Technical Requirements 1) Transformer

SN. 1 Technical Particulars Maximum continuous rating at reference : Parameters 2.00 MVA X 2 Remarks As per Approval guidelines 4MVA Power required for auxiliary system. For reliability point of view 2MVAX2 transformer has been selected. In cost point of view no much difference between 4MVA X1 transformer and 2MVAX 2 transformers. Standard Standard AS per available power supply by WBSEDCL. As per site requirements. As per agreement of WBSEDCL

2 3 4 5 6

7 8

Frequency : No. of phases : Rated primary Voltage on primary side: Rated secondary Voltage : Winding connections: a) HV side : b) LV side : c) Vector group reference : Type of cooling : Percentage impedance at normal voltage & 75 deg.C average winding temp.(on 20 MVA base) between HV-LV. a) At normal tapping : b) At max.tapping (+5%): c) At min.tapping (-15%): d)Tolerance of all tap: ON Load circuit tap changer:

50 Hz 3 phase 33 KV 11 KV Delta Star Dyn11 ONAN 2.00MVA Transformer

Easy to available ,simple in construction ,reliable, cost effective

10 11

Neutral unbalance current: Type of terminal :

12

13

Max.current density in all parts: of HV and LV windings including tapped winding. Bushing metal part for HV & LV bushing. :

5.25% 4.95% 5.87% +-10% Having 16 equal steps (17 positions) of 1.25% of each to have voltage variation of +5% to -15% on HV side. Not exceeding 2.0% Vertical takeoff type suitable for XLPE Cable /ACSR Raccoon/ Dog/Panther conductor on both sides. 2.5Amp./Sq.mm

M -20 size (copper/brass)

For easy assembly and reliably.

2)33KV VCB:SN. 1. 2. 3. 4. 5. 6. 7. 8 9 Technical Particulars Voltage Isolation level Breaking Capacity Making capacity Closing coil Voltage Opening coil Voltage Charging motor Supply Insulation Level Parameters 36000Volt,50Hz Horizontal 26.3KA for 3 sec. 62.5KA 110 Volt DC 110 Volt DC 230 Volt AC 70KV in Average & 170 KV in Peak Remarks Standard Easy to operate and draw out. As per standard availability