You are on page 1of 2

Tower Broad Dimension Check:The following dimensions shall be checked as per the erection drawing so as to ensure the overall

dimension of Tower geometry and Electrical clearances as well. Description Tower Base Dimension at a) 0M Level b) +3 m Extension Level c) +6 m Extension Level d) +9 m Extension Level Hamper Width a) Bottom Cross Arm b) Top Cross Arm Cross Arm Projections a) Bottom Cross Arm b) Middle Cross Arm c) Top Cross Arm Distance Between Earth wire Peaks Distance Between Earth wire Peaks and Top Cross Arm Width of Box Cross Arm a) Bottom Cross Arm b) Middle Cross Arm c) Top Cross Arm Hight of Bottom Cross Arm from 0M Tower Level Distance Between Bottom Cross Arm to Middle Cross Arm Distance Between Middle Cross arm to Top Cross Arm Any other Dimension Right 4700 4759 5027 15200 5112 Values as per Tower drawing 1 15000 17838.0463 (MM) Observed Value (MM) 15000 17840 Remark s

Sl.No.

5800 3946 Left 4700 4759 5027 Right 4700 4759 5027 Left 4700 4759 5027

4 5 6

15200 5111

5800 4890 3945 20509

5800 4890 3945 20510

6466.32

6462

9 10

6366.06 -

6365 -

MEASUREMENT OF DIMENSIONS OF SECTIONS :The measurement such as width of flanges, Thickness, length of angle sections and plates should be taken and matched with Bill of material(BOM)/Shop drawing. Those measurements shall be done for specially Leg, Bracing, Horiontal, Load bearings redundants etc and should be tabulated for members having deviations more than the allowable. Section Size as per drg. Drawing No. Mark Nos Leg Length Section Size as per proto assembly Leg Length Thickness Leg Length With in tolerance Limit as per BSEN 10056

Thickness

Length

Corrective action taken

225XH,225H 233X,233Y,247X,247Y 290XH/290H 110H 533H

110 150 120 200 200

10 10 10 16 20

110 150 120 200 200

9 12 8 15 19

Note: The joint connection at top x-arm part-P2 the joint view P-P,R-R, X-X, Y-Y is not same with drawing similarly it is different in the middle x-arm and bottom x-arm but the members are fully connected at the joint. Note: The bolt diameter is about similar as drawing. In a same joint the bolt length is different in much location we think it may be questionable by inspector. Therefore major quantity of the bolts length is different than the drawing bolts length.