PERBANDINGAN SIMULASI ALIRAN DAYA ETAP HADI SAADAT

Sistem tenaga listrik 5 bus 10 kV. Impedansi saluran dalam per unit dengan base 100 MVA.
Mvar Limits 0.0 150 Mvar P1=200 MW 1 j0.05 |V1|=1.02 2 j0.05 4 100 MW 50 Mvar j0.04 j0.03 5 300 MW 150 Mvar Slack Mvar Limits 0.0 200 Mvar P2=150 MW 3 V3 = 1.02

|V2|=1.030

j0.025

SIMULASI HADI SAADAT

SIMULASI ETAP

HASIL SIMULASI ETAP (ONE LINE DIAGRAM)

HASIL SIMULASI ETAP (TABEL)

HASIL SIMULASI HADI SAADAT

PERBANDINGAN TEGANGAN ETAP HADI SAADAT


BUS 1 2 3 4 5 ETAP V(pu) 1,02 1,03 1,02 0,98233 0,97593 0,4 0,0 -2,2 -4,5 -6,1 HADI SAADAT V pu) 1,02 1,03 1,02 0,982 0,976 0,406 0,000 -2,176 -4,467 -6,1466

PEMODELAN BEBAN
Constant Power Load Constant power loads include induction motors, synchronous motors, conventional and unbalanced lumped loads with % motor load, UPS, and chargers. The power output remains constant for all changes in input voltage. Below are the respective I-V and P-V curves for a constant power load:

Constant Impedance Load Constant impedance loads include static loads, capacitors, harmonic filters, MOV, and conventional and unbalanced lumped loads with % static load. The input power increases proportionally to the square of the input voltage. Below are the respective I-V and P-V curves for a constant impedance load:

Constant Current Loads Constant current loads include unbalanced lumped loads with % constant current load. The current remains constant for all changes in voltage. Below are the respective I-V and P-V curves for a constant current load: