m 0.41 bar 0.44 bar 25 mm 79.9 C 25 mm 60.1 C

QUANTITY HEAT LOAD SOURCE Delta T (Tf - Tr) USABLE DELTA T USABLE LOAD PRESSURE LOSS FLOW PRESSURE LOSS RETURN PRESSURE LOSS TOTAL Pressure rating t 95C a max. Pressureat Service Temperature Pressure LossFLEXALEN pipes only Reserve Press. Service Temperature at Ground Temp. Trench Depth Lambda soil Temperature Drop Flow Line Trench Length Flow time NET VOLUME

DESTINATION

14/06/2011