Guideline to Set DC Parameter

VIETTEL(CAMBODIA)PTE.,LTD NETWORK OPERATION CENTER


No : /Report-NOC

Set DC Parameter Power AGISSON

1.

BF1 =Batt.ery fuse 1

Batt. = Batt.ery Curr. = Current DC = Direct current LVD = Low Voltage Disconnect or Low Voltage Directive LLVD = Load Low Voltage Shut-Down BLVD = Batt.ery Low Voltage Differential Signaling

2.

Parameter Setting
PMU CPMU 01 RUN ALM
Cancel Enter

-Enter : Log into System and Set OK -Arrow Key UP : Go Up -Arrow Key Down : Go Down -Back : Escape or Go back

Power Training

Guideline to Set DC Parameter

2.1 Batt.ery Capacity Setting 2.1.1 Enter |Setting | Batt.ery Setting | Batt. Selection |Batt. String: Cap1, Cap2

BF1

BF2

2.1.2

a) Batt. String :1 Cap. 1 : Cap.2 :0Ah

DC BF1.

2.1.3

a) Batt. String: 2 Cap 1: 2.1.4

BF2. DC BF1,

Cap2 :
DC

, BF2 BF1

a) Batt. String: 2 Cap 1:


1 2 3

Cap2 :
4

MAIN MENU Status

Maintenance
Settings

Settings DC Setting Batt Setting AMB . Setting

Batt Settings Batt Selection LVD Setting Charge

Batt Selection Batt String : Cap 1 : ...Ah Cap2 : ...Ah

Power Training

Guideline to Set DC Parameter

2.2

: 0.10C

2.2.1
1

Enter | Settings | Batt. Setting | Charge | Curr Limit: 0.10C


2
Setting DC Setting Batt. Setting AMB. Setting

3
Batt Settings Batt Selection LVD Setting Charge

4
Float: 53.5V Boost: 56.4 CysBC Duration 60days

MAIN MENU Status Maintenance Settings

Curr Limit 0.10C10

2.3

2.3.1

Alarm
1

Enter |Settings |DC Setting |Under Volt:47.5V


2 3 4

MAIN MENU Status Maintenance Setting

Settings DC Setting Batt Setting AMB. Setting

DC Settings Over Volt : 58.0V Under Volt : 47.5V

Power Training

Guideline to Set DC Parameter

2.4 Alarm 2.4.1


1
MAIN MENU Status Maintenance Settings

Enter | Settings | Batt. Setting | LVD Setting | LLVD 43.2V > BLVD 43.2V
2
Settings DC Setting Batt Setting AMB. Setting

3
Batt Settings Batt Selection LVD Setting Charge

4
LLVD: 43.2V BLVD: 43.2V