QZMU
Change-over relay Start/Stop function 6 Time ranges
Description Functions Ud = Change-over function (beginning with interval) Time Ranges 0,1 99,9s 1 999s 0.1 99,9m 1 999m 0,1 99,9h 1 999h Power Supply 24-48VAC/DC 115VAC (Transformer) 230VAC (Transformer) U1 (12- 72VAC/DC) U2 (80-240VAC/DC) Control Methods Power supply Function
s d
Terminal Designations
14 12 34 32
11
31
Programming
Operating LED Output terminal Range adjustment Time range selection t1
Range adjustment t1
t1
t2
t1
t2
Ud-Function: When s closes d is energised after completion of the time period t1 and remains energised for the time period t2. This cycle repeats itself until s opens. When the relay is controlled by the power supply the relay is de-energised instantaneously when s opens. If the control is by means of an external contact the time already started is first completed.
Range Adjustment t2
Bircher AG SafeTec
CH-8222 Beringen
Phone ++41(0)52-687 11 11
Fax++41(0)52-687 12 10
ZR/37
Control Methods
Technical Data Timing Characteristics Time adjustmen Adjustability Repeat accuracy Temperature stability Voltage stability Voltage Characteristics Voltage variation <100V >100V Frequency Galvanic isolation Control Recovery time Resetting time Min.activating time Cable impedance Output Type Load capacity Display Operation Display Operating temperature Storage temperature Power consumption Order Information digital 1 digit 0,01% or 10ms 0,001%/C 10ms 0,01% or 10ms
Un s
A2
A1
21
22
24
20% 20%/+10% 50/60Hz >100V, U1,U2 >60ms >50ms >40ms <100 Ohm Relay 2 C/O 250VAC; 6A ohmic LED yellow LED green 20C to +60C 20C to +80C max. 4VA
Controlled by potential-free contact for Start/Stop function (In order to use the start/stop function the wire bridge in the lower part of the relay must be interrupted).
ZR/38