You are on page 1of 7

Pipe Thickness Calculation (Internal Pressure Design

Thickness) as per ASME B31.3


whatispiping.com/pipe-thickness-calculation-per-asme-b31-3

Rehan Ahmad Khan

Pipe wall thickness calculation is one


of the important basic activities for every
piping engineer. Process plants deal with
the fluids which flow inside the pipe at
high-pressure and temperature. So, the
pipe deals with high circumferential
pressure which can cause the bursting of
the pipe if the pipe thickness is not
enough. Hence, The designers need to
find out the required piping
thickness as per section “304.1.2 of
ASME B31.3” to resist the internal line pressure. The operation must be leak-
free. In this article, I have simplified the pipe thickness calculation procedure. A
sample pipe wall thickness calculation problem is discussed mentioning the
calculation steps. Process Piping Code ASME B 31.3 is used as the basis for the
Pipe thickness calculation.

Few Important Points required for Pipe thickness Calculation


Before starting the piping thickness calculation, the engineer should be aware of
the following points:

Process plants are designed for 20 years or 7200 cycles. (Considering 1 cycle per
day; Total no of cycles in 20 years=20*360=7200 cycles)
Pressure and temperature can vary from line to line and from time to time.
Fluid could be corrosive and toxic in the system.
Corrosion allowance for ferritic mostly taken 3 mm and zero mm for austenitic
steel.
Mill tolerance for the seamless pipe is 12.50% and 0.3 for the welded pipe.

How do I Calculate Pipe Thickness?


Let’s consider the following details for the pipe thickness calculation of a seamless
Carbon Steel pipe.

MOC (Material of Construction) of the pipe – A106 Gr. B


NPS (Nominal Pipe Size) – 4”
Manufacturing type of the pipe (SMLS, EFW, ERW) – Seamless (SMLS)
Design Pressure (PSI) – 1200 PSIG
1/7
Design Temperature – 500° F
Mechanical, corrosion and erosion allowances – 3 mm
Mill Tolerance – 12.50% of the thickness

Pipe Wall Thickness Calculation Formula


As per clause 304.1.2 (a) of ASME B 31.3, the internal pressure design
thickness for straight pipes with t<D/6 can be calculated using the
following formula (Equation (3a):

Fig. 1: Internal Pressure Design Thickness Equation per ASME B 31.3

Here,

P: Internal Design Gage Pressure=1200 PSIG as per problem definition

D: Outside Diameter of the pipe


The equation for the pipe wall thickness is based on the outside diameter of
pipe, rather than the inside diameter. This is because the outside diameter
of pipe is constant, it is independent of the wall thickness. Hence, the pipe
wall thickness can directly be calculated easily using the pipe outer
diameter.

Outside diameter has to be taken from the below standards-

ASME B36.10M: for ferritic steel (seamless & welded wrought steel pipes).
ASME B36.19M: for austenitic steel (stainless steel pipes)

2/7
Fig. 2: Outside Pipe Diameter from ASME B 36.10M

So from Fig. 2, D= 114.3 mm

S: Allowable Stress value of the Pipe Material (A 106-B) at Design


Temperature (500° F)
Refer to Table A-1 (or Table A-1M) of the ASME B31.3 (Fig. 3) for getting the
value of the allowable stress. Travel in the horizontal (x) direction for allowable stress
value and vertical (y) direction for pipe material, and the match point to get the value
(refer to Fig. 3). If required, use interpolation to calculate the middle value.

Note: the value of the allowable stress in Table A-1 is given in KSI, So we need to
convert the value in PSI.

3/7
Fig. 2: Allowable Stress Value from Table A-1 of ASME B31.3

As per Fig. 3, the allowable stress for ASTM A106 Gr.B is 19,000 psi at 500°F.

E: Quality factor
Quality Factors are used in Pressure Design and applied at Longitudinal
and Spiral Weld Joints and for Castings. The maximum Value of quality
factors is 1.0.

The value of E, Longitudinal Weld Joint Quality Factor, or Casting Quality Factor can
be found in Table A-1A or Table A-1B of the ASME B31.3. The weld joint factor (E)
is 1 for our problem case (Refer to Fig. 4).

4/7
Fig. 4: Quality Factor for Longitudinal Weld

W: Weld Joint Strength Reduction Factor


As per section 302.3.5(e) of ASME B31.3, The weld joint strength reduction
factor, W, is the ratio of the nominal stress to cause the failure of a weld
joint to that of the corresponding base material for an elevated
temperature condition of the same duration. It only applies at weld
locations in longitudinal or spiral (helical seam) welded piping
components.

Weld Joint Strength Reduction Factors are used because at elevated


temperature the weld joint creep rupture strength can be lower than the
base metal.

The value of W can be found from Table 302.3.5 of ASME B 31.3 (Refer to Fig. 5) and
for our problem the value of W=1

Fig. 5: Weld Joint Strength Reduction Factor

Y: Values of Coefficient from Table 304.1.1,


The factor “Y” depends on temperature. At elevated temperatures, the
factor Y increases leading to a decrease in the calculated required pipe wall
thickness.

Refer to Table 304.1.1 of ASME B31.3 for finding the value of Y, It is Valid for t
< D/6 and materials shown below The value of Y may be interpolated for intermediate
temperatures. For material A106 Gr. B, Y is given 0.4 (refer to Fig. 6)

5/7
Fig. 6: Values of Coefficient Y

Pipe Thickness Calculation Steps


Step 1. Put the above values in the equation shown in Fig. 1

t=(1200*114.3)/{2(19000*1*1+1200*0.4)}=3.52 mm; Hence calculated


thickness (t)= 3.52 mm

Step 2. Add the corrosion to the calculated thickness.

t c = t + c = 3.52 + 3
tc = 6.52 mm

Step 3. Add the mill tolerance to the thickness after adding corrosion value.

t m = tc + 12.50 % of the pipe thickness


tm =tc/0.875 =6.52/0.875 = 7.45 mm (This is required thickness)

Step 4. Check the next Ordering thickness available in ASME B36.10M


considering the required thickness.

6/7
Fig. 7: Dimensions and weights of Steel Pipes

So from Fig. 7, The Ordering thickness is 8.56 mm or Schedule 80.

Note:
1. Ordering thickness for seamless pipe will always be the next greater value available
from Schedule to schedule.
2. Whereas for welded pipe any next greater value will be the ordering thickness.
3. Extra thickness can be calculated by ordering thickness minus the required thickness
= (8.56 – 7.45) = 1.11 mm.

Use of the Extra thickness available in the pipes


for calculating the life of a pipe after 20 years.
For calculating maximum pressure holding capacity of the pipe.
For checking extra thickness is sufficient to take care of thinning, if the same pipe
is used for manufacturing the bend.
The extra thickness also minimizes deflection and reduces the number of support.
To compare with flange pressure holding capacity, to declare pipe is stronger than
the flange.

Few more useful Resources for you.

Pipeline wall thickness calculation with example

Meaning of Pipe Schedule / Schedule Numbers?


Piping Layout and Design Basics
Few Job Opportunities for you

7/7

You might also like